avoid mounting ballast close to heat source such as fixture cover plate.
Correct Incorrect Power Wiring
Lamp Lamp
Ballast
Ballast Power Input EcoSystemR Link can be Class 1 or
(Line Voltage): IEC PELV/NECR Class 2:*
NEU. DH SH E1 E2
Lamp
* NOTE: IEC PELV/NECR Class 2 must be separated
Side by side mounting Ballast from Class 1 and line voltage wiring by the
following: 0.25 in (6 mm) or physical barrier. Please
Ballast
Lamp
refer to App Note #142 for further information.
Must be at least 6 in (150 mm) apart.
Ballast
EcoSystemR Link Wiring
Ballast
Balasto
Wire Gauge Digital Link
Lamp Optional for
EC5 & EC3D only Length (max)
Ballast 18-16 AWG 18-16 AWG
(0.75 to 1.5 mm2) (0.75 to 1.5 mm2) 12 AWG 2200 ft
solid copper solid copper 14 AWG 1400 ft
16 AWG 900 ft
Ballast must be electrically grounded for To the EcoSystemR 18 AWG 550 ft
proper performance and to meet UL® & NEC® Link & up to 64 total
ballasts Wire Gauge Digital Link
requirements. Grounding should be
accomplished with paint piercing mounting Ballast Length (max)
hardware to ensure electrical connection Terminals 4.0 mm2 828 m
through ballast enclosure and through fixture. 2.5 mm2 517 m
Ballast 1.5 mm2 310 m
1.0 mm2 207 m
E1
HOT
DH
NEU
E2
E1
HOT
DH
NEU
E2
Bus Bus
0.75 mm2 155 m
Class 2
Line Class 2
Line
When installing more than one ballast in a fixture, contact Lutron Technical
Support at 1.800.523.9466 for specific guidelines to maximize performance.
Sensor Wiring
Lamp Mounting Height Requirements: Sensor Wiring IEC PELV/NECR Class 2 (EC5 only):
+20 V COM IR OCC DAYLIGHT
Lamp Type Lamp Mounting Height 22 AWG (0.25 mm2) solid wire. Do not exceed 100 ft (30 m)
from sensor to ballast.
T8 Linear 1/8 in to 3/4 in (3.2 mm to 19.1 mm) Connect only one sensor per input.
Wire sensors to one ballast only.
T5 Linear 1/16 in to 3/8 in (1.6 mm to 9.5 mm) * NOTE: Sensor wiring only applies to EcoSystemR Ballasts.
EcoSystemR compact, Hi-lumeR 3D, and H-Series ballasts do not
T5 TwinTube 1/16 in to 1/2 in (1.6 mm to 12.7 mm) have connections for sensors.
22 AWG (0.25 mm2) solid * NOTE: IEC PELV/NECR Class 2 must be separated from Class 1 and
line voltage wiring by the following: 0.25 in (6 mm) or physical barrier.
IMPORTANT: Lamp Socket Please refer to App Note #142 for further information.
Lamp (side view)
Lamps must never
Mounting height G–can with daylight sensor J–can with occupancy sensor G–can with wallstation
touch ground plane Red Red Red
and should be placed Grounded Black White White
Ballast metal Black Black
without obstruction. White
Orange
Black Blue/ White
Orange
Black
Yellow Gray
E1 E1
Warranty E2 E2
Lutron, EcoSystem, Hi-lume, and the Sunburst logo are registered trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. UL is a registered
trademark of Underwriters Laboratories, Inc. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. The VDE Mark is registered, protected and recognized as a safety mark in
more than 30 countries. The ENEC Mark is registered by the signatories in their own country.
Lutron Technical Support Hotline 1.800.523.9466 www.lutron.com 041-308a 09/2011