Model YST
Centrifugal Liquid Chiller
Design LEvel F and G
LD12189
Issue Date:
April 1, 2015
FORM 160.67-O2
ISSUE DATE: 4/1/2015
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Unit Installation Manual 160.67-N2
OptiViewTM Control Center - Operation Manual 160.67-O1
Wiring Diagram - Model YST (Style F) 160.67-PW6
Renewal Parts - Unit 160.67-RP1
Renewal Parts - Controls and Instrumentation 160.67-RP2
JOHNSON CONTROLS 3
FORM 160.67-O2
ISSUE DATE: 4/1/2015
NOMENCLATURE
The model number denotes the following characteristics of the unit.
1. Steam Turbine- Smaller capacity YST chillers are 3. Hot Well Pump and Vacuum Pump for Steam Sys-
fitted with a Murray Turbine design, K2G or KG, tem- Single pumps for both is the standard selec-
which will be referred to in this manual as KG. tion. An option for dual pumps, (for standby) on
The larger units include a larger Murray Turbine both hot well and vacuum service is available.
design, KD. The speed control for the two turbine Be sure to note which variation is fur-
designs are similar but mechanically the two mod- nished with your system and be guided by
els are different not only in size and capacity but the sections that follow in this instruction
also notably the lubrication system design which booklet.
is covered further in this document.
2. System Starting- The YST Chiller is available
in two different starting configurations, namely
manual and automatic. Both are covered in this
document.
4 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
TABLE OF CONTENTS
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION......................................... 11
General System Description............................................................................................................................ 11
Refrigeration System Operation...................................................................................................................... 12
Capacity Controls............................................................................................................................................ 12
Steam and Condensate Flow.......................................................................................................................... 15
JOHNSON CONTROLS 5
FORM 160.67-O2
ISSUE DATE: 4/1/2015
6 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 7
FORM 160.67-O2
ISSUE DATE: 4/1/2015
SECTION 6 - MAINTENANCE.................................................................................................................................73
Renewal Parts................................................................................................................................................. 73
Checking System For Leaks........................................................................................................................... 73
Leak Testing During Operation............................................................................................................... 73
Evacuation And Dehydration Of Unit............................................................................................................... 73
Conducting R-22 Pressure Test...................................................................................................................... 74
Vacuum Testing............................................................................................................................................... 74
Vacuum Dehydration....................................................................................................................................... 74
Operation......................................................................................................................................................... 75
Refrigerant Charging....................................................................................................................................... 75
Checking The Refrigerant Charge During Unit Shutdown............................................................................... 76
Handling Refrigerant For Dismantling And Repairs.........................................................................................76
Refrigerant Condensers And Evaporators....................................................................................................... 76
General...................................................................................................................................................76
Chemical Water Treatment.............................................................................................................................. 76
Cleaning Evaporator And Condenser Tubes................................................................................................... 76
Evaporator..............................................................................................................................................76
Condenser..............................................................................................................................................76
Tube Fouling.................................................................................................................................................... 76
Tube Cleaning Procedures.............................................................................................................................. 77
Brush Cleaning of Tubes........................................................................................................................ 77
Acid Cleaning Of Tubes..........................................................................................................................77
Commercial Acid Cleaning.............................................................................................................................. 77
Testing For Evaporator And Condenser ......................................................................................................... 77
Tube Leaks.............................................................................................................................................77
Compressor Maintenance............................................................................................................................... 78
Steam Condenser Condensate Pump Maintenance....................................................................................... 78
Steam Condenser Vacuum Pump Maintenance.............................................................................................78
Turbine Internal Inspection.............................................................................................................................. 78
Check The Casing Interior For Foreign Material Before Closing..................................................................... 80
Electrical Controls........................................................................................................................................... 80
Notes.....................................................................................................................................................................89
8 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
LIST OF FIGURES
Figure 1 - Model YST Chiller������������������������������������������������������������������������������������������������������������������������������� 11
Figure 2 - Compressor Prerotation Vanes������������������������������������������������������������������������������������������������������������12
Figure 3 - Refrigerant Flow - Thru������������������������������������������������������������������������������������������������������������������������14
Figure 4 - Steam And Condensate Flow �������������������������������������������������������������������������������������������������������������16
Figure 5 - Steam Condenser Hotwell Level Switches������������������������������������������������������������������������������������������17
Figure 6 - Slow Roll Time calculation�������������������������������������������������������������������������������������������������������������������27
Figure 7 - Operation Sequence Timing Diagram (Manual Start)�������������������������������������������������������������������������29
Figure 8 - Operation Sequence Timing Diagram (Automatic Start)���������������������������������������������������������������������30
Figure 9 - Liquid Chiller Log Sheets���������������������������������������������������������������������������������������������������������������������44
Figure 10 - System Components�������������������������������������������������������������������������������������������������������������������������49
Figure 11 - Schematic Drawing – (YST) Compressor Lubrication System����������������������������������������������������������51
Figure 12 - KD & KG Turbine Drawing�����������������������������������������������������������������������������������������������������������������54
Figure 13 - O
verspeed Protection Knob Assembly����������������������������������������������������������������������������������������������60
Figure 14 - Oil Return System�����������������������������������������������������������������������������������������������������������������������������63
Figure 15 - Charging Oil Reservoir With Oil���������������������������������������������������������������������������������������������������������64
Figure 16 - Standard Single Oil Filter And Optional Dual Oil Filter����������������������������������������������������������������������65
Figure 17 - Dual Oil Filter Isolation Valve�������������������������������������������������������������������������������������������������������������66
Figure 18 - Evacuation Of Chiller�������������������������������������������������������������������������������������������������������������������������73
Figure 19 - Saturation Curve��������������������������������������������������������������������������������������������������������������������������������75
LIST OF TABLES
Table 1 - Recommended Maximum Turbine Bearing, Oil Sump, And Metal Temperatures���������������������������������66
Table 2 - Refrigerant Charge Level����������������������������������������������������������������������������������������������������������������������68
Table 3 - Operation Analysis Chart�����������������������������������������������������������������������������������������������������������������������71
Table 4 - System Pressures���������������������������������������������������������������������������������������������������������������������������������73
Table 5 - Turbine Tightening Torques (Without Washers)�������������������������������������������������������������������������������������80
Table 6 - Turbine Tightening Torques (With Washers)������������������������������������������������������������������������������������������80
Table 7 - Recommended Limits For Boiler Water (Based On Drum Water Analyses).�����������������������������������������87
Table 8 - SI Metric Conversion�����������������������������������������������������������������������������������������������������������������������������88
JOHNSON CONTROLS 9
FORM 160.67-O2
ISSUE DATE: 4/1/2015
10 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
ATMOSPHERIC RELIEF
VALVE HOTWELL PUMPS
GOVERNOR VALVE
STEAM CONDENSER
PACKAGE
STEAM TURBINE
VACUUM PUMPS
CONDENSER
COMPRESSOR
CONTROL CENTER
POWER PANEL
HOT GAS BYPASS
VALVE
EVAPORATOR
Figure 1 - Model YST Chiller
JOHNSON CONTROLS 11
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
be air conditioning terminal units and/or central sta- Figure 2 - Compressor Prerotation Vanes
tion air handling units and/or other equipment requir-
ing cooling. The warmed liquid is then returned to the
Speed is controlled automatically by a pneumatically
chiller to complete the chilled liquid circuit. The con-
actuated governor valve which throttles the inlet steam
denser water is supplied from a cooling tower system
flow to the turbine to maintain the speed dictated by
or sometimes other sources of water suitable for con-
the capacity control logic.
densing service.
The position of the compressor prerotation vanes is
The chiller is controlled by a modern state of the art
automatically controlled through a lever arm attached
Microcomputer Control Center that monitors its opera-
to an electric motor located outside the compressor
tion. The Control Center is programmed by the opera-
housing. The automatic adjustment of the vane posi-
tor to suit job specifications. The chiller control panel
tion in effect provides the performance of many differ-
provides control of entire system, including turbine
ent compressors to match various load conditions from
and steam condenser operation and monitoring.
full load with vanes wide open to minimum load with
12 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
vanes completely closed. The combination of speed sure to maintain stable operation. The hot gas bypass
control and PRV control will provide capacity reduc- valve is then modulated to admit condenser gas into the 1
tion from 100% to 15% of design for normal air condi- evaporator and reduce the cooling effect as required.
tioning applications. This will maintain a constant leaving chilled liquid
temperature with loads down to 10% of design.
If the tower water temperatures must be held above
75ºF for other chillers on the same tower circuit, the
capacity control logic can be programmed to automati-
cally limit the amount of speed reduction and PRV clo-
JOHNSON CONTROLS 13
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
LEGEND
HIGH PRESSURE VAPOR
DISCHARGE
HOT GAS
BYPASS VALVE
CONDENSER
SUCTION
ELIMINATOR
SUB-COOLER
EVAPORATOR
LEVEL CONTROL
LIQUID LEVEL REFRIGERANT
VALVE
SENSOR DRAIN AND CHARGING
CONNECTION
LD09466
14 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 15
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
GOVERNOR
LD12547
Figure 4 - Steam And Condensate Flow
16 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
Level Transmitter
7.5
5.5
Oper.
Level
7.5 5.5
JOHNSON CONTROLS 17
FORM 160.67-O2
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 4/1/2015
18 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 19
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
loose material in the piping. Piping should be allowed Inspect And Clean The Turbine
to cool down to room temperature, about 6-8 hours.
Before a turbine is operated, certain parts must be
Thermal expansion and contraction, which occurs dur- cleaned to remove the effects of transit and storage.
ing warming up and cooling down, helps break loose Protective mylar sheets installed between the journal
the foreign material inside the piping. Hammering bearing and the shaft journal MUST BE REMOVED
around any welded joints in the piping will also help to PRIOR TO ROTATING THE SHAFT. (See FLUSH
break loose foreign material THE TURBINE LUBE SYSTEM below for instruc-
tions) Bearing caps are easily removed. The interior of
The above procedures of warm-up, blow-down and the bearing cases must be inspected for dust or other
cool-off should be repeated as many times as neces- grit. If any is present, the interior of the bearing cases
sary to clean all foreign materials out of the piping. To must be flushed with kerosene or similar solvent.
check for clean piping, a target should be placed about
two feet away from the blow-down opening so that the Mechanical governor parts should be thoroughly
steam will hit the target, and any solids in the steam washed with a spray of non-acetate solvent to remove
will become embedded in the target. Plywood, alumi- adhering dust particles. The interior of the turbine cas-
num and polished stainless steel are commonly used ing should be thoroughly cleaned so the exhaust sys-
target materials. Piping can be considered clean when tem will not become contaminated with dirt. This can
no embedded particles and indentations are found in be done easily with a water hose through the exhaust
the target after a 15 second blow-down. opening. Valve stems and other exposed machined
surfaces should be cleaned with solvent to remove pro-
Pieces of weld metal, large pieces of scale,
tective grease and/or dirt.
nuts, and other materials are commonly
present in newly erected steam lines. For Exposed machined parts have been masked prior to
that reason it is necessary to emphasize painting. This masking serves as added protection
the importance of blowing out all steam during shipment and is not removed before shipping.
lines with live steam before connecting MASKING SHOULD BE REMOVED DURING THE
the turbine. Failure to do so may result CLEANING PROCEDURE.
in damage to the strainer or more serious
damage such as bent or failed blades. All loose parts (such as loose piping, etc.) should be
cleaned and installed. Turbines packed for export, or
protected for long storage periods may need to be com-
Inspect And Clean Steam Strainers
pletely dismantled and cleaned to remove all protective
The turbine on the standard YST chiller has a built-in grease and flushing compound. YORK will provide
type of strainer. This strainer should be inspected and specific instructions for turbines requiring complete
cleaned periodically and checked for possible damage. dismantling.
A steam strainer affords some measure of protection
against foreign material passing through the nozzles Flush The Turbine Lube System
and blades, but it cannot be expected to stop heavy ob- (Pressure Lubrication Turbine Only)
jects that move through the steam line at high velocity. Flushing the oil circulation system on a turbine sup-
The element of the steam strainer in the steam line up- plied with an auxiliary oil pump is recommended be-
stream of the governor valve should be inspected pe- fore starting a new turbine (or one that has been in stor-
riodically, and cleaned if necessary, to avoid excessive age for a long time). On a new turbine, remove the
steam pressure drop due to a clogged strainer screen. mylar protection that stabilizes the shaft during ship-
Large pressure drops may not only reduce the turbine ment. To do this, remove the upper half of the bearing
load carrying capacity, but may result in a rupture of housing, remove the upper half of the bearing and re-
the strainer element. move all (above and below) pieces of mylar protection
(above and below) from the shaft. This must be done
Inspect And Clean Water Strainers at both the steam and exhaust end bearings. Leave the
upper halves of both bearings out to allow for more
Any strainers in the water inlet lines for the compres- volume of oil to flow during the flush. Reseal the up-
sor oil cooler, turbine oil cooler (if supplied), and the per bearing housing cover and replace the bolting.
steam condenser vacuum pump sealing water should
be inspected and cleaned periodically and checked for
possible damage.
20 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Once the mylar has been removed and you are ready Ring Oil Lubrication
to begin the oil flushing procedure, the following steps
The oil level gauge on the side of the bearing
should be followed:
housing indicates the oil level. A mark inscribed
1. BUMP test the auxiliary oil pump to ensure that on the lower-half bearing housing indicates the 2
the pump is rotating in the proper direction as in- proper oil level. Oil levels in both bearing hous-
dicated by the rotation arrow on the pump. While ings should be checked daily. Always use a strain-
viewing the TURBINE SCREEN on the OptiV- er when adding oil to the systems and cover the
iew™ Control Center, use the Manual Pump key fill connection when finished. If there is any rea-
and enable manual operation. Place the pump mo- son to suspect water in the oil, open the low point
tor protector disconnect switch (OL2) in the Pow- drain in each bearing housings slightly. If water
er Panel in the ON position and immediately back is present, it will be the first thing to come out of
to the off position after the pump starts. the drain. Low point drains in the bearing housing
should be checked weekly for water.
2. Install 100 mesh plain weave (.0059 opening)
screen mesh ahead of all bearing cases. The presence of oil in the constant level
oilers does not necessarily mean that oil
3. Place the auxiliary oil pump motor protector dis- in the bearing housings is at the proper
connect switch (OL2) in the Power Panel in the level. Cleanliness is essential
ON position to start the auxiliary oil pump and for long and trouble free service from the
allow it to run for two hours. Using the Manual bearings. Care must be taken to ensure
Pump key on the TURBINE SCREEN, shut down that no foreign material enters bearing
the pump and check all screens for particles. housings or constant level oilers when
Screens should not have any particles bigger than performing maintenance, checking oil,
.01 inch in diameter and show random distribu- adding oil, or making adjustments.
tion. No metallic particles should be present.
Flushing should continue until screens show no Check The Coupling And Alignment
more than 6 non-metallic particles.
If any maintenance or repairs have been performed on
4. Replace screens with new ones and continue the turbine or compressor that would possibly result in
flushing in one-hour intervals until no metallic a change in the shaft positions, check the alignment per
particles and no more than 6 non-metallic parti- Form 160.67-N2.
cles are present on any of the screens.
Check The Refrigerant Charge
5. Once clean screens are present, remove all
screens, service the turbine bearings and replace The refrigerant level should be visible in the evapora-
them in the bearing housing. Housings must be tor sight glass at the level recorded after the chiller was
cleaned and resealed with Tite-Seal to prevent oil initially charged. Add refrigerant if required per Sec-
leaks at the case split line. tion 6 of this manual.
6. Check the condition and cleanliness of the oil fil- Oil Heaters
ters furnished and replace them with new filters if
needed before continuing with the start up. If the oil heater is de-energized during a shut down pe
riod, it must be energized for 12 hours prior to start
Check The Oil Level In The Turbine ing compres sor, or remove all oil and re charge com
Bearing Reservoirs (Ring Oil pressor with new oil. (See “Oil Charging Procedure”,
Lubrication) Section 4 of this manual.)
On a new turbine, remove the mylar protection that sta- Oil Heater Operation
bilizes the shaft during shipment. To do this, remove
the upper half of the bearing housing, remove the up- The oil heater operation is controlled by the OptiV-
per half of the bearing and remove all pieces of my- iew™ Control Center. The heater is turned on and off
lar protection (above and below) from the shaft. This to maintain the oil temperature differential to a val ue
must be done at both the steam and exhaust end bear- 50°F (27.8°C) above the condenser saturation tem per
ings. Housings must be cleaned and resealed with Tite- a ture. This is the target value and if the oil tem per a
Seal to prevent oil leaks at the case split line.
JOHNSON CONTROLS 21
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
ture falls to 4°F (2.2°C) or more below the target, the Verify The Compressor Oil Pump
heater is turned on. It is turned off when the oil temper- Operation
ature increases to 3°F (1.7°C) above the target value.
Before applying power to the chiller, ensure that the
If the target value is greater than 160°F (71°C), the tar compressor oil heater protector disconnect switch
get de faults to 160°F (71°C). If the target value is less (OL1) in the Power Panel is in the “OFF” position.
than 110°F (43.3°C), it defaults to 110°F (43.3°C). Close the main three-phase disconnect switch and en-
sure that appropriate power is available at the Power
To prevent over heat ing of the oil in the event of a con- Panel. Check that the compressor oil reservoir has the
trol center component fail ure, the oil heat er ther mo proper oil level and switch the oil heater protector dis-
stat (1HTR) is set to open at 180°F (82°C). connect switch (OL1) in the Power Panel to the “ON”
position to energize the oil heater.
Check The Oil Level In The
Compressor Oil Reservoir The oil heater is automatically controlled
by the control panel at all times during
Proper operating oil level – During operation, the oil shutdown and operation of the chiller
level should fall to the “Operating Range” identified on to maintain the oil temperature in the
the vertical oil level indicator label. oil reservoir at a target value which is
• If the oil level during operation is in the 50°F above the condenser refrigerant
LD08647
“Over Full” region of the oil level indi- saturation temperature. It is turned on at
cator, oil should be removed from the 4°F below the target value and off at 3°F
oil reservoir, until the oil level is to the above the target value. To prevent over-
“Operating Range”. heating the oil, the heater has an integral
thermostat that opens at 180°F.
• If the oil level during operation is in
the “Low Oil” region of the oil level
While viewing the compressor OIL SUMP SCREEN
indicator, oil should be added to the
on the OptiView™ Control Center, verify that the com-
oil reservoir. (See SECTION 4 - OP-
pressor oil temperature is at least 110°F. Open the main
ERATIONAL MAINTENANCE in this
three-phase disconnect switch and replace the fuses
manual.) FU10, FU11, and FU12. Close the main three-phase
A complete oil change may disconnect switch and use the MANUAL key to verify
be required if the oil is dark that the oil pump operates properly.
or cloudy or an oil analysis
indicates contaminated oil. Verify The Turbine Governor Valve
Comply with EPA and Local Operation
regulations when removing Ensure that the main steam inlet block valve, steam inlet
or disposing of Refrigeration slow roll bypass valve bypass valve, turbine pneumatic
System oil! trip valve, and turbine governor valve are fully closed.
While viewing the ANALOG I/O EXPANSION TEST
Check The Status Of All Utilities SCREEN on the OptiView™ Control Center, manually
Ensure that the correct three-phase power supply is adjust the output signal to the governor valve and veri-
available at the main disconnect switch in the Power fy that the valve strokes fully between 4 and 20 maDC
Panel and that it is properly phased: Phase A-L1, Phase output signals. The governor valve positioner is fac-
B-L2, Phase C-L3. tory calibrated to provide the correct pressure output to
the valve diaphragm with a 4-20 mA DC control signal
Check that a minimum of 80 PSIG pneumatic control from the OptiView™ Control Center. See Section 24 of
air supply is available at the filter regulators on the Form 160.67-M3 for more information.
turbine governor valve and steam condenser. Check
the gauges to ensure that 25 PSIG is available to the
steam condenser level control valve current to pneu-
matic (I/P) transducer. The governor valve positioner
supply air gauge should read 5 PSIG above the actuator
requirement.
22 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Chillers manufactured after December and lowering the hotwell liquid level. The switch in-
2006 are NOT designed with separate dicator will display OPEN when the level reaches the
steam inlet and slow roll bypass valves. switch actuation point.
Ensure that the Hotwell Pump Motor Protector Over- 2
load Switches are both in the OFF position.
Verify The Compressor Pre-Rotation BUMP test the condensate pump and standby pump (if
Vane Operation supplied) motors for proper rotation. The easiest way
to do this is to first put the selected pump in the Man-
The chiller cannot be started until the pre-rotation ual mode using the Pump Mode key on the CONDEN-
vanes have been calibrated. On standard YST chill- SATE SCREEN, and immediately place the selected
ers, the pre-rotation vanes are calibrated at the factory hotwell pump motor protector overload switch in the
during functional testing. For retrofit applications, the Power Panel in the ON position (within 10 seconds)
vanes must be calibrated per the OptiView™ Control and immediately back to the OFF position after the
Center Service Instructions Form 160.67-M3. After pump starts. In the Manual Mode, if the pump motor
completing the calibration, the operation must be veri- does not start within 5 seconds after the pump start is
fied. While viewing the AUTO/MANUAL SCREEN, initiated an alarm is sounded. Since the standby pump
place the pre-rotation vanes in Manual and manually will not start (Overload switch is OFF), the Mode key
drive the vanes fully open and then fully closed while will revert back to Auto after 5 seconds and the Pump
observing the position indicator on the operating shaft. Run Output will go off. The condensate pump should
When the PRV control signal is set to 0% in the Man- rotate clockwise when viewed from the back of the
ual mode, the vane actuator closed limit switch (VMS) motor. If pump runs backwards, interchange two wires.
may not be activated. Place the control signal back to
the Auto mode to activate the switch. Reverse operation can cause extensive
damage to the pump. Failure to correct the
Verify The Hot Gas Bypass And rotation could result in injury or property
Subcooler Level Control Valve damage.
Operation
While viewing the AUTO/MANUAL SCREEN, place
each valve in Manual and manually drive the valve Before starting a condensate pump, open the suction-
fully closed and then fully open while observing the side isolation valve, both vent line valves and partially
position indicator on the operating shaft. The hot gas open the discharge valve of the selected pump and the
valve is fully closed when the flats on the valve stem standby pump (if supplied). Start the pump by plac-
are perpendicular to the pipe it is installed in. ing the hotwell pump motor protector overload switch
in the Power Panel in the ON position and using the
Prepare The Steam Condenser hotwell Pump Mode key to manually start the selected
Hotwell And Pumps pump. Slowly open the discharge valve allowing the
level controller to react to the change in the level. The
Ensure that the water level in the hotwell is at approxi- hotwell fill valve may be opened to make up water
mately 50% (refer to Figure 5 on page 17). If the used to fill the condensate discharge piping. When the
water level is less than 50%, close the drain valve and level appears to be stable, close the fill line valve and
open the main isolation valve at the edge of the base open the discharge valve fully.
frame. Open the valve next to the fill connection on
the hotwell and fill the hotwell to approximately 62%. Verify the operation of the level control system by
While viewing the CONDENSATE SCREEN on the adding water to the hot well and viewing the action of
OptiView™ Control Center, verify that the condensate the valves. As the level in the hot well increases, the
level display is indicating the correct level. I/P transducer pneumatic output signal to the valves
should decrease to open the overboard valve and close
Ensure that the high and low level switches are secured the recirculation valve. Refer to the PID Tuning sec-
at the correct elevations per Figure 5 on page 17. tion of the OptiView™ Control Center Service Instruc-
Check each switch function by viewing the switch in- tions Form 160.67-M3 for more details on the hotwell
dicators on the CONDENSATE SCREEN and raising level control tuning parameters.
JOHNSON CONTROLS 23
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Check piping connections for leaks. Pipe unions and Do not start the pump if the pump cham-
flanges may loosen during shipment. Retighten as ber is full, since this could result in the
necessary. breakage of a blade or the impeller drive
shaft. If the pump motor fails to start
After testing, return the pump to the AUTOMATIC within 5 seconds after the contactor is
mode. energized, the sealing water solenoid is de-
Test the operation of the standby pump the same as de- energized to stop the flow of water into the
scribed above. chamber. After a pump motor failure, it is
recommended that some water be drained
If the chiller is equipped with an optional from the chamber to ensure a safe restart.
standby pump, in the automatic mode, the
hotwell pumps will be switched-over (at
each chiller start) to share operational Open the main isolation valve at the edge of the base
time. If the lead pump fails to start or frame and all valves in the sealing water line of the se-
fails while the chiller is operating, toggle lected pump and the standby pump (if supplied).
to standby pump will be done automati- Ensure that the Vacuum Pump Motor Protector Over-
cally. If both pumps fail, the chiller will load switches are in the OFF position.
not be allowed to start and will shutdown
if operating. BUMP test the vacuum pump and standby pump (if
supplied) motors for proper rotation. The easiest way
The lead hotwell pump will be started to do this is to first put the selected pump in the manual
automatically 50 seconds after a start is mode. While viewing the VACUUM SCREEN on the
initiated if condenser cooling liquid flow OptiView™ Control Center, use the vacuum pump,
is verified. Pump Mode key to put the selected pump in the Manu-
al mode. In the Manual Mode, if the pump motor does
not start within 5 seconds after the pump start is initi-
Prepare The Steam Condenser
ated an alarm is sounded. Since the standby pump will
Vacuum Pumps
not start (Overload switch is OFF), the Mode key will
Depending on the length of time the pump revert back to Auto after 5 seconds and the Pump Run
has been idle or in storage, it may be Output will go off. When a pump start is initiated, the
charged with a rust inhibited 50% ethyl- sealing water solenoid valve is energized and when the
ene glycol solution. This must be properly flow switch closes, the Run Output LED is illuminat-
drained prior to operating the pump. ed. Place the selected vacuum pump motor protector
overload switch in the Power Panel in the ON posi-
Prior to operating the pump, the housing should be tion (within 10 seconds) and immediately back to the
drained of any storage solution. Remove the screw OFF position after the pump starts. The vacuum pump
plug on the pump cover and allow the liquid to run out. should rotate as indicated by the arrow on the pump. If
When draining, rotate the motor occasionally in the op- pump runs backwards, interchange two wires.
posite direction to the running direction (see direction
Even though it is not necessary to prime
arrow on the casing) by hand at the external fan until
the vacuum pumps, they must not be run
no more liquid runs out.
dry after the initial startup. Normally the
Reinstall the drain plug and remove the vacuum gauge flow switch will prevent this from hap-
to prime the pump housing with approximately 3.25 pening. However, the drain line from the
quarts (3 liters) of water via the vacuum gauge port. separator should be checked after the
initial startup and periodically thereafter
to verify that the sealing water is present.
If no water is coming out of the vacuum
pump separator when the pump is operat-
ing, stop the pump immediately!
24 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Place the vacuum pump motor protector overload The relief valve hand wheel must be ro-
switch in the power panel in the ON position. While tated fully counter-clockwise to prevent
viewing the VACUUM SCREEN on the OptiView™ the valve from being manually lifted off
Control Center, use the vacuum pump, Pump Mode its seat. 2
key to manually start the selected pump. When a pump
start is initiated, the sealing water solenoid valve is en-
ergized. As soon as the flow switch contacts close, the Open the valve supplying sealing water to the atmo-
pump motor is started. In the Manual mode, if seal- spheric relief valve enough to obtain a trickle flow out
ing water flow is not established within 10 seconds af- the overflow line. This will ensure that atmospheric re-
ter the pump start is initiated, an alarm is sounded the lief valve sealing water is present to the proper level in
mode key reverts back to Auto, and the Run Output the valve.
goes OFF. Adjust the sealing water flow to the pump
using the hand valve (downstream of the solenoid Prepare The Chilled And Condenser
valve) to obtain a slight vacuum reading on the gauge Water Piping And Pumps
down stream of the valve. When the desired vacuum
Ensure that the pump motor starters and any automatic
is achieved, the sealing water flow may be further re-
duced. Gradually close the throttling valve until either isolation valves located in the inlet/outlet piping are
a loss of vacuum (at the gauge on the pump inlet pip- operable.
ing below the check valve) is experienced or the pump Before the initial operation of the pumps,
trips on low sealing water flow. This is the minimum both water circuits should be thoroughly
setting and the valve should be opened slightly from vented of all air at the high points. Failure
this position to obtain the best vacuum. Failure to ob- to do so will result in pass baffle damage.
tain the design vacuum may be due to excessive air
infiltration. Check flanged connections for leaks. After
testing, return the pump to the AUTOMATIC mode.
Prepare The Pressure Powered Pump
Test the operation of the Standby Pump
the same previously described. If the If the chiller is supplied with a Pressure Powered Pump
to remove condensate from the Turbine casing (Ex-
chiller is equipped with an optional
haust end), open the valve in the Motive Pressure Line
standby pump, in the automatic mode, the
to the pump.
vacuum pumps will be switched-over (at
each Chiller start) to share operational Verify All User Defined Setpoints
time. If the lead pump fails to start or fails
Using the checklist in the YST Start-up checklist Form
while the chiller is operating, toggle to
160.67-CL1, ensure that all setpoints are correct for the
standby pump will be done automatically.
equipment supplied on the chiller and expected operat-
If both pumps fail, the chiller will be not
ing conditions. Refer to the YST OptiView™ Control
be allowed to start and will shutdown if Center Operation Manual Form 160.67-O1 for a de-
operating. tailed explanation of all setpoints.
The lead vacuum pump will be started
Pre-Startup Procedures – After
automatically after the fifty second pre-
Short Term Shutdown
lube. The vacuum pump will be stopped
automatically at shutdown when the A short term shutdown is defined as overnight or
vacuum breaker solenoid is de-energized. several days where the turbine has been allowed to
cool down but the system remains in a ‘READY TO
START” condition. During this shutdown period, all
Prepare The Steam Condenser
manual valves with the exception of the steam sup-
Atmospheric Relief Valve
ply valves, the atmospheric relief valve sealing water
Check the steam condenser atmospheric relief valve to supply, and the turbine steam ring drain valve would
ensure that the manual opening device is disabled. The remain in their original operating positions. The oil
discharge of this valve must be piped to a safe location, heater and motor protector disconnect switches in the
outdoors. Power Panel would remain in the “ON” position. The
turbine steam ring drain valve (if NOT supplied w/
JOHNSON CONTROLS 25
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
steam ring drain solenoid) should have been opened 6. Open the valve supplying sealing water to the at-
after the previous shutdown to remove any conden- mospheric relief valve enough to obtain a trickle
sate as the turbine cooled down. Prior to starting the flow out the overflow line. This will ensure that
chiller, some routine checks are required to be certain atmospheric relief valve sealing water is present
plant conditions that would affect the chillers operation to the proper level in the valve.
have not changed since the last operation. The follow-
ing procedures must be performed prior to starting the 7. Ensure that sealing water is available for the vac-
chiller: uum pump(s).
8. If the OptiView™ Control Center is used to initi-
1. Check the status and availability of all utilities;
ate the chilled and condenser liquid flow to the
electric, water, instrument air, and steam. Check
chiller, ensure that any manual isolation valves in
that a minimum of 80 PSIG pneumatic control
the chilled and condenser liquid lines are open.
air supply is available at the filter regulators on
the turbine governor valve and steam condenser. 9. Check the oil levels in the compressor and turbine
Check that 25 PSIG is available to the steam con- oil reservoirs.
denser level control valve current to pneumatic
(I/P) transducer. The governor valve positioner 10. Verify that all pressure and temperature displays
supply air gauge should read 5 psig above the ac- on the OptiView™ screens display values as ex-
tuator requirement. pected for the present ambient temperatures and
condition of the chiller components (oil heater on,
2. Ensure that all condensate is thoroughly drained oil pump running etc.).
from the steam supply and exhaust lines.
The oil heater is automatically controlled
Operators must make every effort to blow by the control panel at all times during
the inlet steam line and turbine free of shutdown and operation of the chiller to
condensed steam, otherwise damage to maintain the oil temperature in the oil
the turbine may occur. reservoir at a target value which is 50°F
above the condenser refrigerant satura-
tion temperature. It is turned on at 4°F
below the target value and off at 3°F above
3. Ensure that the main steam inlet block valve, the target value. To prevent overheating
steam inlet slow roll bypass valve, bypass valve the oil, the heater has an integral ther-
(if supplied), turbine pneumatic trip valve, and mostat that opens at 180°F.
turbine governor valve are fully closed.
4. If the chiller is not supplied with at steam ring Sequence Of Operation
drain solenoid, open turbine steam ring drain Refer to Figure 8 on page 30 Opera-
valve (if not already open) to remove any conden- tion Sequence Timing Diagram – Manual
sate. Leave the drain valve open until the turbine Start/Variable Speed or Figure 8 on page
has been warmed up by slow rolling it for the re- 30 – Operation Sequence Timing Dia-
quired time. gram - Automatic Start/Variable Speed
On newer chillers, the drain line will be along with the following paragraphs. If
equipped with a check valve and solenoid any of the speeds, ramp rates, or time
valve to perform the above operation at the delays described in the following para-
appropriate times during the startup and graphs are adjustable, the factory default
shutdown sequence. values are show for clarity. Refer to the
OptiView™ Control Center Operation
5. Ensure that the water level in the hotwell is at ap- Manual Form 160.67-O1 for details on
proximately 50%. If the water level is less than adjustable setpoints.
50%, open the valve next to the fill connection on
the hotwell and fill the hotwell to approximately
50%.
26 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
2
rolling startup of the turbine is necessary
to avoid problems with thermal stresses
Idle and expansion. This slow roll startup is
accomplished manually from the control
SR Time LD09899
panel on systems furnished with “Manual
Startup”, and is accomplished automati-
Figure 6 - Slow Roll Time calculation
cally on systems furnished with “Auto-
matic Startup”.
A period of slow roll at idle speed is required before the
turbine can be run continuously. After SLOW ROLL, If the steam turbine has remained warm
the turbine speed can be increased to normal operat- for some time after a shutdown because of
ing speed. Slow roll is shown in the above diagram as a leaking throttle valve, or if it displays ab-
a solid line. The dotted line shows where the turbine normal vibration during slow roll startup
speed is ramped up to minimum governor speed after or at design speed, it is possible the shaft
the chilled liquid flow has been established. has taken a bow because of heat distor-
The amount of time required to slow roll at idle speed tion. The shaft on the turbine design is
varies, depending on the inlet steam temperature and returned to its normal shape by rotating
the number of stages in the turbine. The following for- slowly at 750-1200 RPM for 15-30 min-
mula is used by the OptiView™ Control Center to de- utes with the auxiliary oil pump in opera-
termine the minimum slow roll time required: tion. If the KG turbine displays the same
indications it must be slow rolled for 15-30
SRT = 20 + Ti-350 / 50 + Ns minutes at 1200 RPM to assure a high
enough speed to provide lubrication by
where SRT = Slow Roll Time in minutes the oil ring lubrication system. The control
Ti = Inlet Temperature in °F panel display includes a countdown timer
showing the time remaining in the slow
Ns = Number of Turbine Stages roll warm-up. Vibration on either turbine
design may indicate other problems. Refer
Example: Consider a KD71750125 turbine with an in-
to SECTION 5 – TROUBLESHOOTING.
let temperature of 353°F.
So we know that Ti = 353, Ns = 7
SRT = 20 + 353-350 / 50 + 7
Therefore, this turbine should slow roll for a minimum
of 27 minutes.
JOHNSON CONTROLS 27
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
28 JOHNSON CONTROLS
4500
"CHILLER UNLOADING BEFORE SHUTDOWN"
“SYSTEM RUN” 4000
“TURBINE 3200
STABILIZING”
3000 TURBINE AUXILIARY OIL PUMP ON
FORM 160.67-O2
JOHNSON CONTROLS
“SLOW ROLLING” 500 AUTO ZEROING DIFFERENTIAL
OIL PRESSURE TRANSDUCERS
“SYSTEM STARTING”
ENERGIZE OIL RETURN & LIQUID
TURBINE AUX. OIL PUMP ON LINE SOLENOIDS
ENERGIZE TURBINE TRIP & VACUUM
MAN. OIL BREAKER SOLENOIDS
PUMP ENERGIZE OIL COOLER
DISABLED LIQUID VALVE ACTUATORS
ENERGIZE TURBINE
TRIP SOLENOID
“COMPRESSOR
RUN
“START SEQUENCE SOFT SHUTDOWN TIME SHUTDOWN
START-UP TIME TIME “SYSTEM COASTDOWN”
INITIATED” (SEE NOTE 5) TURBINE
SLOW ROLL (SEE
COOLDOWN”
WARM-UP NOTE 4)
SPEED IN RPM
OIL PRESSURE CHECK
COMPRESSOR OIL
PUMP ON
CONDENSER LIQUID
FLOW SWITCH BYPASS
HOTWELL
PUMP ON
CONDENSER LIQUID
PUMP ON
VACUUM PUMP ON
CHILLED LIQUID FLOW SWITCH BYPASS
CHILLED LIQUID
PUMP ON
0
0 10 13 45 50 “BEGIN “READY SHUTDOWN 0 35 70 360 1800
START (0.17) (0.22) (0.75) (0.83) SLOW TO RUN” STOPPED (0.58) (1.2) (6.0) (30.0)
INITIATED ROLL”
OPERATOR
OPERATOR PRESSES RUN
PRESSES BEGIN AT RATED KEY TIME IN SECONDS
SLOW ROLL KEY (MINUTES)
TIMING DIAGRAM – (MANUAL StarT)
NOTES:
1.Text in quotations indicates a Display Message.
2.Start-Up Time, Run Time, Soft Shutdown Time, and System Coastdown Time will vary depending on the system conditions and programmable set-
points.
3.Speeds and times shown, if programmable, are shown with default values.
4.During the Run Time, the Operating Speed may be anywhere from 3200-4500 RPM depending on Load and System Operating Conditions.
5.Only applicable to the following shutdowns: Low Water Temperature, Remote/Local Cycling (TB4-13), Remote Stop (TB4-8), Remote Stop (ISN Se-
rial Port). Operator initiated Soft Shutdown.
LD12576
Figure 7 - Operation Sequence Timing Diagram (Manual Start)
29
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
2
30
4500
“CHILLER UNLOADING BEFORE SHUTDOWN”
“SYSTEM RUN” 4000
“TURBINE 3200
STABILIZING”
3000 TURBINE AUXILIARY OIL PUMP ON
ENERGIZE TURBINE STEAM RING
“RAMPING TO 1500
RATED SPEED” DRAIN SOLENOID
1000
“SLOW ROLLING” 500 AUTO ZEROING DIFFERENTIAL
OIL PRESSURE TRANSDUCERS
“SYSTEM STARTING” ENERGIZE OIL RETURN & LIQUID
LINE SOLENOIDS
TURBINE AUX. OIL PUMP ON
ENERGIZE TURBINE TRIP, VACUUM
BREAKER, & MAIN STEAM INLET
ENERGIZE TURBINE BLOCK VALVE AIR DUMP SOLENOIDS
TRIP SOLENOID
ENERGIZE OIL COOLER
MAN. OIL LIQUID VALVE ACTUATORS
PUMP
DISABLED RUN “COMPRESSOR
“START SEQUENCE TIME SOFT SHUTDOWN TIME SHUTDOWN
START-UP TIME “SYSTEM COASTDOWN”
INITIATED” (SEE (SEE NOTE 5) TURBINE
SLOW ROLL NOTE 4) COOLDOWN”
SPEED IN RPM WARM-UP
OIL PRESSURE CHECK
COMPRESSOR OIL
PUMP ON
CONDENSER LIQUID
FLOW SWITCH BYPASS
HOTWELL
PUMP ON
CONDENSER LIQUID
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
PUMP ON
VACUUM PUMP ON
CHILLED LIQUID FLOW SWITCH BYPASS
CHILLED LIQUID
PUMP ON
0
0 10 13 45 50 “READY SHUTDOWN 0 35 0 3 0 1800
START (0.1 ) (0.22) (0. 5) (0.83) TO RUN” STOPPED (0.58) (1.2) ( .0) (30.0)
INITIATED
SPEED SETPOINT IS RAMPED MAIN STEAM INLET MAIN STEAM INLET BLOCK
UP TO 1000 RPM BLOCK VALVE IS VALVE & STEAM INLET SLOW ROLL
RAMPED OPEN BYPASS VALVE ARE CLOSED
TIME IN SECONDS
(MINUTES)
NOTES:
TIMING DIAGRAM – (Automatic StarT)
LD12577
JOHNSON CONTROLS
ISSUE DATE: 4/1/2015
FORM 160.67-O2
Startup Sequence Of Operation Automatic Start: The main steam inlet block valve
and slow roll bypass valve air dump solenoids are
1. On the OptiView™ Control Center HOME
energized to apply supply air pressure to the actu-
screen, press the STEAM SYSTEM key to go to
ators. This enables manual operation of the valves 2
the STEAM SYSTEM screen.
if required.
2. On the front of the OptiView™ Control Center, Chillers manufactured after December
place the keypad switch in the (O) STOP/RESET 2006 are not supplied with separate au-
position to reset any previous safety trips. The tomatic main steam inlet and slow roll
message SYSTEM READY TO START is dis-
bypass valves. The main steam inlet sup-
played.
ply isolation valve should be fully open
3. On the front of the chiller panel, place the key- at this time.
pad switch in the (◄) “START” position and re-
lease. This starts the compressor oil pump and If the turbine trip valve fails to open
the turbine auxiliary oil pump (if equipped). The within 10 seconds after the trip solenoid
condenser liquid pump start contacts (terminals is energized, the start is aborted and the
150-151 on the I/O board) are closed to start the message "TURBINE MECHANICAL
condenser liquid pump. If the operator has NOT TRIP" is displayed.
logged in using the OPERATOR access code, the During this period, before the turbine is
message "MANUAL START REQUIRES OP-
started, all condensate should be return-
ERATOR ACCESS LEVEL" is displayed. If the
operator has logged in using the OPERATOR ac- ing to the hot well (recirculation valve is
cess code, the message START SEQUENCE INI- open, overboard valve is closed).
TIATED is displayed. The compressor oil pump is If the chiller is equipped with an op-
started after the 13-second delay for auto-zeroing tional standby hotwell pump, in the au-
of the differential oil pressure. tomatic mode, the Hotwell pumps will be
If the condenser liquid pump contacts switched-over (at each Chiller Start) to
are not used, the plant control system or share operational time. If the lead pump
operator must ensure that the condenser fails to start or fails while the chiller is
cooling liquid flow is established within operating, toggle to standby pump will be
45 seconds after these contacts are closed. done automatically. If both pumps fail, the
Otherwise, the low flow switch will trip chiller will be not be allowed to start and
the chiller. will shutdown if operating.
If for any reason, the turbine begins
rotating prior to a start sequence being 6. After the turbine trip valve limit switch is closed,
initiated, the oil pumps will be started the vacuum pump sealing water solenoid valve
automatically. The condenser liquid is energized. When the sealing water flow switch
pump contacts are also closed and the oil contact closes, the vacuum pump is started. When
cooler liquid solenoids are energized to the exhaust pressure has been reduced to 10 PSIA,
provide oil cooling during this abnormal the message "READY TO BEGIN SLOW ROLL"
operation. is displayed. Press the BEGIN SLOW ROLL key
that appears on the STEAM SYSTEM screen.
4. Forty-five seconds after the start is initiated, the The message "WAITING FOR STEAM FLOW"
control logic will check that adequate compressor is displayed.
oil pressure, turbine oil pressure (if Pump Lubri- THE ACCESS LEVEL MUST BE DIS-
cation), and condenser liquid flow are established. PLAYED “OPERATOR” IN ORDER
FOR THE BEGIN SLOW ROLL KEY TO
5. Fifty seconds after the start is initiated, the main
start relay (K18 on the I/O board) is energized. BE DISPLAYED. If the BEGIN SLOW
The turbine trip and vacuum breaker solenoid ROLL key is not pressed within 20 min-
valves are energized, the pneumatic turbine trip utes after it appears, the turbine will be
valve is opened, the hotwell pump is started, and tripped and the message "EXCESSIVE
the message SYSTEM STARTING is displayed START DELAY" is displayed.
at this time.
JOHNSON CONTROLS 31
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Automatic Start: The BEGIN SLOW ROLL key ring drain line prevents air from being drawn into
does not appear and the start sequence proceeds the turbine when the turbine steam ring drops be-
to paragraph 7. low atmospheric pressure during the initial evacu-
ation and while the turbine is slow rolling. When
7. The speed controller setpoint is ramped up to 1000
the inlet steam valves open to begin slow roll and
RPM. This causes the output signal to the gover-
during the ramp up to minimum speed, the steam
nor valve transducer to increase to open the gov-
ring will rise above atmospheric pressure and any
ernor valve. Open the steam inlet slow roll bypass
condensate will be blown out of the turbine.
valve to start the turbine slow rolling. The valve
should be opened only far enough to achieve 1000 9. If the turbine is equipped with an auxiliary oil
RPM with the governor valve at least 25-35% pump, the turbine oil cooler liquid valve is opened
open. This will provide optimum speed control to allow the turbine oil temperature control valve
with less hunting. to maintain the bearing supply oil temperature at
Chillers manufactured after December 2006 do approximately 110-120ºF. For turbines with Ring
not require the manipulation of a slow roll by- Lubrication, the liquid valve is opened to allow
pass valve. The output signal to the valve control- cooling liquid to flow through the bearing oil res-
ler automatically modulates the ball valve posi- ervoir jackets. Adjust the valve in the cooling
tion to achieve and maintain the slow roll speed. liquid outlet line to maintain a minimum oil tem-
perature of 130°F in both bearing oil sumps.
Automatic Start: The output of the Governor Do Not Allow The Cooling Liquid To Cool
(Slow Roll) PID also controls the slow roll bypass The Bearing Oil Sump Temperature To
valve. As the speed setpoint is ramped up to 1000 Below 130°F (54°C), As This May Inter-
RPM, both the governor valve and the slow roll fere With The Action Of The Oil Rings
valve open to start the turbine slow rolling. As the Or Cause Atmospheric Moisture To Con-
speed approaches set point, both valve outputs are dense In The Oil Reservoir.
reduced to control the slow roll at 1000 RPM.
Chillers manufactured after December 2006 DO 10. A period of slow roll at 1000 RPM is required
before the turbine can be run continuously. After
NOT use a separate slow roll bypass valve.
slow roll, the turbine speed may be increased to
After rotation begins, if 1000 RPM is not achieved normal operating speed. The amount of time re-
in 100 seconds, the turbine will be tripped by the quired to slow roll varies, depending on the inlet
under speed logic and the message TURBINE steam temperature and the number of stages in the
UNDERSPEED is displayed. If the speed drops turbine. The chiller control logic automatically
below 900 RPM for more than 60 seconds, the calculates the slow roll time required and displays
chiller will also shut down on under speed. the time remaining via a countdown timer in the
status bar of the OptiView™ Control Center
8. When the panel senses that the speed has increased
screens.
above 500 RPM, the message "SLOW ROLL-
ING" is displayed. If the chiller is not supplied If a chiller start is initiated within 15 minutes of
with a solenoid in the turbine steam ring drain the last trip after a ramp-to-rated speed was initi-
line, the manual valve in the steam ring drain line ated, the calculated slow roll time is reduced to 5
should be closed at this time. The evaporator low- minutes because the turbine rotor is still hot and
pressure safety shutdown set point is increased to the shaft has not been stationary long enough to
30 PSIG. The compressor oil cooler liquid valve bow.
is opened (only if the compressor oil temperature
increases above 150°F) to allow the compressor 11. During slow roll, when the turbine exhaust pres-
oil temperature control valve to maintain the bear- sure has decreased to the PSP5-Vacuum Pump
ing supply oil temperature at approximately 110- Shutdown setpoint (9 PSIA) shown on the PRES-
120°F. SURE SETPOINTS SCREEN , the vacuum
pump is stopped. If the turbine exhaust pressure
If the chiller is supplied with a check valve and increases to the PSP6- Ready To Run Turbine Ex-
solenoid valve in the turbine steam ring drain line, haust Pressure setpoint (12 PSIA) shown on the
the solenoid valve remains energized (open) dur- PRESSURE SETPOINTS SCREEN, the vacuum
ing the initial startup. The check valve in the steam pump is restarted.
32 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
12. Perform the following while the turbine is slow (12 PSIA) and the vacuum pump is restarted. This
rolling: energizes the sealing water solenoid valve. If
flow is not established within 10 seconds after the
a. Check turbine and compressor for proper op-
pump start is initiated, an alarm is sounded. If the 2
eration of lubrication system.
chiller is equipped with a standby vacuum pump,
When starting a turbine with cold oil, the oil it will be started to continue with the startup, oth-
pressure will be somewhat higher than when erwise the startup will be aborted.
the oil reaches operating temperature. This
If the chiller is equipped with an optional standby
is a natural condition due to the change in oil
viscosity with temperature. ANY ADJUST- pump, in the automatic mode, the vacuum pumps
MENT TO OIL PRESSURE SHOULD BE will be switched-over to share operational time. If
MADE WITH THE OIL AT OPERATING the lead pump fails to start or fails while the chill-
TEMPERATURE. er is operating, toggle to standby pump will be
b. Check for vibration or any unusual noise or done automatically. If both pumps fail, the chiller
condition. will be not be allowed to start and will shutdown
if operating.
c. Check hotwell pump and pneumatic con-
densate level controls for proper operation. 15. When the turbine exhaust pressure has decreased
If the pump or level controls fail, the con- to the PSP6- Ready To Run Turbine Exhaust Pres-
densate level in the hotwell will increase. If sure setpoint (12 PSIA), the turbine should be
the hotwell high level switch contacts wired able to be safely ramped up to rated speed since
to terminals 1 & 80 of the I/O board remain there is essentially no load with the compressor
open for 10 seconds, the turbine will be pre-rotation vanes closed and the hot gas valve
tripped and the message HOTWELL CON- fully open. The message "READY TO RUN" is
DENSATE HIGH LEVEL will be displayed. displayed. Slowly open the main steam inlet block
valve and then press the RUN AT RATED key that
d. Check atmospheric relief valve sealing wa-
appears on the STEAM SYSTEM screen.
ter.
Chillers manufactured after December 2006 do
e. Check that the automatic turbine condensate
not require the manipulation of the main steam
removal system is operating properly. Dur-
inlet block valve. The output signal to the valve
ing slow roll, the system should be cycling
controller automatically modulates the ball valve
as required to drain the condensate from the
position to achieve and maintain the fixed rated
exhaust end of the turbine.
speed.
13. During the slow roll period, the evaporator low- If the RUN AT RATED button is not
pressure cutout is raised to 30 PSIG. If the slow pressed within 20 minutes after the slow
rolling produces enough flow through the com-
roll time has elapsed, the chiller will be
pressor to reduce the evaporator pressure below
tripped and the message "EXCESSIVE
this elevated pressure, the turbine will be tripped
immediately. If the turbine speed increases above SLOW ROLLING TRIP" will be dis-
1500 RPM, the chilled liquid pump contacts (ter- played.
minals 44-45 on the I/O board) are closed to start
the chilled liquid pump. Automatic Start: The RUN AT RATED key does
not appear and the start sequence proceeds to
If the chilled liquid pump contacts are not used, paragraph
the plant control system or operator must ensure
16. The chilled liquid pump contacts (terminals 44-45
that the chilled liquid flow is established within
on the relay output board) are closed to start the
10 seconds after these contacts are closed. Oth- chilled liquid pump.
erwise, the low flow switch will trip the chiller.
If the chilled liquid pump contacts are not used,
14. After the chiller has been slow rolled for the cal- the plant control system or the operator must
culated time, the message "TURBINE IDLING ensure that the chilled liquid flow is established
– INSUFFICIENT VACUUM" is displayed if the within 10 seconds after these contacts are closed.
turbine exhaust pressure is not less than the PSP6- Otherwise, the flow switch will trip the chiller.
Ready To Run Turbine Exhaust Pressure setpoint
JOHNSON CONTROLS 33
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
17. When the chilled liquid flow switch contacts Whenever the turbine bearing supply oil pressure
close, the speed setpoint is increased to the Fixed falls below the auxiliary oil pump control setting,
Rated Speed of 3600 RPM at 200 RPM/second the auxiliary pump motor will be restarted.
causing the governor valve to open rapidly. The
d. At 3200 RPM, the under speed safety log-
governor valve will continue to open until 3600
RPM is achieved. The vacuum pump is started ic is enabled. If the speed falls below 3100
(if not already running) and latched on until the RPM for more than 60 seconds, the turbine
chiller is shutdown. will be tripped by the under speed logic and
the message "TURBINE UNDERSPEED" is
Automatic Start: As the speed setpoint increases, displayed.
the governor valve and slow roll valve both open.
When the speed setpoint has increased to 500 e. At the minimum rated speed, the message
RPM above the slow roll speed setpoint, the main "TURBINE STABILIZING" is displayed
steam inlet valve control signal is ramped from 0 and the evaporator low-pressure cutout is
to 100% at 5%/second to open the valve. reduced to the normal cutout of 25 PSIG.
The turbine speed will continue to increase
Chillers manufactured after December 2006 are to 3600 RPM. As the system head increases,
not supplied with separate automatic slow roll the anti-surge logic will position the speed
bypass and main steam inlet valves. and vanes as required to maintain stable op-
eration.
18. The compressor pre-rotation vane control signal
is set to the PRV Minimum Open Position of 10% 20. After 5 seconds, the capacity control and com-
as soon as the ramp-to-rated speed is begun. This pressor Variable Geometry Diffuser (VGD) logic
allows the vane actuator to begin moving the link- are enabled and the message "SYSTEM RUN" is
age so that the vanes begin to move off of their displayed. The speed will decrease to the calcu-
fully closed position by the time the minimum lated anti-surge minimum speed based on the cur-
rated speed is achieved. rent system head. The hot gas bypass valve con-
trol signal is ramped down to 0% at 5 %/second
19. The chiller controls initiate the following actions
to close the valve. When the hot gas valve (HGV)
based upon the sensed turbine speed:
control signal is at 0%, the compressor pre-rota-
a. After the speed has increased above 1500 tion vanes (PRV) control signal is ramped up to
RPM, the message "RAMPING TO RATED 100% at 5 %/second.
SPEED" is displayed. Close the slow roll bypass valve.
b. At 2000 RPM, the under-speed trip time de-
Chillers manufactured after December 2006 do
lay is initiated. The turbine speed must now
not require the manipulation of a slow roll by-
be increased to 3200 RPM within 17 seconds
or the turbine will be tripped by the under pass valve.
speed logic and the message "TURBINE Automatic Start: The steam inlet slow roll bypass
UNDERSPEED" is displayed. solenoid valve is de-energized to close the bypass
c. If the turbine is equipped with an auxiliary line.
oil pump, and after the speed has increased Chillers manufactured after December 2006 are
above 3000 RPM, if the turbine shaft driven not supplied with a separate automatic slow roll
oil pump is producing sufficient pressure bypass valve.
to maintain the turbine supply oil pressure
above the set point of the turbine auxiliary The PRV and HGV ramped signals are used to
oil pump control set point, the turbine auxil- provide a controlled loading rate after the chiller
iary oil pump will be stopped. The oil return has been ramped up to the minimum rated speed
and liquid line solenoid valves are opened. If and the turbine stabilization delay has elapsed.
the chiller is supplied with a solenoid valve Regardless of the ramp rate setpoints, the chiller
in the turbine steam ring drain line, it is de- capacity will only increase as fast as the HGV
energized at this time. closes and the PRV open based on the stroke rate
of the electric actuators. The rates shown above
34 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
are increased to initiate the Capacity Ratchet For turbines with pressure feed lubrica-
Mode change to PRV before the HGV has actually tion, the oil pressure should be observed
closed fully and the mode change to Speed before frequently until the turbine has been
the vanes have actually opened fully. This will al- operated for several days as failure of oil 2
low the vanes and speed to begin increasing the pressure can result in extensive damage.
capacity sooner and provide a faster pull-down to The oil reservoirs should be maintained
the system design conditions. at the proper level using oil of the recom-
mended grade.
21. Under full load conditions, when the PRV control
signal is at 100%, the speed setpoint is ramped up
to the 4500 RPM at 10 RPM/second. If the cool- Hourly
ing load is low, the chiller will continue to run at Record operating readings. Walk through chiller area
the calculated anti-surge minimum speed. As the and perform a visual inspection of turbine, compressor,
system head increases, the speed will increase to steam system and control panel. Listen for any unusual
the higher calculated anti-surge minimum speed. noises.
As the vanes are ramping open, if the leaving
chilled liquid temperature decreases to less than Check turbine ring pressure verses steam inlet pressure.
2ºF above the leaving chilled liquid temperature Open or close nozzle valves to maintain ring pressure
controller setpoint, the controls will automatically at approximately 90 percent of steam inlet pressure. If
override the ramp signals to prevent over shooting an increase in load is expected, nozzle valves may be
the setpoint. The capacity control/anti-surge logic left open to ensure reserve turbine horsepower. How-
will always adjust the turbine speed and compres- ever, optimum turbine performance is achieved by
sor pre-rotation vanes as required, providing sta- having the least number of nozzle valves opened while
ble operation and maintaining the leaving chilled maintaining the horsepower required for the load.
liquid temperature at set point.
Do not partially open nozzle hand valves.
22. Verify general operation, oil pressures, tempera- Valves should be fully open or fully closed.
tures, vibration and noise levels, and hotwell con- Leaving the valves partially open could
densate level. cause seat and valve damage.
23. After the chiller has been running at or above
the minimum rated speed for 10 minutes, the
subcooler refrigerant liquid level controller Automatic Start: The nozzle valves are opened/closed
setpoint is ramped up to the desired setpoint at automatically based on the turbine first stage pressure
the 0.1 %/second. This causes the subcooler level that varies with each application. As the load on the
control valve to slowly close until the refrigerant turbine increases, the governor valve opens and the
level in the subcooler is at the setpoint. first stage pressure increases. When the first stage pres-
24. After the chiller has achieved the SYSTEM RUN sure has been above the Turbine Nozzle Solenoid #1
mode, if the turbine exhaust pressure increases Activate pressure setpoint continuously for 300 sec-
above 3.5 PSIA for a continuous period of 10 onds, Nozzle Solenoid #1 is energized to open addi-
seconds, the warning message "TURBINE EX- tional inlet nozzles and increase the horsepower output
HAUST HIGH PRESSURE" will be displayed. If of the turbine. If the load continues to increase and the
the pressure remains above the set point for 10 first stage pressure has been above the Turbine Nozzle
minutes, the turbine will be tripped. Solenoid #2 Activate pressure setpoint continuously
for 100 seconds, Nozzle Solenoid #2 is energized to
System Operating Procedure open additional inlet nozzles. If the load decreases,
the governor valve closes and the first stage pressure
General decreases. Each nozzle valve will be closed when the
Refer to the OPERATING INSPECTIONS in this pressure decreases 5 PSIG below the respective acti-
manual for complete details on the routine operation vate setpoint.
of the equipment.
JOHNSON CONTROLS 35
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Shut Down Sequence Of Operation Automatic Start: When the Soft Shutdown is initi-
ated, the Main Steam Inlet Valve control output
Normal (Controlled) Stop is first decreased (ramped down at 5 %/second)
The chiller capacity will be reduced to perform a con- until it is equal to or less than the current output to
trolled shutdown. This will slightly decrease the sud- the Governor Valve. From this point as the chiller
den loss of steam load when the chiller trips, thus pos- unloads and until it is shutdown, the Main Steam
sibly preventing boiler relief valves from lifting. The Inlet Valve output will equal the Governor Valve
following sequence is applicable when the Speed Con- output. When the two valve signals are tracking,
trol Mode is set for Variable: the present LCLT Controller SP (Local/Remote
setpoint, whichever is selected) is ramped up to a
1. To initiate the controlled stop, push the SOFT value equal to the return chiller liquid temp +5 °F
SHUTDOWN key on the OptiView™ Control and the chiller capacity controls begin unloading
Center HOME screen or open one of the remote the chiller as described above.
cycling contacts (if connected to the chiller pan-
el). The message "CHILLER UNLOADING BE- Chillers manufactured after December 2006 are
FORE SHUTDOWN" is displayed. not supplied with a separate automatic main
steam inlet valve.
2. The present LCLT Controller SP (Local/Remote
setpoint, whichever is selected) is ramped up to When the Speed Control Mode is set for Fixed,
a value equal to the return chiller liquid temp +5 the unloading sequence begins with the PRV and
°F and the chiller capacity controls begin unload- proceeds to the hot gas valve as described above.
ing the chiller. At the same time, a Soft Shutdown
timer (TDSP9-Soft Shutdown Rampdown Timer, Immediate Stop
adjustable 2-20 minutes on the Time Setpoints 1. On the front of the OptiView™ Control Center,
Screen) is enabled. The unloading begins with place the keypad switch in the (O) STOP/RESET
speed reduction to the calculated anti-surge mini- position to immediately trip the turbine without
mum speed. When the speed has decreased to the the unloading delay. In the event that the STOP/
calculated anti-surge minimum speed, the PRV RESET switch fails to trip the turbine, push the
will close to the calculated anti-surge minimum hand trip knob on the turbine.
vane position. While the vanes are closing and The oil pumps will continue to run
the head is decreasing, the speed will continue through their normal shutdown sequence
to ramp down to the lower calculated anti-surge after any of the above operations. If all
minimum speed. motors must be stopped for safety reasons,
When the PRV position feedback signal is equal the 120 VAC power supply to the chiller
to the calculated anti-surge minimum vane posi- panel must be shut off by an external
tion, the hot gas valve will begin opening. While EMERGENCY STOP switch contact (sup-
the hot gas valve is opening and the head is de- plied by others).
creasing, the speed will continue to ramp down
to the lower calculated anti-surge minimum speed Post Trip Shutdown Sequence
and the vanes will continue to close to the lower 1. When a turbine trip is initiated, the main start
calculated anti-surge minimum. relay (K18 on the I/O board) is immediately de-
3. The chiller will be shutdown when the hot gas energized. This de-energizes the the turbine trip
valve signal has increased to 95% (if HGV is En- solenoid, which causes the pneumatic turbine trip
abled) or the Soft Shutdown logic has been un- valve to close. The compressor pre-rotation vanes
loading the chiller longer than the TDSP9-Soft are closed, the compressor Variable Geometry
Shutdown Rampdown Timeout minutes entered Diffuser (VGD) is opened, and the hot gas valve
on the Time Setpoints Screen (if HGV is Dis- and subcooler level control valve are opened. The
abled). main steam inlet isolation valve should be closed
at this time.
36 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Automatic Start: The main steam inlet block valve closed if the cycling shutdown message "SYSTEM
air dump solenoid is de-energized to close the CYCLING – CONTACTS OPEN" is displayed.
valve immediately and its control signal is set to If the chilled liquid pump contacts are not
0%. The steam inlet slow roll bypass valve control used, the plant control system or operator 2
signal is also set to 0% to close the valve. should shut off the chilled liquid flow at
Chillers manufactured after December this time.
2006 are not supplied with separate au-
tomatic slow roll bypass and main steam
inlet valves. 6. The turbine auxiliary oil pump (if equipped) will
continue to run for 30 minutes to remove excess
heat from the turbine bearings.
The vacuum pump is stopped and the vacuum breaker The drive train will normally coast to a
solenoid valve is opened to break the vacuum in the complete stop within 6 minutes after a trip.
exhaust line and slow the turbine down faster. If for any reason the turbine is still rotat-
The speed control set point is set to 0 RPM which ing 6 minutes after the trip, the Oil Pumps
causes the control output signal to the governor valve will continue to operate. If the Turbine
to decrease to 0% and close the governor valve. begins rotating again after having come
to a complete stop, the message "STEAM
In the case of a mechanical trip, when the trip valve is SUPPLY VALVE MALFUNCTION" is
actuated by hand or by an over speed condition not de- displayed and the oil pumps will be re-
tected by the control panel logic, the trip valve closed started. Verify that the governor valve,
limit switch is actuated for feedback to the control pneumatic trip valve, and main steam
panel and the message "TURBINE MECHANICAL inlet block valves are all fully closed and
TRIP" is displayed. no steam is entering the turbine.
2. When the speed decreases below 3000 RPM,
7. Six minutes after the turbine was tripped, if no
the oil return and liquid line solenoid valves
rotation is detected, the condenser liquid and
are closed and the turbine auxiliary oil pump (if
hotwell pumps are stopped and the oil cooler liq-
equipped) is started. If the chiller is supplied with
uid valves are closed. If the chiller is not supplied
a solenoid valve in the turbine steam ring drain
with a solenoid in the turbine steam ring drain line
line, it is opened at this time.
and the chiller will not be restarted in a short time
3. During the coast down of the drive train and the (the turbine will be allowed to cool down), open
compressor oil pump and turbine auxiliary oil the manual valve in the steam ring drain line.
pump (if equipped) will continue to run to main- If the condenser liquid pump contacts
tain lubrication of the bearings and the message are not used, the plant control system or
"SYSTEM COASTDOWN" is displayed. operator should shut off the condenser
4. When rotation has ceased for 35 seconds, the liquid flow at this time.
message "COMPRESSOR SHTDN; TURBINE
COOLDOWN" is displayed if the turbine has
Pump Lubrication. If the turbine has Ring Lubrica- 8. Thirty minutes after the rotation has stopped, the
tion the message "SYSTEM READY TO START" turbine auxiliary lube oil pump (if equipped) will
is displayed. be stopped and the message "SYSTEM READY
5. When the compressor oil pump has been stopped TO START" is displayed.
for 35 seconds, the chilled liquid pump contacts If the trip was caused by a power failure and the
(terminals 44-45 on the I/O board) are opened to power is restored within 6 minutes of the last
stop the chilled liquid pump unless the cycling chiller run cycle, the oil pumps are started as soon
shutdown message "LEAVING CHILLED LIQ- as the power is restored. The compressor oil pump
UID – LOW TEMPERATURE" is displayed, in will then run for 35 seconds and stop. The turbine
which case the contacts will remain closed. If the auxiliary oil pump (if equipped) will run for 30
Chilled Liquid Pump Operation is set for Enhanced minutes and stop.
on the Setup Screen, the contacts will also remain
JOHNSON CONTROLS 37
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
The chiller may not be restarted until after the compres- to be fully closed at low loads. During off design op-
sor coast down sequence is completed and the message eration, the outputs of the high condenser pressure, low
"COMPRESSOR SHTDN; TURBINE COOLDOWN" evaporator pressure and torque limiting override PID
(Pressure Lubrication) or "SYSTEM READY TO controllers override the output of the primary Leav-
START" (Ring Lubrication) is displayed. ing Chilled Liquid Temperature Controller to maintain
stable operation and prevent the chiller from shutting
Capacity Controls down. The tuning of the primary Leaving Chilled Liq-
uid Temperature, Evaporator Pressure and Condenser
Overview
Pressure PID controllers is automatically adjusted to
Both fixed and variable speed modes of operation are match the response time of the process when the hot
included. The fixed speed mode would likely only be gas valve is being controlled. To achieve maximum
used in plants where the condensing cooling liquid is efficiency at part load conditions, the unloading se-
always at a high temperature so that speed reduction quence is vane closure and hot gas valve opening.
would not be possible due to the high system pres-
sure differential. The Speed Control Mode is factory Refer to the YST OptiView™ Control Logic Diagram
set for Variable (default mode) to provide the greatest (Capacity Control 1, Capacity Control 2, and Capac-
efficiency of operation in plants where the condenser ity Control 3 Diagrams) along with the following para-
cooling liquid is allowed to decrease to the minimum graphs for a more detailed description of the operation.
allowed. This allows the turbine speed to be reduced If any of the speeds, ramp rates, or time delays de-
to the minimum rated speed and the compressor pre- scribed in the following paragraphs are adjustable, the
rotation vanes to be closed completely prior to opening factory default values are show for clarity. Refer to the
the hot gas valve. In this mode, the capacity controls OptiView™ Control Center Operation Manual Form
will automatically utilize the full range of the governor, 160.67-O1 for details on adjustable setpoints.
compressor PRV and hot gas valve capabilities to con-
trol the capacity of the chiller and provide anti-surge Fixed Speed Chiller Loading
and override control functions to prevent unsafe opera- Sequence
tion. The chiller is started with the Leaving Chilled Liquid
Temperature Controller inactive and its output equal
For easy adjustments all operating mode selections and
to the fixed speed tieback signal after LSR3. When the
PID tuning parameters are included on various setpoint
ramp-to-rated speed is initiated, the vane output signal
screens on the OptiView™ Control Center graphic dis-
is set to the minimum start-up value (PRVM). After the
play.
minimum rated speed of 3200 RPM has been achieved,
Only a qualified YORK Service Techni- the vanes are ramped open and the hot gas valve is
cian should make adjustments to capacity ramped closed. As the system pressure differential
controls. (condenser minus evaporator pressure) increases, if the
output of the Minimum Vane Position Calculation in-
creases above the PRV ramp output signal, HSR5 will
select the higher value to open the vanes farther and
Fixed Speed Chiller Capacity prevent surging. The Leaving Chilled Liquid Tempera-
Controls Operation ture Controller becomes active when the vane ramp
signal is at 97% or the leaving chilled liquid temper-
During operation at a fixed speed, the vanes and hot ature decreases to within 2°F of the Leaving Chilled
gas valve are controlled by the output of a single PID Liquid Temperature Controller set point. The Leaving
controller that responds to changes in the leaving Chilled Liquid Temperature Controller will adjust the
chilled liquid temperature. A ratio calculation is used vanes as required to maintain the leaving chilled liquid
to position the hot gas valve after the vanes have been temperature at set point.
closed to their minimum position based on the sys-
tem pressure differential (condenser minus evaporator For fixed speed operation, TDSP17 – Turbine Stabi-
pressure). A separate PID controller is also provided to lization Delay should be set to 0 to allow loading to
control the hot gas valve based on leaving chilled liquid begin as soon as the minimum rated speed is achieved.
temperature if operating conditions require the vanes Refer to the OptiView™ Control Center Operation
Manual Form 160.67-O1 for details on adjustable set-
points.
38 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Fixed Speed Chiller Unloading Sequence trols at a leaving chilled liquid temperature set point
that is slightly below the main Leaving Chilled Liquid
PRV Control Temperature Controller set point. If the load continues
If the load decreases, the output of the Leaving Chilled to decrease with the vanes fully closed, the leaving 2
Liquid Temperature Controller will decrease to close chilled water temperature will decrease below the set
the vanes to the minimum position established by the point of the HGV Temperature Controller causing its
Minimum Vane Position Calculation. output to increase. HSR6 will select this higher signal
and begin opening the hot gas valve to maintain the
As the system pressure differential falls, the compres- leaving chilled liquid temperature at the lower HGV
sor is capable of stable operation with less refrigerant Temperature Controller set point.
gas flow (lower minimum compressor pre-rotation
vane positions). For the greatest efficiency, the com- Fixed Speed Chiller Override
pressor pre-rotation vanes must be used for capacity Controllers
control rather than hot gas bypass whenever possible.
The Minimum Vane Position Calculation output signal High and Low Refrigerant Pressure
to HSR5 provides a minimum closure of the pre-rota- The Evaporator Pressure and Condenser Pressure con-
tion vanes to suite the measured pressure differential trollers are inactive when the chiller is stopped with
input. This output also provides one of the input signals their outputs set to 100%. If the monitored parameter
for the Hot Gas Ratio calculation which to use in con- exceeds the set point of the controller during any ab-
trolling the output to the hot gas valve. normal operation when running at or above the mini-
mum rated speed, the output of the appropriate control-
Hot Gas Ratio Control ler is set to the tieback signal for the device currently
The Hot Gas Ratio calculation controls the hot gas by- being controlled before the controller is activated, thus
pass valve at a scaled ratio to the percentage of avail- providing a bumpless transfer to the override control.
able Leaving Chilled Liquid Temperature Controller If the monitored parameter exceeds the set point of the
signal below the Minimum Vane Position Calculation controller, the controller output will decrease. LSR2
output, thus providing a 0-100% control signal for the and LSR1 will select the lower signal to override the
hot gas bypass valve. Leaving Chilled Liquid Temperature Controller output
and close the compressor PRV as described above, thus
To provide greater stability at very low system pressure preventing unsafe operation and an unnecessary shut-
differentials when the minimum vane position calcula- down.
tion would normally be 0%, a minimum vane position
may be entered into the HGVRAT set point. HSR1 will If the override signal falls below the Minimum Vane
select this higher value to give the Hot Gas Ratio cal- Position Calculation output, the tuning parameters for
culation a greater range of control for the hot gas valve. hot gas control are loaded into the override controller.
As long as the capacity signal from the Leaving Chilled While any override controller is active, the primary
Liquid Temperature Controller is above the Minimum Leaving Chilled Liquid Temperature Controller is in-
Vane Position Calculation output (or the HGVRAT) activated and its output is set to equal the appropriate
signal, the hot gas valve remains closed. When the tieback, thus providing a bumpless transfer to normal
capacity signal falls below the Minimum Vane Posi- leaving chilled liquid temperature control. After the
tion Calculation output, the tuning parameters for hot override controllers monitored parameter has not ex-
gas control are loaded into the Leaving Chilled Liquid ceeded the set point for 5 seconds, the Leaving Chilled
Temperature Controller. The output of the Hot Gas Ra- Liquid Temperature Controller is reactivated and its’
tio calculation increases, which starts to open the hot PID algorithm begins controlling the output at the tie-
gas bypass valve. Thus at low loads, the capacity is back value.
controlled by modulating the hot gas bypass valve.
Turbine Governor Position Power Limiting
HGV Temperature Controller In some applications, during high load/pulldown con-
In some cases, it may be desirable to allow the vanes ditions, the turbine may be capable of producing more
to go completely closed which would leave no signal horsepower than the compressor bearings are rated for.
for the Hot Gas Ratio calculation to control the hot gas To provide protection for retrofitted chillers that do not
valve. A separate PID controller is provided which con- have the ability to monitor turbine first stage pressure,
JOHNSON CONTROLS 39
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
the logic monitors the governor valve actuator output horsepower output of the turbine. While the Turbine
from the chiller panel as done on previous chillers. Horsepower Limit Controller is active, the primary
The Governor Position Controller is inactive when the Leaving Chilled Liquid Temperature Controller is in-
chiller is stopped with its’ outputs set to 100%. activated and its output is set to equal the appropriate
tieback, thus providing a bumpless transfer to normal
When the chiller is running at or above the minimum leaving chilled liquid temperature control. After the
rated speed, if the integrated speed control PID at- turbine horsepower has not exceeded the set point for
tempts to open the governor valve more than a preset 5 seconds, the Leaving Chilled Liquid Temperature
value (determined by field testing at start up), the out- Controller is reactivated and its’ PID algorithm begins
put of the Governor Position Controller will decrease. controlling the output at the tieback value.
LSR2 and LSR1 will select the lower signal to over-
ride the Leaving Chilled Liquid Temperature Control- Variable Speed Chiller Capacity
ler output and unload the chiller as described above. Controls Operation
With the load reduced, the turbine will begin to speed During operation, the speed, vanes and hot gas valve
up and the speed control PID will begin to close the are controlled by the output of a single PID control-
governor valve, thus limiting the torque output of the ler that responds to changes in the leaving chilled liq-
turbine. While the Governor Position Controller is ac- uid temperature. The Capacity Ratchet Mode Selector
tive, the primary Leaving Chilled Liquid Temperature directs the controllers output to the appropriate con-
Controller is inactivated and its output is set to equal trolled device depending on system load and system
the appropriate tieback, thus providing a bumpless pressure differential (condenser minus evaporator
transfer to normal leaving chilled liquid temperature pressure). During off design operation, the outputs of
control. After the load is reduced sufficiently to return the high condenser pressure, low evaporator pressure
the governor valve to a safe position for 5 seconds, the and torque limiting override PID controllers are also
Leaving Chilled Liquid Temperature Controller is re- directed to the appropriate device to maintain stable
activated and its’ PID algorithm begins controlling the operation and prevent the chiller from shutting down.
output at the tieback value. The tuning of the primary Leaving Chilled Liquid Tem-
perature, Evaporator Pressure and Condenser Pressure
Turbine Horsepower Limiting PID controllers is automatically adjusted to match the
All new YST chillers are provided with a transmitter to response time of the process depending on the device
monitor the turbine first stage pressure. This pressure being controlled. To achieve maximum efficiency at
is used along with the steam inlet pressure and tem- part load conditions, the unloading sequence is speed
perature and the turbine exhaust pressure to calculate reduction, vane closure, and hot gas valve opening.
the turbines power output. A separate PID controller is Refer to the YST OptiView™ Control
provided to unload the chiller when the turbine power Logic Diagram (Capacity Control 1,
approaches the maximum that the compressor bearings Capacity Control 2, Capacity Control
are rated for or 115% of the turbine design horsepower, 3, and Capacity Ratchet Mode Selector
whichever is lower. The logic will calculate the actual
Diagrams) along with the following para-
horsepower based on the steam inlet temperature and
graphs for a more detailed description of
pressure so that the override controller automatically
adapts to fluctuations in the quality of the steam sup- the operation. If any of the speeds, ramp
plied to the turbine inlet. rates, or time delays described in the fol-
lowing paragraphs are adjustable, the
If the calculated horsepower increases above the set factory default values are show for clarity.
point, the output of the Turbine Horsepower Limit Refer to the OptiView™ Control Center
Controller will decrease. LSR2 and LSR1 will select Operation Manual Form 160.67-O1 for
the lower signal to override the Leaving Chilled Liquid details on adjustable setpoints.
Temperature Controller output and unload the chiller
as described above. With the load reduced, the turbine
will begin to speed up and the speed control PID will
begin to close the governor valve, thus reducing the
40 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 41
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
PRV Mode the HGV. As the HGV is opened, the system pressure
When the Leaving Chilled Liquid Temperature Con- differential will decrease resulting in lower outputs
troller output is equal to the Minimum Speed Calcu- from the Minimum Speed Calculation and Minimum
lation output signal, the Leaving Chilled Liquid Tem- Vane Position Calculation. The Capacity Ratchet logic
perature Controller PID calculation is halted while the will decrease the speed set point and PRV control sig-
tuning parameters for PRV control are loaded and its’ nals to the lower values after 30 seconds to maintain
output is set to the current PRV control signal which maximum efficiency of operation. If the system pres-
would be 100% since the PRV signal would be at 100% sure differential increases, the outputs of the Minimum
while the speed is being controlled. The controller PID Speed Calculation and Minimum Vane Position Calcu-
algorithm then begins modulating the PRV control sig- lation will increase. The higher values are immediately
nal to maintain the leaving chilled liquid temperature at moved into the speed set point and PRV control signal
set point. As the vanes are closed, the system pressure to prevent surging.
differential will decrease resulting in a lower output
Variable Speed Chiller Override
from the Minimum Speed Calculation.
Controllers
The Capacity Ratchet logic will decrease the speed set
High and Low Refrigerant Pressure
point to the lower value after 30 seconds to maintain
maximum efficiency of operation. If the system pres- The Evaporator Pressure and Condenser Pressure con-
sure differential increases, the output of the Minimum trollers are inactive when the chiller is stopped with
Speed Calculation will increase. The speed set point is their outputs set to 100%. If the monitored parameter
immediately set to the higher value to prevent surging. exceeds the set point of the controller during any ab-
normal operation when running at or above the mini-
For the greatest efficiency, the compressor pre-rotation mum rated speed, the output of the appropriate control-
vanes must be closed as far as possible prior to opening ler is set to the tieback signal for the device currently
the hot gas valve. The Minimum Vane Position Cal- being controlled before the controller is activated, thus
culation output signal to HSR5 provides a minimum providing a bumpless transfer to the override control.
closure of the pre-rotation vanes to suite the measured
pressure differential input. The Capacity Ratchet logic If the monitored parameter exceeds the set point of the
constantly monitors the Minimum Vane Position Cal- controller, the controller output will decrease. LSR1
culation output signal to ensure that the chiller is al- will select the lower signal to override the Leaving
ways operating at the lowest PRV signal possible while Chilled Liquid Temperature Controller output and un-
maintaining system stability. load the chiller as described above using the Capacity
Ratchet Mode Selector to direct the controllers output
Hot Gas Mode to the appropriate controlled device depending on sys-
If the load continues to decrease, the output of the tem load and system pressure differential, thus prevent-
Leaving Chilled Liquid Temperature Controller will ing unsafe operation and an unnecessary shutdown.
decrease. When the Leaving Chilled Liquid Tempera- While any override controller is active, the primary
ture Controller output is equal to the Minimum Vane Leaving Chilled Liquid Temperature Controller is in-
Position Calculation output signal, the Leaving Chilled activated and its output is set to equal the appropriate
Liquid Temperature Controller PID calculation is halt- tieback, thus providing a bumpless transfer to normal
ed while the tuning parameters for HGV control are leaving chilled liquid temperature control. After the
loaded and its’ output is set to a value equal to 100% override controllers monitored parameter has not ex-
minus the current HGV control signal. This value ceeded the set point for 5 seconds, the Leaving Chilled
would be 100% since the HGV signal would be 0% Liquid Temperature Controller is reactivated and its’
while the vanes are being controlled. The controller PID algorithm begins controlling the output at the tie-
PID algorithm then begins modulating the HGV con- back value.
trol signal to maintain the leaving chilled liquid tem-
perature at set point. Turbine Governor Position Power Limiting
If the load continues to decrease, the Leaving Chilled In some applications, during high load/pulldown con-
Liquid Temperature Controller output will begin de- ditions, the turbine may be capable of producing more
creasing from 100%. This signal is subtracted from horsepower than the compressor bearings are rated for.
100% to provide the increasing signal required to open To provide protection for retrofitted chillers that do not
42 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
have the ability to monitor turbine first stage pressure, If the calculated horsepower increases above the set
the logic monitors the governor valve actuator output point, the output of the Turbine Horsepower Limit
from the chiller panel as done on previous chillers. Controller will decrease. LSR2 and LSR1 will select
the lower signal to override the Leaving Chilled Liquid 2
The Governor Position Controller is inactive when the Temperature Controller output and unload the chiller
chiller is stopped with its’ outputs set to 100%. When as described above.
the chiller is running at or above the minimum rated
speed, if the integrated speed control PID attempts to With the load reduced, the turbine will begin to speed
open the governor valve more than a preset value (de- up and the speed control PID will begin to close the
termined by field testing at start up), the output of the governor valve, thus reducing the horsepower output
Governor Position Controller will decrease. of the turbine. While the Turbine Horsepower Limit
Controller is active, the primary Leaving Chilled Liq-
LSR2 and LSR1 will select the lower signal to over- uid Temperature Controller is inactivated and its output
ride the Leaving Chilled Liquid Temperature Control- is set to equal the appropriate tieback, thus providing a
ler output and unload the chiller as described above bumpless transfer to normal leaving chilled liquid tem-
using the Capacity Ratchet Mode Selector to direct the perature control.
controllers output to the appropriate controlled device
depending on system load and system pressure differ- After the turbine horsepower has not exceeded the set
ential. With the load reduced, the turbine will begin to point for 5 seconds, the Leaving Chilled Liquid Tem-
speed up and the speed control PID will begin to close perature Controller is reactivated and its’ PID algo-
the governor valve, thus limiting the torque output of rithm begins controlling the output at the tieback value.
the turbine.
Operating Log Sheet
While the Governor Position Controller is active, the
primary Leaving Chilled Liquid Temperature Control- A permanent daily record of system operating condi-
ler is inactivated and its output is set to equal the ap- tions (temperatures and pressures) recorded at regular
propriate tieback, thus providing a bumpless transfer to intervals throughout each 24 hour operating period
normal leaving chilled liquid temperature control. Af- should be kept.
ter the load is reduced sufficiently to return the gover- An optional status printer is available for this purpose
nor valve to a safe position for 5 seconds, the Leaving or Figure 9 on page 44 shows a log sheet used by
Chilled Liquid Temperature Controller is reactivated Johnson Controls personnel for recording test data on
and its’ PID algorithm begins controlling the output at chiller systems. It is available from the factory in pads
the tieback value. of 50 sheets each under Form 160.44-F7 and may be
obtained through the nearest YORK office. Automatic
Turbine Horsepower Limiting
data logging is possible by connecting the optional
All new YST chillers are provided with a transmitter to printer and programming the DATA LOGGER func-
monitor the turbine first stage pressure. This pressure tion. See Form 160.67-O1, Section 3 - Printers for ad-
is used along with the steam inlet pressure and tem- ditional information.
perature and the turbine exhaust pressure to calculate
the turbines power output. An accurate record of readings serves as a valuable ref-
erence for operating the system. Readings taken when
A separate PID controller is provided to unload the a system is newly installed will establish normal condi-
chiller when the turbine power approaches the maxi- tions with which to compare later readings.
mum that the compressor bearings are rated for or
115% of the turbine design horsepower, whichever is For example, an increase in condenser approach tem-
lower. The logic will calculate the actual horsepower perature (condenser temperature minus leaving con-
based on the steam inlet temperature and pressure so denser water temperature) may be an indication of
that the override controller automatically adapts to dirty condenser tubes.
fluctuations in the quality of the steam supplied to the
turbine inlet.
JOHNSON CONTROLS 43
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Operating Inspections
By following a regular inspection using the display 6. Check the compressor discharge temperature on
readings of the Microcomputer Control Center, and the SYSTEM Screen. During normal operation
maintenance procedure, the operator will avoid serious discharge temperature should not exceed 220°F
operating difficulty. The following list of inspections (104°C).
and procedures should be used as a guide.
7. Check for any signs of dirty or fouled condenser
Daily tubes. (The temperature difference between wa-
ter leaving condenser and saturated condensing
1. Check OptiView™ Control Center displays. temperature should not exceed the difference re-
2. If the compressor is in operation, check the bear- corded for a new unit by more than 4°F (2.2°C).
ing oil pressure on the COMPRESSOR Screen. 8. Complete a visual inspection of the Turbine for
Also check the oil level in the oil reservoir. Oper- external damage or leaks.
ating oil level should be in the "Operating Range"
identified on the vertical oil level indicator label . 9. Inspect the Turbine for unusual vibration or noise.
Drain or add oil if necessary. 10. The turbine oil temperatures should be checked
3. Check entering and leaving condenser cooling several times a day. On KG turbine design oil
liquid pressure and temperatures for comparison temperature in the bearing oil should be between
with job design conditions. Condenser liquid tem- 130° and 180°F (54°C - 82°C). Cooling water
peratures can be checked on the SYSTEM Screen. flow should be adjusted to maintain this range.
On KD turbines the oil supply from the oil cooler
4. Check the entering and leaving chilled liquid tem- to the turbine bearings should be between 110°
peratures and evaporator pressure for compari- - 120°F, (38°C - 49°C). Adjust cooling water as
son with job design conditions on the SYSTEM necessary.
Screen.
11. Check oil pressures on the KD turbine lubrication
5. Check the refrigerant condenser saturation tem- system every one or two hours.
perature (based upon condenser pressure sensed
by the condenser transducer) on the SYSTEM 12. Check The Turbine Oil Level And Oil Condition:
Screen.
DATE
TIME
Hour Meter Reading
O.A. Temperature Dry Bulb / Wet Bulb / / / / / / / / /
Oil Level
Oil Pressure
Oil Temperature
Compressor
Oil Pump/VSOP Output/Hz
Discharge Temperature
AL
PRV % Open UG
RIF
Evaporator Pressure E NT
TC
Refrigerant Evaporator Saturation Temperature YS
Small Temperature Difference
Evaporator
Supply Temperature
Supply Pressure
Liquid Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
Discharge Pressure
...an E
ne
approa rgy-Savin
Corresponding Temperature
ch g
Refrigerant
Subcooler Liquid Temperature
Service to your
Small Temperature Difference needs.
..
Condenser
Refrigerant Level %
Refrigerant Level Setpoint
Issue
Supply Temperature Febru Date:
ary 10, Form
160.67
2014 -MR1
Supply Pressure New Re (214)
lease
Liquid Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
- CONTINUED ON REVERSE -
23889A
160.67-MR1 (114)
New Release
Issue Date: January 24, 2014
*NOTE:These items can be printed by an electronic printer connected to the Microboard and pressing the PRINT key on the Keypad, or auto-
matically using the Data Logger feature.
44 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
Ring Oil Lubrication 14. Observe supply pressure from pressure reducing
The oil level gauge on the side of the bearing housing valve for air in bearing seal air purge piping to
indicates the oil level. A mark inscribed on the low- bearing housings.
er-half bearing housing indicates the proper oil level. Weekly
2
Oil levels in both bearing housings should be checked
daily. Always use a strainer when adding oil to the sys- 1. Check the refrigerant charge. (See “Checking The
tems and cover the fill connection when finished. If Refrigerant Charge”, Section 6 of this manual.)
there is any reason to suspect water in the oil, open the 2. Leak check the entire chiller.
low point drain in each bearing housings slightly. If
water is present, it will be the first thing to come out 3. Check the KD Turbine Auxiliary Oil Pump Op-
of the drain. Low point drains in the bearing housing eration.
should be checked weekly for water. 4. Check the compressor oil pump operation.
The presence of oil in the constant level
5. Test the KD turbine manual overspeed trip valve.
oilers does not necessarily mean that oil
To do this, use the SOFT SHUTDOWN key and
in the bearing housings is at the proper
allow the control panel to unload the chiller. Then
level. Cleanliness is essential
use the hand trip knob (See Figure 12 on page
for long and trouble free service from the
54) to manually activate the 3 way Trip Valve
bearings. Care must be taken to ensure
and shutdown the turbine.
that no foreign material enters bearing
housings or constant level oilers when 6. On KG turbines check the low point drains in the
performing maintenance, checking oil, bearing housings for presence of water.
adding oil, or making adjustments. 7. Check the shafts for dirt, oil, or grease buildup.
Pressure Lubrication 8. Check the water seal ring on the steam condenser
relief valve.
Always keep the proper oil level in the sight gauge on
the oil reservoir that is an integral part of the turbine 9. Check the liquid ring vacuum pump on the steam
base. The system must supply continuous lubrica- condenser package.
tion to all contact surfaces. The Oil Level Should Be
Monthly
Checked At Least Once A Day Or Every 8 Hours If
The Turbine Operates 24 Hours A Day. Normally, a 1. Test the turbine mechanical overspeed trip device
small amount of oil (of the recommended type and vis- by slowly running the turbine up to 110% of de-
cosity) should be added between oil changes to main- sign maximum speed. See the OptiView™ Con-
tain the proper oil level. Always use a strainer when trol Center Operation manual, form 160.67-O1
adding oil to the systems and cover the fill connection for the Overspeed Test Procedure using the Auto/
when finished. Manual Screen.
Water gives oil a milky appearance, and it 2. On the KG steam turbine, (has no oil filter),
has a tendency to settle at the bottom of the change the oil in the bearing housings monthly,
reservoir when the turbine is not running. more often if oil analysis indicates a need to, or if
If there is any reason to suspect water in it is suspected contaminants have gotten in the oil.
the oil, open the reservoir drain slightly. If
3. Check Hotwell Condensate Pump and Operation
water is present, it will be the first thing to
come out of the drain. Refer to SECTION 4. Check Hotwell Condensate Pump seals.
4 - OPERATIONAL MAINTENANCE to
determine the possible cause and proce- 5. Check Hotwell liquid level and operation of con-
dure to follow. trol valves.
Quarterly
13. Observe if steam is venting from gland leak-off
line. If the amount of steam is excessive and con- 1. Perform chemical analysis of oil for KG turbine
denssate is draining from the exhaust end gland, models.
the seals should be replaced.
JOHNSON CONTROLS 45
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
2. Clean all linkage systems and inspect for wear. On 4. Perform refrigerant analysis.
the turbine, clean and oil or grease all the moving
5. Remove and clean the Steam Strainer on the Tur-
parts (fulcrum points). For units with inlet operat-
bine, refer to the product specific Service manual
ing temperatures above 500 F a high temperature
for instructions.
grease (DuPont Krytox) is required for lubrication
on linkage parts. 6. Inspect turbine shaft seals.
Semi-Annually (or more often as required) 7. Check thrust bearing end play.
1. Remove and inspect turbine journal and thrust 8. Remove and check the operation of the turbine
bearings. Sentinel Warning Valve, refer to the product spe-
cific Service manual for instructions.
2. Change and inspect compressor oil filter.
9. Drain and Clean KD turbine Oil Reservoir.
3. Check controls and safety cutouts.
Change oil filter with oil change.
4. Check the steam turbine sentinel warning valve
and steam condenser relief valve to ensure they 10. Clean the steam governor valve according to
are operational. The relief valve should start open- product specific Service instructions.
ing when the sentinel valve opens and should be 11. Perform Oil Analysis on the KG turbine design.
completely open when the pressure in the turbine Change the oil.
casing is 10% above normal pressure.
12. Check and recalibrate pressure gauges. Check all
5. Inspect and clean coupling between turbine and level indicating devices and clean as necessary.
compressor. Disassemble and inspect thoroughly
if any question about reliability 13. Inspect and Clean tubes as necessary in all water
cooled heat exchangers on the system.
6. Operate the turbine without load and inspect gov-
ernor operation. Check for excessive vibrations. 3 Year
7. Check the effectiveness of all steam condensate 1. Open and inspect turbine internals. Refer to SEC-
drains. TION 6 - TURBINE INTERNAL INSPECTION
8. On compressor oil return system: and SECTION 7 - STEAM PURITY/ TURBINE
DEPOSITS for additional information.
Change dehydrator.
2. Inspect the rotor, blades and nozzles for pitting
Check nozzle of eductor for foreign particles. and damage.
Annually (more often if necessary) 3. Inspect the Labyrinth Seals
If quarterly inspection indicates oil is fine, 4. Inspect the bearings for signs of excessive wear.
replacing the oil is not necessary.
5. Inspect the End Seals
46 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 47
FORM 160.67-O2
SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
ISSUE DATE: 4/1/2015
48 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
STEAM TURBINE
GOVERNOR VALVE
STEAM CONDENSER 3
PACKAGE
VACUUM BREAKER
SOLENOID VALVE
TURBINE OIL
COOLING WATER
INLET VALVE
CONDENSER COMPRESSOR
COMPRESSOR OIL
TURBINE COOLING
BOX WATER INLET VALVE
CONTROL
CENTER
POWER
HOT GAS BYPASS PANEL
VALVE
EVAPORATOR
ATMOSPHERIC
RELIEF VALVE
CONDENSATE OVER-
BOARD VALVE
General
The YORK Model YST Centrifugal Liquid Chiller ometry Diffuser Screen as “Stall Detector Voltage”
Unit is completely factory-packaged including; the and is input to the Microboard where it is compared to
evaporator, refrigerant condenser, compressor, steam the Low Limit and High Limit setpoint thresholds to
turbine, lubrication systems, power panel, control cen- determine if the stall noise is acceptable or unaccept-
ter, and all interconnecting unit piping and wiring. The able. The control logic manipulates the VGD actuator
steam condenser package is shipped separately and as necessary to eliminate the stall noise. Refer to the
suitable for direct mounting onto the chiller or mount- OptiView™ Control Center Service Instructions Form
ing along side the chiller. (Refrigerant and oil charges 160.67-M1 for additional details.
shipped separately unless optional condenser isolation
valves are ordered.) Compressor Lubrication System
To provide the required amount of oil under the neces-
Chillers can also be shipped dismantled when required
sary pressure to properly lubricate these parts, a motor
by rigging conditions, but generally it is more econom-
driven submersible oil pump is located in a remote oil
ical to enlarge access openings to accommodate the
sump.
factory assembled unit. Chillers shipped dismantled
MUST be field assembled under the supervision of a Lubrication oil is force-fed to all bearings, gears and
Johnson Controls representative, but otherwise instal- rotating surfaces by the variable speed drive pump
lation will be as described in this instruction. which operates prior to startup, continuously during
operation and during coastdown.
Compressor Variable Geometry
Diffuser (VGD) There are main points within the unit which must be
supplied with forced lubrication as follows:
Certain York compressors are equipped with a Vari-
able Geometry Diffuser (VGD). It is used to reduce ro- 1. Compressor Drive Shaft (Low Speed)
tating stall conditions and associated stall noise. Stall
may occur at low load conditions with high head. A me- a. Shaft seal.
chanical ring, located in the diffuser passage after the b. Front and rear journal bearings – one on
impeller discharge, is mechanically operated through each side of driving gear.
linkages via an electric actuator like that used to op-
erate the pre-rotation vanes. It is closed (extended) to c. Low speed thrust bearing (forward and re-
narrow the diffuser gap. It is opened (retracted) to open verse).
the diffuser gap. An internal actuator end switch pre- 2. Compressor Driven Shaft (High Speed)
vents travel beyond the fully open or closed positions.
In response to a stall condition, the ring is closed as a. Forward and reverse high speed thrust bear-
much as necessary to eliminate the stall. Since stall is ing.
caused by reduced gas flow through the compressor, b. Two journal bearings.
narrowing the diffuser gap reduces the cross sectional
area through which the gas flows, thereby increasing 3. Speed Increasing Gears
the gas velocity through the compressor. a. Meshing surfaces of drive and pinion gear
A stall pressure transducer mounted in the discharge teeth.
scroll of the compressor, detects the pressure pulsa- There is a price option to add dual oil filters on both the
tions created by the stall noise in the compressor dis- compressor and KD steam turbine. (The KG turbine
charge and outputs DC voltage pulsations to the stall has no oil filter.) This provides the capability of chang-
detector board in the OptiView™ Control Center. This ing the oil filters while the system is in operation. The
board converts the voltage pulsations into an analog external oil sump is vented to the compressor suction
voltage that represents the magnitude of the stall noise. to permit refrigerant gas that is boiled off by the elec-
This analog voltage is displayed on the Variable Ge- tric heater in the oil to equalize back to the system.
50 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
COMPRESSOR
OIL
ROTOR EMERGENCY
VARIABLE
SUPPORT OIL RESERVOIR
GEOMETRY
SECTION (Completely Full
SUPPLY DIFFUSER (VGD)
During Operation)
OIL PRESSURE
TRANSDUCER
(high pressure)
IMPELLER
THRUST
COLLAR
THRUST BEARING
PROXIMITY (PINION
PROBE GEAR
SHAFT)
HIGH SPEED
REVERSE
THRUST PRV
BEARING INLET
VANES
DOUBLE
BELLOWS
SHAFT SEAL
LOW SPEED
GEAR REAR
BEARING LOW SPEED
SUMP GEAR
PRESSURE
THRUST
TRANSDUCER OIL RETURN LINE FROM COLLAR
CO
(low pressure) EDUCTOR BLOCK BEARING
BE
OIL
TEMPERATURE LOW SPEED
THERMISTOR THRUST VENT LINE
NE
COVER
OIL FILTER
LIQUID
LEVEL
GAUGE
3-PHASE OIL
HEATER
OIL TEMPERATURE
CONTROL VALVE
LIQUID COOLED
OIL COOLER
COOLING
LIQUID
LD09580
Figure 11 - Schematic Drawing – (YST) Compressor Lubrication System
JOHNSON CONTROLS 51
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
52 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
The turbine requires a main steam block valve (sup- The thrust bearings on KD turbines are double act-
plied by others) for isolation which remains closed ing thrust collars or multi-segmented tilting pad type.
during the slow roll warm-up. This main block valve Thrust collars are simply two rings, one at each side
should also be supplied upstream of the automated of the journal bearing, holding the shaft in place. The
valve (supplied by York) on Auto-Start design sys- multi-segmented tilting pad type is self-adjusting so
tems. A smaller valve called a slow roll bypass valve, that the thrust is equally divided among all the shoes
bypasses the main block valve and is opened to begin on either side of the collar. The thrust bearing is acces-
the slow rolling warm-up. This valve is manual on sible and removable without lifting the top half of the
standard systems and is an automated valve on systems turbine casing.
with Auto Start. The main block valve is opened fully
The thrust bearings on KG turbines are antifriction ball
when operating speed is reached and the bypass valve
bearings. They should be replaced each 20,000 hours
is closed. See the Sequence Of Operation on page 26
or when indicated by vibrations. The thrust bearing is
of this manual for more details.
accessible and removable without lifting the top half of
Chillers manufactured after December the turbine casing.
2006 are NOT supplied with separate
automatic slow roll bypass and main inlet Turbine Lubrication Systems
steam valves. Two types of lubrication are supplied on steam turbines
furnished on YST systems. The smaller turbine design,
KG, has an integral lube system and is used for designs
For speed and overspeed control the turbine has two up to 1700 HP. The larger turbine design, KD, has an
additional valves in the steam supply. Both are auto- external lube system and is used for designs above
matic valves. The governor valve is used to control the 1700 HP.
turbine speed automatically from the control panel.
The other valve is the fast acting butterfly trip valve
which is operated by the chiller control center, the me-
chanical overspeed device, or the manual trip device
that can by actuated by the operator. Refer to the fol-
lowing TURBINE GOVERNOR AND OVERSPEED
CONTROLS section in this manual for additional de-
tails.
JOHNSON CONTROLS 53
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
TURBINE TRIP
VALVE
VACUUM BREAKER LIMIT SWITCH
SOLENOID
TURBINE NOZZLE
VALVE AIR DUMP
SOLENOID VALVE
TURBINE
AUXILIARY
OIL PUMP MOTOR STEAM RING
DRAIN SOLENOID
OIL SHAFT OIL PUMP
RESERVOIR
GLAND LEAK-OFF
OIL COOLER
CONNECTION
INLET THERMOMETER
OIL COOLER TURBINE TRIP
OUTLET THERMOMETER SOLENOID VALVE
OIL FILTER HAND TRIP
OIL COOLER KNOB LD09427a
KG TURBINE (Small)
FIRST STAGE
SENTINEL WARNING VALVE
PRESSURE TRANSMITTER
TURBINE
NOZZLE
VALVE AIR
DUMP
SOLENOID
VALVE
CONSTANT LEVEL
OILER
STEAM RING
TURBINE TRIP VALVE LIMIT SWITCH DRAIN SOLENOID
GLAND LEAK-OFF
TURBINE TRIP SOLENOID VALVE CONNECTION
KG Steam Turbine with Ring Oil Lubrication lube oil reservoir with level gauge, an open motor
The KG turbine models have an integral ring oil lu- driven auxiliary oil pump, (not submersible as on the
brication system built into the turbine. Brass oil rings compressor oil pump), water cooled shell and tube oil
running on the turbine shaft pick up oil from the res- cooler, (with copper tubes), 25 micron full flow oil fil-
ervoirs in the two bearing housings. As the shaft and ter, (dual oil filters available as a price addition). Oil
rings rotate together, oil flows from the oil rings onto temperature control is by a three way temperature con-
the shaft and ultimately into the bearings providing lu- trol valve. The bearing housings are located on each 3
brication. The oil level in the bearing housing must be end of the turbine shaft outboard of the gland seals.
maintained at a sufficient level to allow the oil rings The bearing housings are continuously purged during
to run in the oil. An oil level that is too high results operation with instrument air that has been reduced
in oil leakage past the shaft seals. Oil rings cease to in pressure by a pressure reducing valve. This helps
rotate sufficiently fast below 900 RPM to assure ad- prevent contaminants such as steam from entering the
equate lubrication. During startup, the automatic con- bearing housing. The pressure reducing valve should
trols will shut the turbine down if the turbine does not be checked for maintenance and for outlet pressure
achieve 1200 RPM within 100 seconds after the start from time to time.
is initiated, the turbine trip solenoid is energized, and
KD Turbine Auxiliary Oil Pump
rotation begins. See the Startup Sequence Of Opera-
tion on page 31 of this manual for more details. The On startup, the KD turbine auxiliary oil pump is started
turbine does not have an oil pump, oil filter, external automatically before the turbine is rotated and prior to
oil cooler, or an external oil reservoir. There are two the start of the compressor oil pump. After the turbine
bearing housings which are located on each end of the has been slow roll and ramped up to above 3000 RPM,
turbine shaft outboard of the gland seals. Bearing hous- if the turbine shaft driven oil pump is producing suf-
ings on the KG turbine are directly cooled with water. ficient pressure above the set point of the auxiliary
It is important that the valve in the cooling water outlet oil pump control logic, the auxiliary oil pump will be
line be adjusted so that the temperature of the oil in the stopped. On shutdown for any reason, (except power
bearing housings does not drop below 130°F (54°C). failure) the auxiliary oil pump will be energized when
the turbine slows to 3000 RPM and will continue to
Cooling water must be supplied at 2 GPM (7.0 L/ run until 30 minutes after the turbine has come to rest
min) minimum, 90°F (32°C) maximum, and 150 PSIG to remove excess heat from the bearings.
(1035 kPaG) for the bearing housings.
Do not allow the COOLING WATER Turbine Gland Seal System
to COOL THE BEARING OIL SUMP Gland seals are provided on both the high pressure in-
TEMPERATURE to below 130°F (54°C), let end and low pressure outlet end of the steam turbine
as this may interfere with the action of the to minimize the leakage of steam from the turbine or
oil rings or cause atmospheric moisture to prevent the leakage of air into the turbine. The inlet
condense in the oil reservoir. steam pressure for standard YST turbines can be from
90 to 200 psig depending on the design for the particu-
The bearing housings are continuously purged during lar job. The outlet steam pressure is below atmospher-
operation with instrument air that has been reduced in ic, typically in the neighborhood of 1.5 PSIA. A small
pressure by a pressure reducing valve. This air purge flow of steam through the gland seal is maintained to
helps prevent contaminants such as steam from enter- prevent condensation and a loss of seal in the gland.
ing the bearing housing. The pressure reducing valve Additional details of the standard gland seal systems
should be checked for maintenance and for outlet pres- as well as those that could be supplied on non-standard
sure from time to time. applications such as non-condensing turbines and on
turbines with inlet steam pressures above 200 PSIG are
KD Steam Turbine with External Pressurized described in the following paragraphs.
Lube System
The lubrication system is external but completely fac- Types of Gland Leak-Off Systems
tory assembled into the turbine driveline base. The KD Steam in non-condensing turbines tends to leak around
steam turbines have a shaft mounted main oil pump. the shaft since the pressure in the casing is greater than
The external lubrication system includes an remote atmospheric. Leaks should be limited for the follow-
ing reasons:
JOHNSON CONTROLS 55
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
• Steam finds its way to the bearing housings, con- Gland Seal System: Standard YST
denses there and contaminates the oil. Condensing Turbines
• Efficiency is reduced since escaped steam produc- Turbines are equipped with a gland seal system similar
es no useful work. to that of non-condensing machines, although the func-
tion is different. The purpose of the sealing system is
• Each pound of steam lost requires adding one to keep outside air from leaking into the casing since
pound of make-up water to the boiler. it would reduce the vacuum and cause a loss of power.
• Excessive leaks cause an unpleasant working at- The system is not as effective when the machine is
mosphere. standing idle as when it is operating.
The gland leak-off system for non-condensing appli- The exhaust pressure in the casing is always below
cations and the gland seal system for condensing ma- atmospheric pressure. In the majority of condensing
chines, are used to minimize leaks. This is achieved turbines, the casing pressure is also below atmospheric
with a system that permits steam leakage where the when operating without load but rises above atmo-
gland seals make contact with the shaft, using the pres- spheric, in proportion to the increase in power, when a
sure differential between them as an effective seal. A load is added. As load is applied, steam from the inlet
leak-off connection, just before the exterior inactive gland will escape through the leak-off and supply seal-
seals, is designed so steam reaching that point will run ing to the exhaust gland.
through it instead of the seals.
As the amount of steam moving through the leak-off
Gland seals can either be of the segmented carbon ring connection rises, the excess leak-off steam is dis-
type, the labyrinth type or a combination of both. Un- charged to the atmosphere or some evacuation device.
less one of these two types is specifically mentioned in
this section they will simply be referred to as “gland Gland Seal Wear
seals”. As time goes on, the normal wear of the seals will re-
Carbon Ring Type Glands Have Excel- sult in more steam passing out the leak-off line to sew-
lent Sealing Capabilities When New But er. The steam required to seal the exhaust gland may
Are Subject To Wear. They Should Be go up some, but not as much as the increase in leakage
Replaced Every One To Three Years. Note from the steam gland. Eventually the seals will wear to
That They Lose Effectiveness When The the point where there will be more steam trying to leak
Pressure Differential Is Excessive. to sewer than the line can handle without causing some
backpressure on the seal steam header. This will cause
condensate to start dripping from the exhaust gland. At
Usually, a single leak-off system is enough to seal
that time, the leakage will be excessive from the steam
those turbines operating with moderate temperatures
gland and the seals should be replaced.
and pressures. If a more effective seal is necessary, or
if the working pressures are higher, a double leak-off
Gland Seal Leak-Off Piping
system is used.
Where the rotor shaft passes through the turbine cas-
In these cases, leak-off connections closer to the cas- ing, packing glands of the segmented carbon ring or
ing (interior leak-offs) are connected to the same pipe labyrinth type are provided. These have leak-off con-
and to a header with a steam pressure of 10-20 PSI nections piped to a common point. From This Point,
(non-condensing turbine) or 1-5 PSI (for condensing
The Customer Must Provide Suitable Piping Of A
machines). Exterior connections are either piped to the
Size Indicated On The Outline Drawing.
atmosphere or to an evacuation device.
The best system for any specific application depends If it is necessary to run the pipe for a long distance the
upon the pressures involved, the required efficiency, size should be increased so that back pressure does not
and the availability of low pressure lines at the instal- build up on the packing gland. This pipe must slope
lation site. down from the connection point to avoid forming a wa-
ter trap and must not contain a shut-off valve.
A small amount of steam will pass through this line at
all times. The amount of steam passing through the line
will depend upon the amount of back pressure.
56 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 57
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
The steam ring drain solenoid valve remains energized An automatic pressure powered pump is
(open) during the initial startup. The check valve in the supplied by Johnson Controls when the
steam ring drain line prevents air from being drawn Auto-Start option is ordered.
into the turbine when the turbine steam ring drops be-
low atmospheric pressure during the initial evacuation
and while the turbine is slow rolling. When the inlet
steam valves open to begin slow roll and during the Liquid enters the pump body through the inlet check
ramp up to minimum speed, the steam ring will rise valve causing the float to rise. As the chamber fills
above atmospheric pressure and any condensate will the valve changeover linkage is engaged opening the
be blown out of the turbine. motive supply valve and closing the equalizing valve.
On older manually started chillers, the As motive pressure is above the total back pressure,
steam ring drain is not automated. In this condensate is forced out through the outlet check valve
case, the steam ring drain valve must be into the return system.
manually opened at shutdown and closed Motive pressure for automatic pressure
after the turbine is slow rolling at initial powered pumps cannot exceed a maxi-
start up. mum of 200 PSIG (steam or air may be
used). Application with higher pressure
On standard YST chillers with up-discharge turbine ex-
motive supply must use custom selected
haust, an exhaust casing drain connection is supplied.
condensate drain equipment suitable for
The turbine must be supplied with a means of draining
higher pressures.
the casing during operation (while under vacuum). The
standard Factory supplied option is an automatic pres-
As the liquid level falls within the pump, the float re-
sure powered pump. Also available by special quota-
engages the valve changeover linkage causing the mo-
tion is a condensate drain tank (manual or automatic).
tive supply valve to close and the equalizing valve to
When either option is supplied, it is shipped loose for
open allowing condensate to re-enter through the inlet
installation at the job site.
check valve and the cycle is repeated. Refer to York
On non-condensing turbines with side-discharge tur- standard flow diagram for typical pressure pump pip-
bine exhaust, there is no need for an exhaust casing ing installation.
drain since condensate cannot collect in the turbine ex-
All the piping associated with the installation of the
haust end.
Automatic Pressure Powered Pump is field provided
On any application where the exhaust piping bends and installed .
upward after leaving the turbine, steam traps must be
provided to keep the exhaust line drained to prevent Condensate Drain Tank – Optional Supply by
water from building up in the exhaust pipe and turbine Special Quotation
casing. When ordered, a Factory supplied condensate drain
Failure to keep the exhaust line drained tank is provided for draining the condensate from the
may result in a restriction in the exhaust exhaust end of the steam turbine during operation. The
line, causing a loss of power and damage tank is shipped loose and all piping and installation is
to the turbine rotor. provided by others.
The tank is provided with a high level alarm switch
which is connected to the OptiView™ Control Center
Pressure Powered Condensate Drain Pump to signal the operator that the tank must be manually
drained by closing and opening the appropriate valves
A Factory supplied automatic pressure powered pump to isolate the tank from the turbine during the drain-
is provided for draining condensate from the steam ing process and allow the condensate to drain into the
turbine casing, during operation. The pressure power sewer. If the tank is automated, the tank is provided
pump is shipped loose and all piping and installation with a self contained control panel, float switches, and
is provided by others. solenoid valves to control the draining isolation/drain-
ing process.
58 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 59
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
60 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 61
FORM 160.67-O2
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 4/1/2015
62 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
COMPRESSOR
OIL FROM
TEMPERATURE
CONTROL VALVE
SOLENOID VALVE
DEHYDRATOR
STOP VALVE
LIQUID INJECTION
SOLENOID
(J COMPR. ONLY) OIL TO COMPRESSOR
OIL COOLER LD09607
JOHNSON CONTROLS 63
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
The Compressor Oil Charge ing valve (A) located on the remote oil reservoir
cover plate. Do not tighten the connection at the
The nominal oil charge for all YST compressors is 20
charging valve until after the air is forced out
gallon, type “York K”.
by pumping a few strokes of the oil pump. This
New YORK Refrigeration oil must be used in the cen- fills the lines with oil and prevents air from being
trifugal compressor. Since oil absorbs moisture when pumped into the system.
exposed to the atmosphere, it should be kept tightly 3. Open the oil charging valve and pump oil into the
capped until used. system until oil level in the compressor oil reser-
voir is in the “Over Full” region of the oil level
Compressor Oil Charging Procedure
indicator label. Close the charging valve and dis-
During operation the compressor oil level must be connect the hand oil pump.
maintained in the "Operating Range" identified on the
vertical oil level indicator. If the oil level falls into the 4. As soon as oil charging is complete, ensure that
lower sight glass, it is necessary to add oil to the com- the power is available to the control center and
pressor oil reservoir. The oil should be charged into power panel to energize the oil heater. This will
the oil reservoir using the YORK Oil Charging Pump keep the concentration of refrigerant in the oil to
– YORK Part No. 070-10654. To charge oil into the oil a minimum.
reservoir, proceed as follows: When the oil reservoir is initially charged with oil, the
oil pump should be started manually to fill the lines,
1. The unit must be shut down.
passages, oil cooler and oil filter. This will lower the oil
2. Immerse the suction connection of the oil charging level in the reservoir. It may then be necessary to add
pump in a clean container of new oil and connect oil to bring the level back into the “Operating Range”
the pump discharge connection to the oil charg- of the oil level indicator label.
LD08579
OIL CHARGING VALVE
LD08648
64 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
To Compressor
To Compressor
To Thermostatic
Control Valve
LD010025
Figure 16 - Standard Single Oil Filter And Optional Dual Oil Filter
JOHNSON CONTROLS 65
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
Dual Oil Filter Replacement of the bearing housing indicates the oil level. A mark
The dual oil filter option allows one oil filter to be iso- inscribed on the lower-half bearing housing indicates
lated and changed with the chiller in operation. the proper oil level. Oil levels in both bearing housings
should be checked daily. Always use a strainer when
1. Isolate the left hand filter by turning the valve adding oil to the systems and cover the fill connection
stem parallel with the valve body. 90º counter when finished. If there is any reason to suspect wa-
clockwise. ter in the oil, open the low point drain in each bearing
housings slightly. If water is present, it will be the first
2. Isolate the right hand filter by turning the valve
thing to come out of the drain. Low point drains in the
stem 1/4 turn clockwise.
bearing housing should be checked weekly for water.
Do not force the valve stem past the stop.
Damage to the Isolation Valve will occur. The presence of oil in the constant level
oilers does not necessarily mean that oil
in the bearing housings is at the proper
level. Cleanliness is essential
for long and trouble free service from the
bearings. Care must be taken to ensure
that no foreign material enters bearing
housings or constant level oilers when
performing maintenance, checking oil,
adding oil, or making adjustments.
Table 1 - Recommended Maximum Turbine Bearing, Oil Sump, And Metal Temperatures
RECOMMENDED MAXIMUM TURBINE BEARING, OIL SUMP, AND METAL TEMPERATURES
Bearing Oil Sump Temperature Bearing Metal Temperature
Operating Status °F °C °F °C
Normal Operation 130-180 54-82 150-200 66-93
Alarm 200 93 210* 99
Trip 210 99 220* 104
* Bearing alarm & trip values should be set at 10 °F (5.5 °C) to 15 °F (8.4 °C) above operating temperature when running at unit design condi-
tions. Maximum alarm setting of 210 °F (99 °C) and 220 °F (104 °C) trip.
66 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
Establish an oil change frequency based on oil tests. The most common sources of oil contamination are im-
Otherwise, oil in bearing housings should be changed purities picked up during storage, shipping, or adding
monthly; or earlier, if there is reason to believe that the of the lubricant, dirt in the entrained air, water in the
oil has been contaminated with water, dirt, or by over- oil reservoirs, leaks in the oil cooler, or condensation
heating. The basic turbine oil for new units is a #68 of gland leakage.
which has an average viscosity of 319 SSU @ 100°F.
If there are any doubts about the particular oil for tur- Always use a strainer when adding oil to the systems
bine use, consult the YORK Service Department. and cover the fill connection when finished. Make
sure the gland system works properly. For details, see
Pressure Lubrication Turbine Gland Seal System on page 55 for details. 4
Turbines supplied with pressure lubrication consist of Water gives oil a milky appearance, and it has a ten-
a main oil pump powered by the turbine shaft and a dency to settle at the bottom of the reservoir when the
motor driven auxiliary oil pump. Both pumps draw oil turbine is not running. If there is any reason to suspect
from the oil reservoir that is an integral part of the tur- water in the oil, open the reservoir drain slightly. If
bine base. Pressure relief valves are used in the pres- water is present, it will be the first thing to come out
sure lubricating system to control pressures through of the drain.
the oil filter, oil cooler, piping, and auxiliary oil pump.
Always keep the proper oil level in the sight gauge. The oil in the turbine should be inspected while the
The system must supply continuous lubrication to all equipment is standing idle. If the turbine operates con-
contact surfaces. THE OIL LEVEL SHOULD BE stantly, take a small sample of oil from the reservoir
CHECKED AT LEAST ONCE A DAY OR EVERY 8 and let it sit a few hours. If any water is present it will
HOURS IF THE TURBINE OPERATES 24 HOURS settle to the bottom of the container.
A DAY. Normally, a small amount of oil (of the recom- The probability of oil contamination will increase if:
mended type and viscosity) should be added between
oil changes to maintain the proper oil level. Always use • Gland seals are allowed to become excessively
a strainer when adding oil to the systems and cover the worn, if obstructions are allowed to develop in
fill connection when finished. leak-off piping
If an elevation in the oil level is observed in the sight • If the turbine is allowed to stand idle with back
gauge when no oil has been added, water is probably pressure in the casing of a non-condensing tur-
collecting in the oil. If an abnormal decrease is ob- bine.
served, there are oil leaks in the system. If an unex- • If there is too much sealing pressure on a condens-
plained rise or drop in oil level is observed in the sight ing turbine.
gauge, investigate immediately and stop the chiller if
necessary. Care should be taken to avoid these conditions.
The tendency of oil to oxidize and deteriorate increases When oil is agitated it mixes with air and produces
with temperature. A rise in oil temperature also de- foam. Foam inhibits the ability of oil to lubricate prop-
creases viscosity, which progressively lowers the abil- erly by reducing the oil pressure and causing excessive
ity of oil to lubricate the turbine properly. wear of moving parts, rapid oil deterioration and oxi-
dation, and loss of oil through seepage. The problem is
The operator should frequently observe the tempera- usually solved with oil additives, lowering water flow
tures at the inlet and outlet of the oil cooler. Any dras- to the cooler and circulating the oil at a slightly higher
tic change should be investigated. Keeping a record of (not to exceed 120°) temperature, lowering the oil cir-
temperatures is advisable since it provides a good base culation pressure (not less than 13 PSIG), and main-
for comparison. taining the proper oil level.
Take readings from the pressure gauges every one Sludge impairs oil circulation and causes oil tempera-
or two hours and investigate any change (gradual or ture elevation, which accelerates oxidation and reduces
sudden). The most frequently encountered difficulty lubricant life. Any sludge should be removed as soon
is pressure drop, and the most common causes are as it is found. Using high quality oil and keeping the
clogged oil filter, worn pump, faulty relief valves, in- system free of impurities can minimize sludge forma-
sufficient oil in the reservoir, clogged piping, entrained tion.
air, and temperature elevation.
JOHNSON CONTROLS 67
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
Establish an oil change frequency based on oil tests. Determining Correct Refrigerant
Otherwise, the oil reservoir should be drained and Charge Level
cleaned yearly; or earlier, if there is reason to believe
The refrigerant charge level is correct when the mea-
that the oil has been contaminated with water, dirt, or
sured evaporator approach and discharge refrigerant
by overheating.The basic turbine oil for new units is
gas superheat are within the values listed in Table 2 on
a #32 which has an average viscosity of 162 SSU @
page 68.
100°F. If there are any doubts about the particular oil
for turbine use, consult the YORK Service Department. Important: The chiller must be at design operating
conditions and full load operation before the correct re-
Lube Oil Flushing frigerant charge level can be properly determined.
If the lube system has been contaminated, the oil should
Liquid refrigerant will be visible in the evaporator
be changed and the entire system should be flushed. To
sight glass. The refrigerant level cannot be properly
do this, remove the upper half of the bearing housing,
determined by viewing the liquid refrigerant level in
remove the upper half of both bearings to allow for
the evaporator sight glass.
more volume of oil to flow during the flush. Reseal the
upper bearing housing cover and replace the bolting. All YST Chillers shipped Form 1 are charged with the
correct amount of refrigerant. Under some operating
The following steps should be followed:
conditions the chiller may appear to be overcharged or
1. Install 100 mesh plain weave (.0059 opening) undercharged with refrigerant. Consult with the YORK
screen mesh ahead of all bearing cases. Factory prior to removing or adding refrigerant. The
liquid line isolation valve may have to be partially
2. While viewing the TURBINE SCREEN on the throttled to prevent overfeeding the evaporator in some
OptiView™ Control Center, use the Manual applications and under certain operating conditions.
Pump key and enable manual operation and allow
it to run for two hours. Using the Manual Pump Definitions:
key on the TURBINE SCREEN, shut down the
pump and check all screens for particles. Screens Evaporator Approach = (S.E.T) - (L.E.L.T)
should not have any particles bigger than .01 inch Discharge Superheat = (C.D.G.T) - (S.C.T)
in diameter and show random distribution. No
metallic particles should be present. Flushing Where:
should continue until screens show no more than S.E.T. = Saturated Evaporator Temperature
6 non-metallic particles.
L.E.L.T. = Leaving Evaporator Liquid Temp.
3. Replace screens with new ones and continue
flushing in one-hour intervals until no metallic C.D.G.T. = Compressor Discharge Gas Temp.
particles and no more than 6 non-metallic parti- S.C.T. = Saturated Condensing Temperature
cles are present on any of the screens.
These values can be obtained from the OptiView™
4. Once clean screens are present, remove all Control Center. Refer to OptiView™ Control Center
screens, service the turbine bearings and replace Operation Manual, Form 160.67-O1.
them in the bearing housing. Housings must be
cleaned and resealed with Tite-Seal to prevent oil Table 2 - Refrigerant Charge Level
leaks at the case split line.
Condition R-134a Refrigerant
5. Check the condition and cleanliness of the oil fil- Comfort Cooling Applications
ters furnished on the set and replace them with Evaporator Approach 1°F-5°F
new filters if needed before continuing with the Discharge Superheat 12°F-18°F
start up. Brine (Ice Making) Applications
Evaporator Approach 4°F-8°F
Discharge Superheat 24°F-36°F
68 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
A charging valve is located in the liquid line below the The O-ring straight thread fittings and O-ring face seal
evaporator (See Figure 3 on page 14). The size of fittings are designed and used in accordance with SAE
the charging connection is 3/4 inch male flare. Purge J1926 and J1453. Should it become necessary to remove 4
air and non-condensables from the charging hose. Only a fitting, the O-ring(s) should be replaced. Make cer-
add new refrigerant, or refrigerant that has been tested tain to use only neoprene replacement O-rings. O-rings
and certified to meet American Refrigeration Institute can be ordered from the local Johnson Controls Service
Standard (ARI-700). Office.
Refrigerant Leak Checking Pipe sealant compounds are not required with SAE
type O-ring fittings. The O-ring seal accomplishes the
Periodic refrigerant leak checking must be part of a pressure sealing. Lubricate the O-ring with compressor
comprehensive maintenance program. Leak check the oil prior to assembly.
entire chiller using a calibrated electronic leak detector.
All filter driers and angle shut off valves use Primore
Use a soap solution to confirm leaks that are found us- Rotalock fittings. These fittings use a Teflon fiber
ing the electronic leak detector. seal washer. The Teflon fiber seal washers should be
Check refrigerant relief valve piping and tube rolled replaced each time the filter driers are changed.
joints as part of the comprehensive refrigerant leak
checking program.
JOHNSON CONTROLS 69
FORM 160.67-O2
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 4/1/2015
70 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
SECTION 5 – TROUBLESHOOTING
JOHNSON CONTROLS 71
FORM 160.67-O2
SECTION 5 – TROUBLESHOOTING
ISSUE DATE: 4/1/2015
72 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
SECTION 6 - MAINTENANCE
Renewal Parts Evacuation And Dehydration Of Unit
For any required Renewal Parts, refer to YORK Renew-
al Parts Unit Components Manual 160.67-RP1.
JOHNSON CONTROLS 73
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
Conducting R-22 Pressure Test 2. Open wide all system valves. Be sure all valves to
the atmosphere are closed.
With the R-134a charge removed and all known leaks
repaired, the system should be charged with a small 3. Operate the vacuum pump in accordance with
amount of R-22 mixed with dry nitrogen so that an VACUUM DEHYDRATION until a wet bulb
electronic leak detector can be used to detect any leaks temperature of +32°F or a pressure of 5 mm Hg
too small to be found by the soap test. is reached. See Table 4 for corresponding values
of pressure.
To test with R-22, proceed as follows:
4. To improve evacuation circulate hot water (not
1. Valve off the water side of the evaporator and to exceed 125°F, 51.7ºC) through the evaporator
refrigerant condenser and blow down the bundle and condenser tubes to thoroughly dehydrate the
pressure to 0 PSIG. shells. If a source of hot water is not readily avail-
2. With no pressure in the system, charge R-22 gas able, a portable water heater should be employed.
into the system through the charging valve to a DO NOT USE STEAM. A suggested method is
pressure of 2 PSIG. to connect a hose between the source of hot water
under pressure and the evaporator head drain con-
3. Build up the system pressure with dry nitrogen to nection, out the evaporator vent connection, into
approximately 75 to 100 PSIG (517 to 690 kPa). the condenser head drain and out the condenser
To be sure that the concentration of refrigerant vent. To avoid the possibility of causing leaks, the
has reached all parts of the system, slightly open temperature should be brought up slowly so that
the oil charging valve (If oil charge is not present) the tubes and shell are heated evenly.
and test for the presence of refrigerant with a leak
detector. 5. Close the system charging valve and the stop
valve for the vacuum indicator. Then disconnect
Do not open the oil charging valve if oil
the vacuum pump leaving the vacuum indicator
charge has not been drained. Test for
in place.
R-22 at the condenser service valve if oil
charge is present. 6. Hold the vacuum obtained in Step 3 in the system
for 8 hours; the slightest rise in pressure indicates a
leak or the presence of moisture, or both. If, after 24
4. Test around each joint and factory weld. It is im- hours the wet bulb temperature in the vacuum indi-
portant that this test be thoroughly and carefully cator has not risen above 40°F (4.4°C) or a pressure
done, spending as much time as necessary and us- of 6.3 mm Hg, the system may be considered tight.
ing a good leak detector. Be sure the vacuum indicator is valved off
while holding the system vacuum and be
5. Check if any pressure buildup has occurred in
sure to open the valve between the vacuum
the water side of the evaporator and condenser.
indicator and the system when checking
Open the vents in the evaporator and condenser
the vacuum after the 8 hour period.
heads and test for the presence of refrigerant. If
no refrigerant is present, the tubes and tube sheets
may be considered tight. If refrigerant is detected 7. If the vacuum does not hold for 8 hours within the
at the vents, the heads must be removed, the leak limits specified in Step 6 above, the leak must be
located (by means of soap test or leak detector) and found and repaired.
repaired.
Vacuum Dehydration
Vacuum Testing To obtain a sufficiently dry system, the following in-
After the pressure test has been completed, the vacuum structions have been assembled to provide an effective
test should be conducted as follows: method for evacuating and dehydrating a system in the
field. Although there are several methods of dehydrat-
1. Connect a high capacity vacuum pump, and an ing a system, we are recommending the following, as
indicator to the system as shown in Fig. 15 and it produces one of the best results, and affords a means
start the pump. (See “Vacuum Dehydration”.) of obtaining accurate readings as to the extent of de-
hydration.
74 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
Checking The Refrigerant Charge As a preventive measure against scale and corrosion
During Unit Shutdown and to prolong the life of evaporator and condenser
tubes, a chemical analysis of the water should be made
The refrigerant charge is specified for each chiller
preferably before the system is installed. A reliable wa-
model on the unit data plate. Charge the correct amount
ter treatment company can be consulted to determine
of refrigerant and record the level in the evaporator
whether water treatment is necessary, and if so, to fur-
sight glass.
nish the proper treatment for the particular water con-
The refrigerant charge should always be checked and dition.
trimmed when the system is shut down.
Cleaning Evaporator And Condenser
The refrigerant charge level must be checked after the Tubes
pressure and temperature have equalized between the
condenser and evaporator. This would be expected Evaporator
to be 4 hours or more after the compressor and water It is difficult to determine by any particular test wheth-
pumps are stopped. The level should visible in the sight er possible lack of performance of the water evaporator
glass. is due to fouled tubes alone or due to a combination
of troubles. Trouble which may be due to fouled tubes
Charge the refrigerant in accordance with the method
is indicated when, over a period of time, the cooling
shown under the “Refrigerant Charging”, above. The
capacity decreases and the split (temperature differ-
refrigerant level should be observed and the level re-
ence between water leaving the evaporator and the
corded after initial charging.
refrigerant temperature in the evaporator) increases. A
Handling Refrigerant For gradual drop-off in cooling capacity can also be caused
Dismantling And Repairs by a gradual leak of refrigerant from the system or by a
combination of fouled tubes and shortage of refrigerant
If it becomes necessary to open any part of the refriger- charge. An excessive quantity of oil in the evaporator
ant system for repairs, it will be necessary to remove can also contribute to erratic performance.
the charge before opening any part of the unit. If the
chiller is equipped with optional valves, the refrigerant Condenser
can be isolated in either the condenser or evaporator / In a condenser, trouble due to fouled tubes is usually
compressor while making any necessary repairs. indicated by a steady rise in head pressure, over a pe-
riod of time, accompanied by a steady rise in condens-
Refrigerant Condensers And
ing temperature, and noisy operation. These symptoms
Evaporators
may also be due to foul gas buildup. Purging will re-
General move the foul gas revealing the effect of fouling.
Maintenance of the refrigerant condenser, steam con- Tube Fouling
denser, and evaporator shells is important to provide
trouble free operation of the chiller. The water side of Fouling of the tubes can be due to deposits of two types
the tubes in the shell must be kept clean and free from as follows:
scale. Proper maintenance such as tube cleaning, and
1. Rust or sludge – which finds its way into the
testing for leaks, is covered on the following pages.
tubes and accumulates there. This material usu-
Chemical Water Treatment ally does not build up on the inner tube surfaces
as scale, but does interfere with the heat transfer.
Since the mineral content of the water circulated Rust or sludge can generally be removed from the
through evaporators and condensers varies with almost tubes by a thorough brushing process.
every source of supply, it is possible that the water be-
ing used may corrode the tubes or deposit heat resistant 2. Scale – due to mineral deposits. These deposits,
scale in them. Reliable water treatment companies are even though very thin and scarcely detectable
available in most larger cities to supply a water treat- upon physical inspection, are highly resistant to
ing process which will greatly reduce the corrosive and heat transfer. They can be removed most effec-
scale forming properties of almost any type of water. tively by circulating an acid solution through the
tubes.
76 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS 77
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
4. After the tubes have been corked for 12 to 24 Steam Condenser Condensate Pump
hours, it is recommended that two men working Maintenance
at both ends of the evaporator carefully test each
While the pump is running, re-grease the pump bear-
tube – one man removing corks at one end and
ing with #2 lithium base petroleum grease. This should
the other at the opposite end to remove corks and
be done after every 2500 hours of operation or every 6
handle the leak detector. Start with the top row of
months, whichever occurs first. Lubricate the motor
tubes in the section being investigated. Remove
per the instructions on the nameplate.
the corks at the ends of one tube simultaneously
and insert the exploring tube for 5 seconds – this Steam Condenser Vacuum Pump
should be long enough to draw into the detector Maintenance
any refrigerant gas that might have leaked through
the tube walls. A fan placed at the end of the evap- After approximately 3 years of operation, the rolling-
orator opposite the detector will assure that any contact bearings and the adjacent spaces should have
leakage will travel through the tube to the detec- the spent grease and other dirt deposits removed and be
tor. repacked with fresh grease. The pump must be disas-
sembled for this procedure. UNIREX N3 or equivalent
5. Mark any leaking tubes for later identification. grease per DIN51825-K3N must be used. Different
6. If any of the tube sheet joints are leaking, the leak types of grease should not be mixed. Fill 50% of the
should be indicated by the detector. If a tube sheet free hollow space in the deep-groove ball bearing at
leak is suspected, its exact location may be found the impeller end with grease. Fill the deep-groove ball
by using a soap solution. A continuous buildup of bearing at the motor end flush. Do not fill the bear-
bubbles around a tube indicates a tube sheet leak. ing caps as his could result in an excessive amount of
grease. When re-lubricating or replacing rolling-con-
Compressor Maintenance tact bearings, inspect and replace any worn seals such
as the V ring.
Maintenance for the compressor assembly consists of
checking the operation of the oil return system and Turbine Internal Inspection
changing the dehydrator, checking and changing the
oil, checking and changing the oil filters, checking the To perform the thorough periodic inspections, it will
operation of the oil heater, checking the operation of be necessary to remove the turbine cover. Housed un-
the oil pump, and observing the operation of the com- der that cover are diaphragms, the turbine rotor, nozzle
pressor. block, shaft seals, the stationary blade segment, and the
casing interior. Refer to SECTION 7 - STEAM PURI-
Internal wearing of compressor parts could be a serious TY/TURBINE DEPOSITS for additional information.
problem caused by improper lubrication, brought about
by restricted oil lines, passages, or dirty oil filters. If Inspection of other parts, such as bearings, governor
the unit is shutting down on COMPR OIL - HIGH and linkage, oil pump drive assembly, governor valve
TEMPERATURE or COMPR OIL - LOW DIFFER- and trip valve, can be accomplished without casing
ENTIAL PRESSURE, change the oil filter element. cover removal.
Examine the oil filter element for the presence of alu-
Where turbines have a top exhaust, the inspection pro-
minum particles. Aluminum gas seal rings can contact
cedure is more involved since the exhaust pipe must
the impeller and account for some aluminum particles
first be removed to provide the necessary free space
to accumulate in the oil filter, especially during the ini-
above the turbine. The casing cover can then be re-
tial start up and first several months of operation. How-
moved by the following procedure:
ever, if aluminum particles continue to accumulate and
the same conditions continue to stop the unit operation It should be remembered that the casing assembly is
after a new filter is installed, notify the nearest Johnson a pressure tight vessel and that all joints are necessar-
Controls office to request the presence of a Johnson ily sealed to prevent steam leakage. These include the
Controls Service Technician. main horizontal casing flange, gland case splits and
vertical surfaces.
78 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
These joints have been kept in contact by the bolts After the parts are free, a chain hoist can be used to
while under prolonged exposure to heat and moisture. remove cover and rotor. The lower diaphragm portion
Even though joint compounds have been used at the cannot rise and the upper portion is fastened to it.
factory, which assist sealing and help prevent sticking,
it is to be expected that more or less sticking may oc- No difficulty should be encountered in lifting the cas-
cur from corrosion at one or more of these points. It ing cover. The packing cases employ stainless steel
is therefore necessary to proceed with care in order carbon ring retainer plates. Should the plates stick in
to avoid damage to the rotor and other stationary the packing case, screw an eyebolt in the horizontal
parts. flange and impose a lift strain by means of a hand op-
erated chain hoist while tapping on the upper portion
First, remove sheet metal covering, if provided, insu- of the packing case near the centerline.
lation and piping as required, then all horizontal joint
bolts. There are four tapped holes in the horizontal If it is found that any retainer plates are stuck in the
flange. These are provided for the use of jack-bolts in lower portion, these should be freed up with penetrat-
order to “break” the main casing joint. ing oil. After the retainer plates are all free, the ro-
tor, with retainer plates, may be lifted out with a chain 6
Insert bolts and apply reasonable torque to part the hoist.
joint. In some cases, it may be necessary to use pene-
trating oil and tap on the casing barrel while jack-bolts The diaphragms are removed by rolling out, assisted
are fully tightened. After the joint separates, continue by pulling on a clamp fastened on one corner with a
to raise the casing cover with the jack-bolts. The rotor chain hoist. It may be necessary to free-up the dia-
must remain free and bearing caps must not lift as the phragms with penetrating oil before they can be rolled
cover is raised. out.
Rotating the shaft while raising the cover will assure Before re-assembly, the pressure joints must be com-
that the rotor is not in contact with any parts being pletely cleaned to the bare metal. The joints must then
raised. If the rotor rises with the cover, it indicates that be re-coated with sealing compound using a type that
either the lower half of a diaphragm or a carbon ring will not harden in service. Murray joint compound
retaining plate is rising with the cover. This situation is available for this purpose and will not “freeze” the
is brought about by diaphragm halves sticking together joints.
in or by retainer plates sticking in the casing cover and The joint compound is also suitable as an anti-seize
being free in the base. In either case, the cover should compound or pipe thread sealant. The compound must
be lifted with the jack-bolts only until all the clearance be kept absolutely clean and free of metal particles that
(1/6 to 1/8 inch) is taken up and the rotor starts to rise. might interfere with proper sealing.
Do not lift beyond this point, but retract two diagonally
opposite jack-bolts and rock the cover back and forth. Apply a light even coat, leaving about ¼ inch of the
joint surface on the inside and outside uncoated to
Try to determine where the sticking is occurring so that avoid surplus squeeze-out. Coat only the casing joints
if the rocking does not release the stuck joint, the use and the packing case joints of bolted type packing
of penetrating oil and tapping on the outside of the cas- case. Do not apply closer than ¼ inch to carbon rings.
ing will. Do not use wedges or pry bars between
the joint as this will damage the surface and cause Do not coat diaphragm joints or grooves. Bearing caps
leakage. should not be sealed with high temperature joint com-
pound. Instead, use a material intended for oil tight
If there is persistent sticking of these parts, consider- joints such as “Tite-Seal” or a similar non-hardening
able care must be exercised to free them. Tapping and Teflon-based paste compound.
rocking as described above should be continued; pos-
sibly tapping directly on the circumference of the dia- Refer to the Turbine Tightening Torque Specifications
phragm or retainer plate by inserting a flat bar between at the end of this section when reassembling the tur-
the casing flanges (against the diaphragm or plate) and bine.
tapping on the exposed end.
JOHNSON CONTROLS 79
FORM 160.67-O2
SECTION 6 - MAINTENANCE
ISSUE DATE: 4/1/2015
Check The Casing Interior For The following torques are to be applied to socket
Foreign Material Before Closing. head and hex head capscrews, bolts, and nuts of
The casing cover should be carefully lowered. If it ap- SAE Grade 8, alloy steel and 17-4 Ph stainless
pears to “hang up”, use a slight rocking motion to assist steel.
proper mating of parts. Use the dowels on guide rods Table 6 - Turbine Tightening Torques
to assist positioning. The bolting should be tightened (With Washers)
uniformly, in about three stages, finally achieving ap- Size Final Torque
proximately uniform torque on all bolts of the same 1/4" 120 in.- lbs.
size. If the joint has been properly serviced, it should
5/16" 250 in.- lbs.
be as tight as before the inspection.
3/8" 445 in.- lbs.
Electrical Controls 7/16" 60 ft.- lbs.
1/2" 90 ft. - lbs.
Periodically check that all pressure and temperature
9/16" 130 ft.- lbs.
data fields on the OptiView™ Control Center screens
5/8" 180 ft. - lbs.
display values as expected for the present ambient tem-
peratures and operating conditions. 3/4" 315 ft. - lbs.
7/8" 515 ft. - lbs.
The following torques are to be applied to socket head 1" 770 ft. - lbs.
and hex head capscrews, bolts and nuts of SAE grade
1-1/8" 1100 ft. lbs.
8, alloy steel and 17-4 Ph stainless steel.
1-1/4" 1545 ft. - lbs.
80 JOHNSON CONTROLS
FORM 160.67-O2
ISSUE DATE: 4/1/2015
2. Oil Changing – The oil in the compressor must be Oil Return System
changed annually or earlier if it becomes dark or
1. Change the dehydrator in the oil return system
cloudy. However, quarterly oil analysis can elimi-
semiannually or earlier if the oil return system
nate the need for an annual change provided the
fails to operate.
analysis indicates there is no problem with the oil.
2. When the dehydrator is changed, the nozzle of the
Leak Testing eductor should be checked for any foreign par-
The unit should be leak tested quarterly. Any leaks ticles that may be obstructing the jet.
found must be repaired immediately.
Electrical Controls
Evaporator And Refrigerant 1. All electrical controls should be inspected for ob-
Condenser vious malfunctions.
The major portion of maintenance on the condenser 2. It is important that the factory settings of controls
and evaporator will deal with the maintaining the water (operation and safety) not be changed. If the set-
side of the condenser and evaporator in a clean condi- tings are changed without YORK’s approval, the
tion. warranty will be jeopardized.
The use of untreated water in cooling towers, closed
water systems, etc. frequently results in one or more of
the following:
1. Scale Formation.
2. Corrosion or Rusting.
JOHNSON CONTROLS 81
82
MAINTENANCE REQUIREMENTS FOR YORK YST CHILLERS
CHILLER
Clean Oil Cooler Heat Exchanger Tubes X
Perform Oil Analysis On Compressor Lube Oil1 X
Perform Refrigeration Analysis1 X
Perform Vibration Analysis X
Clean Heat Exchanger Tubes X2
Perform Eddy Current Testing And Inspect Tubes 2-5 Years
Check Operation of all Shutdowns (History Print) X
Conduct Panel Overspeed Test X
Check Operation of Motor Contactors in Power Panel X
Visually Inspect For Leaks / Abnormal Noise X
Check Liquid Ring Seal On Relief Valve &
X
Liquid Ring Vacuum Pumps
Check Conedsate Pump Operation / Seals X
Check Hotwell Liquid Level / Pump X
Lubricate The Hotwell Pump Bearing 6 Months
Check And Tighten All Electrical Connections X
Check Three-Phase Voltage And Current X
STEAM CONDENSER
Inspect / Clean Tubes With Chiller Heat Exchangers X
Clean And Grease Vacuum Pump Bearings 3 Years
JOHNSON CONTROLS
ISSUE DATE: 4/1/2015
FORM 160.67-O2
160.67-MR1 (614)
Issue Date: 6/20/2014
PROCEDURE DAILY WEEKLY MONTHLY YEARLY
Visual Inspection (external damage, leaks) X
Check Oil Level in Reservoir (and Governor If Applicable) X
Check for Unusual Vibration / Noise X
FORM 160.67-O2
JOHNSON CONTROLS
Check Aux. Oil Pump Operation (KD Only) X
Check Shafts (free of Oil and Grease) X
Exercise Trip Valve Remote Knob Operation X
Check Oil System Operation X
Verify Operation / Setting / Calibration of Safety Controls1 X
Leak Check and Repair Leaks as Needed1 X
Check Oil and Filter X
Remove / Clean Steam Strainer X
TURBINE
Check Thrust Bearing End Play X
Remove / Check Operation Sentinel Warning Valve X
Drain / Clean Oil Reservoir X
Drain / Clean Governor (If Applicable) X
Change Filter with Oil Change X
Check / Recalibrate Gauges X
Open / Inspect Turbine / Replace as Required 3 Years
Rotor 3 Years
Labyrinth Seals 3 Years
Bearings 3 Years
Gland Seals 3 Years
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls Service Office.
1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of Johnson Controls equipment. A record of
this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
2
More frequent service may be required depending on local operating conditions.
160.67-MR1 (614)
Issue Date: 6/20/2014
83
SECTION 7 - PREVENTIVE MAINTENANCE
7
84
CENTRIFUGAL Chiller Location
LIQUID CHILLER LOG SHEET System No.
DATE
TIME
Hour Meter Reading
O.A. Temperature Dry Bulb / Wet Bulb / / / / / / / / /
Oil Level
Oil Pressure
Oil Temperature
Compressor
SECTION 7 - PREVENTIVE MAINTENANCE
Evaporator
Liquid Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
Condenser Pressure
Corresponding Temperature
Subcooler Liquid Temperature
Refrigerant
Small Temperature Difference
Refrigerant Level %
Refrigerant Level Setpoint
Supply Temperature
Condenser
Supply Pressure
Liquid Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
- CONTINUED ON REVERSE -
160.67-MR1 (614)
Supersedes: 160.67-MR1 (514)
Issue Date: June 20, 2014
JOHNSON CONTROLS
ISSUE DATE: 4/1/2015
FORM 160.67-O2
CENTRIFUGAL Chiller Location
LIQUID CHILLER LOG SHEET System No.
FORM 160.67-O2
DATE
TIME
ISSUE DATE: 4/1/2015
JOHNSON CONTROLS
Hour Meter Reading
O.A. Temperature Dry Bulb / Wet Bulb / / / / / / / / /
Oil Level
Oil Pressure *(KD Only)
Oil Temperature
Bearing Temp. DE & NDE
Inlet Steam Pressure
Turbine
Inlet Steam Temperature
First Stage Pressure
Exhaust Pressure
Vibration Level DE & NDE
Gov. & Trip Valve Supply Air Press.
Hotwell Level %
Steam Condenser Hotwell Level Setpoint
Leaving Water Temperature
Remarks:
160.67-MR1 (614)
Supersedes: 160.67-MR1 (514)
Issue Date: June 20, 2014
85
SECTION 7 - PREVENTIVE MAINTENANCE
7
FORM 160.67-O2
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 4/1/2015
To avoid these deposits, adequate boiler water chem- • Reduced power output.
istry control and other precautions are required along • Increased active thrust with increased oil or bear-
with the need for constant surveillance during opera- ing temperatures in the thrust bearing.
tion and inspections. When deposits or material attack
are noted during inspections, investigations into the • Excessive vibration
nature and origin of contaminants should be conducted If deposits are observed in the turbine during inspec-
and a program for corrective action begun tion, samples should be taken and submitted for chemi-
cal analysis by a laboratory to determine their make-up
Steam Purity
and what action is required to remove them from the
Deposits and harmful ions come from additive chemi- system.
cal elements in boiler feedwater. Make-up water for
many steam systems utilizing Murray turbines is in- Detection Of Corrosion
dustrial grade water which contains dissolved and sus- Indications of corrosion may be difficult to determine.
pended contaminants which must be removed prior to A steam turbine’s efficient performance dictates that
use in the steam system. it’s steam path possess tight corners and crevices.
To avoid the likelihood of adverse effects from depos- These areas can be susceptible to pitting due to the col-
its and harmful ions, limits shown in Table 7 are estab- lection of condensate that possesses harmful ions.
lished for steam turbines. These limits are based on The turbine’s blade and first stage nozzles should be in-
operating history and recommendations from various spected during scheduled shutdown using a bore scope.
consultants. Their maintenance will ensure protection If possible the upper half casing should be removed,
of the turbine. under supervision of a YORK Service Representative
Warranty may be void in the event opera- for better inspection.
tional failure is attributed to inadequate
boiler feed water treatment. Pitting of the blades and nozzles is evidence of a cor-
rosive attack, making them susceptible to stress cor-
rosion cracking. YORK Service should be consulted
prior to the restart of the turbine. If residue or conden-
sate is present in the turbine and corrosion is present,
Effects Of Deposits And Harmful samples of the residue or condensate should be submit-
Ions On Turbine ted for chemical analysis to determine the presence of
Efficiencies in a steam turbine are sensitive to surface excessive chlorides and other harmful ions.
finish because of the high velocities and sharp turning
that are required by the design. While corrosion and
stress corrosion problems are unusual in steam plants,
such problems can result from boiler carry-over due
to inadequate de-aeration and boiler feed-water treat-
ment.
86 JOHNSON CONTROLS
FORM 160.67-O2
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 4/1/2015
Table 7 - Recommended Limits For Boiler Water (Based On Drum Water Analyses).
Pressure at
Total OH
Outlet of Steam Silica Phosphate Sulfite Hardness Chlorides
Solids Alkalinity
Generating Unit, ppm ppm ppm ppm ppm
ppm ppm
PSIG
0-150 2,000 200 50 50 30 0 250
151-450 1,500 100 35 50 30 0 200
451-750 1,000 60 25 25 25 0 150
751-900 750 55 10 25 20 0 50
JOHNSON CONTROLS 87
FORM 160.67-O2
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 4/1/2015
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
88 JOHNSON CONTROLS
FORM 160.67-O2
Notes
ISSUE DATE: 4/1/2015
Notes
JOHNSON CONTROLS 89