Contents
Preface 1
Product Overview 2
SIMATIC
Configuration Options 3
Configuring and
ET 200S Assigning Parameters 4
Distributed I/O System Address Assignment and
5
Installation
Fail-Safe Modules
Wiring and Fitting Modules 6
Manual 7
Diagnostics
Edition 04/2004
A5E00103686-02
Safety Guidelines
This manual contains notices intended to ensure personal safety, as well as to protect the products and
connected equipment against damage. These notices are highlighted by the symbols shown below and
graded according to severity by the following texts:
Danger
! indicates that death, severe personal injury or substantial property damage will result if proper
precautions are not taken.
Warning
! indicates that death, severe personal injury or substantial property damage can result if proper
precautions are not taken.
Caution
! indicates that minor personal injury can result if proper precautions are not taken.
Caution
indicates that property damage can result if proper precautions are not taken.
Notice
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons
are defined as persons who are authorized to commission, to ground and to tag circuits, equipment, and
systems in accordance with established safety practices and standards.
Correct Usage
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed
correctly, and operated and maintained as recommended.
Trademarks
SIMATIC®, SIMATIC HMI® and SIMATIC NET® are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to trademarks
might infringe upon the rights of the trademark owners.
Copyright © Siemens AG 2004 All rights reserved Disclaimer of Liability
The reproduction, transmission or use of this document or its We have checked the contents of this manual for agreement with
contents is not permitted without express written authority. the hardware and software described. Since deviations cannot be
Offenders will be liable for damages. All rights, including rights precluded entirely, we cannot guarantee full agreement. However,
created by patent grant or registration of a utility model or design, the data in this manual are reviewed regularly and any necessary
are reserved. corrections included in subsequent editions. Suggestions for
improvement are welcomed.
Siemens AG
Bereich Automation and Drives
Geschaeftsgebiet Industrial Automation Systems ©Siemens AG 2004
Postfach 4848, D- 90327 Nuernberg Technical data subject to change.
Siemens Aktiengesellschaft A5E00103686-02
Contents
What's New
Compared with the previous version, this manual includes the following major
changes/additions:
• New PM-E F pp DC24V PROFIsafe power module
• PM-D F DC24V PROFIsafe power module has been added
• Change in the name of the PM-E F DC24V PROFIsafe power module:
⇒ new PM-E F pm DC24V PROFIsafe
• PM-E F pm DC24V PROFIsafe power module and
4 F-DO DC24V/2A PROFIsafe electronic module with selectable "readback
time“
• 4/8 F-DI DC24V PROFIsafe electronic module with selectable "discrepancy
behavior“
Approvals
See Section 8.2 Standards and Approvals
In addition, ET 200S fail-safe modules are certified for use in safety mode up to the
following levels:
• Safety class SIL3 (Safety Integrity Level) in compliance with IEC 61508
• Requirements class (AK) 6 in accordance with DIN V 19250 (DIN V VDE 0801)
• Category 4 in accordance with EN 954-1
CE Certification
See Section 8.2 Standards and Approvals
Standards
See Section 8.2 Standards and Approvals
Conventions
In this manual, the terms "safety engineering" and "fail-safe engineering" are used
synonymously. The same applies to the terms "fail-safe" and "F-."
"S7 Distributed Safety" and "S7 F Systems" in italics refer to the optional packages
for the two fail-safe systems: "S7 Distributed Safety" and "Programmable
Controllers S7 F/FH Systems".
Additional Support
If you have any additional questions about the use of products presented in this
manual, contact your local Siemens representative:
http://www.siemens.com/automation/partner
Training Center
We offer courses to help you get started with the S7 automation system. Contact
your regional training center or the central training center in Nuremberg (90327),
Federal Republic of Germany.
Telephone +49 (911) 895–3200
Internet: http://www.sitrain.com
H/F Competence Center
The H/F Competence Center in Nuremberg offers special workshops on SIMATIC
S7 fail-safe and redundant automation systems. The H/F Competence Center can
also provide assistance with onsite configuration, commissioning, and
troubleshooting.
Telephone: +49 (911) 895-4759
Fax: +49 (911) 895-5193
For questions about workshops, etc.: hf-cc@nbgm.siemens.de
Nuremberg
Worldwide (Nuernberg)
Technical Support
Phone: +49 (180) 5050-222 Phone: +1 (423) 262 2522 Phone: +86 10 64 75 75 75
Fax: +49 (180) 5050-223 Fax: +1 (423) 262 2289 Fax: +86 10 64 74 74 74
The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.
2.1 Introduction
Overview
This chapter provides information about the following topics:
• ET 200S distributed I/O system with fail-safe modules and its place in
SIMATIC S7 fail-safe automation systems
• Components comprising the ET 200S distributed I/O system with fail-safe
modules
• The steps required from selecting F-modules to commissioning ET 200S on
PROFIBUS-DP
Note
The operators of systems with safety-related characteristics must adhere to
operational safety requirements. The supplier is also obliged to comply with
special product monitoring measures. To keep you informed, a special newsletter
is therefore available containing information on product developments and
properties that are important (or potentially important) for operating systems
where safety is an issue. By subscribing to the appropriate newsletter, you will
ensure that you are always up-to-date and able to make changes to your system,
when necessary. At the following Internet address:
http://my.ad.siemens.de/myAnD/guiThemes2Select.asp?subjectID=2&lang=en
you too can register for the following newsletters:
• SIMATIC S7-300
• SIMATIC S7-400
• Distributed I/O
• SIMATIC Industrial Software
To receive these newsletters, select the "Updates" check box.
Use in F-Systems
Fail-safe ET 200S modules can be used:
• In the S7 Distributed Safety F-system with the S7 Distributed Safety optional
package as of version V 5.1
• In S7 F/FH Systems with the S7 F Systems optional package as of version
V 5.2
When using fail-safe ET 200S I/O modules in F-systems, the information in the
following manuals applies:
• ET 200S Distributed I/O System
• Safety Engineering in SIMATIC S7
• S7 Distributed Safety, Configuration and Programming or Programmable
Controllers S7 F/FH Systems
S7-300 with
CPU 315F-2 DP ET 200M
Fail-safe signal
modules
Fail-Safe
Modules
PROFIBUS DP
ET 200S
ET 200S
Introduction
In the following table, you will find all the important steps you must perform to
commission ET 200S distributed I/O systems with fail-safe modules as DP slaves
on PROFIBUS DP.
Note
You must configure and assign parameters to the F-modules in STEP 7 before
commissioning them.
Reason: The PROFIsafe addresses of F-modules are assigned automatically by
STEP 7. You must set these PROFIsafe addresses on each F-module by means
of switches before mounting the module.
3.1 Introduction
Overview
This chapter provides information about the following topics:
• Fail-safe modules that can be used to configure an ET 200S distributed I/O
system
• Terminal, F-power and F-electronic modules that can be used together
• Number of fail-safe modules that can be used per ET 200S
• Maximum configuration per voltage group
Introduction
You can configure ET 200S distributed I/O systems with standard and fail-safe
modules. This chapter present an example configuration.
Terminal module
Fail-Safe Modules
Warning
! Please note that for AK6/SIL3/Category 4, mixing F-DI-/F-DO modules and
standard DI-/DO-/FM modules within a voltage group is not permitted.
For AK4/SIL2/Category 3, mixing F-DI-/F-DO modules and standard DI-/
DO-/FM modules within a voltage group is permitted.
1 2 3 4 5 6 7 8 Slot
PM-E DC24..48V
IM151-1 HIGH
Terminal
FEATURE
d l
PM-D F DC24V
PROFIsafe
F-CM
3~
M M
3~ 3~
Figure 3-2 Example of an ET 200S Configuration with Fail-Safe Motor Starters and Connection Multiplier
Introduction
This section presents the following module assignments for ET 200S:
• F-power modules to terminal modules
• F-electronic modules to terminal modules
• Power modules to electronic modules/motor starters
Table 3-3 Assigning Power Modules to Electronic Modules/Motor Starters and Safety
Class (Safety Integrity Level)
Example
In the following example, modules with a total parameter length of 224 bytes have
been used in an ET 200S. This means that 20 bytes are still available for inserting
additional modules.
Requirements
One of the following optional packages must be installed in STEP 7 to configure
and assign parameters to ET 200S fail-safe modules:
• S7 Distributed Safety, Version V 5.1 or higher
• S7 F Systems, Version V 5.2 or higher
For the power module PM-E F pp DC24V PROFIsafe, the following are required:
• STEP 7 V 5.2 and higher
• F Configuration Pack, V 5.3 Service Pack 2 and higher
The F Configuration Pack can be downloaded from the Internet at:
http://www.siemens.com/automation/service&support.
Configuration
Follow the usual procedure with STEP 7 HW Config to configure fail-safe modules
(in the same way as standard ET 200S modules).
5.1 Introduction
Overview
This chapter provides information about the following topics:
• Addresses of the fail-safe modules in the F-CPU
• Assigning the PROFIsafe address for fail-safe modules
• Installing Fail-Safe Modules
Address Assignment
The fail-safe modules occupy the following address ranges in the F-CPU:
• For S7 Distributed Safety: in the process image range
• For S7 F/FH systems: in the entire I/O range (inside and outside the
process image)
Warning
! You must only access the addresses occupied by useful data. The other address
ranges occupied by the F-modules are assigned for functions including safety-
related communication between the F-modules and F-CPU in accordance with
PROFIsafe.
In 1oo2 evaluation of sensors, only the less significant channel of the channels
that are grouped as a result of the 1oo2 sensor evaluation can be accessed in the
safety program.
Additional Information
Detailed information on F-I/O access can be found in the S7 Distributed Safety,
Configuring and Programming manual or the Programmable Controllers S7 F/FH
Systems manual.
PROFIsafe Address
Each fail-safe module has its own PROFIsafe address in addition to the
PROFIBUS address. Before installing fail-safe modules, you must set the
PROFIsafe address on each F-module.
Note
Fail-safe modules in ET 200S can only be used in safety mode.
Example:Address 1018
9 8 7 6 54 3 2 1 0
ON
OFF
512
32
256
128
64
16
8
4
2
1
Figure 5-1 Example for Setting the Address Switch (DIP Switch)
Warning
! • Make sure that the address switch setting on the module matches the
PROFIsafe address in STEP 7 HW Config.
• The switch setting on the address switch of the F-I/O, in other words, its
PROFIsafe destination address must be unique within the network* and
station** (throughout the system). A maximum of 1,022 PROFIsafe
destination addresses can be assigned in one system. That is, a
maximum of 1,022 F-modules can be addressed using PROFIsafe.
Exception: In different I-slaves, F I/Os can have the same PROFIsafe target
address since they are only addresses within the station, in other words by the
F-CPU in the I-slave.
• The following restriction applies only to F-modules of the ET 200S, whose
preset PROFIsafe addresses cannot be modified in HW Config:
If you use F-modules of the ET 200S in a PROFIBUS network, whose
PROFIsafe addresses cannot be modified in HW Config, you can only operate
one DP master with an F-CPU in this network, otherwise the network-wide
uniqueness of the PROFIsafe addresses is not guaranteed.
5.4 Installation
Mounting Dimensions
Note that fail-safe modules are 30 mm wide (twice as wide as standard ET 200S
modules). Otherwise, information provided in the ET 200S Distributed I/O System
manual is applicable.
6.1 Introduction
Warning
! In order to prevent hazardous threats to persons or the environment, you must
not under any circumstances override safety functions or implement measures
that cause safety functions to be bypassed or that result in the bypassing of
safety functions. The manufacturer is not liable for the consequences of such
manipulations or for damages that result from failure to heed this warning.
Overview
This chapter presents special features involved in wiring and fitting fail-safe
modules. Information on this subject that applies to both ET 200S with fail-safe
modules and ET 200S with standard modules can be found in the ET 200S
Distributed I/O System manual.
Warning
! Fail-safe modules must be operated with safe functional extra low voltage. This
means that these modules, even in the event of a fault, can only have a
maximum voltage of Um. The following applies for all fail-safe modules:
Um < 60.0 V
You can find additional information about safe functional extra low voltage, for
example, in the data sheets of the applicable power supplies.
All components of the system that are capable of supplying electrical energy in any
form must satisfy this requirement.
Each additional circuit (24 VDC) implemented must have a safe functional extra
low voltage. Refer to the relevant data sheets or contact the manufacturer for this
information.
Note, too, that sensors and actuators having an external power supply can be
connected to F-modules. Once again, make sure that the supply voltage is safe
functional extra-low voltage. The process signal of a 24 VDC digital module must
not exceed a fault voltage of Um in the event of a fault.
Warning
! All power sources, for example internal 24 V DC load voltage power supplies,
external 24 V DC load voltage power supplies, 5 V DC bus voltage must be
electrically connected externally. This prevents voltage additions in the individual
voltage sources that would cause the fault voltage Um to be exceeded even if
there are voltage differences. Ensure that there is sufficient line cross section for
the electrical connection, in accordance with the ET 200S configuration
guidelines (see ET 200S Distributed I/O System manual).
Note
You must use only power packs or power supplies (230 VAC --> 24 VDC) with a
power failure ride-through of at least 20 ms to comply with NAMUR
recommendation NE 21, IEC 61131-2, and EN 298. The following power supply
board components are available, for example:
S7-400:
• 6ES7 407-0KA01-0AA0 for 10 A
• 6ES7 407-0KR00-0AA0 for 10 A
S7-300 (fixed to standard mounting rail with installation adapter
(6ES7 390-6BA00-0AA0)):
• 6ES7 307-1BA00-0AA0 for 2 A
• 6ES7 307-1EA00-0AA0 for 5 A
• 6ES7 307-1KA00-0AA0 for 10 A,
ET 200S:
• 6ES7 138-4JC00-0AA0 for 5 A.
These requirements also apply, of course, to power packs and power supplies
with a construction different from that of the ET 200 S or S7-300/440.
Warning
! When assigning signals of the F-DI module, remember that signals should only
be routed within a cable or a nonmetallic sheathed cable if:
• A short circuit in the signals does not conceal a serious safety risk
• Signals are supplied by different sensor supplies of this F-DI module
Mounting Rails
Only 35 x 15 mm zinc-plated mounting rails in accordance with EN 50022 can be
used for installing ET 200S with fail-safe modules. Mounting rails with the following
order numbers, for example, comply with this requirement:
• 6ES5 710-8MA11
• 6ES5 710-8MA21
• 6ES5 710-8MA31
• 6ES5 710-8MA41
Note
Note that replacing fail-safe modules in ET 200S during operation causes a
communication error on the F-CPU.
You must acknowledge the communication error in your safety program (for the
response of the F-system after communication errors, output of a fail-safe value
and user acknowledgment, refer to the manual S7 Distributed Safety,
Configuration and Programming or Programmable Controllers S7 F/FH Systems).
If the communication error is not acknowledged, the useful data of the F-DO
modules remain passivated (outputs at "0").
Table 6-1 Conditions for Inserting and Removing Fail-Safe Modules During Operation
Warning
! The use of sensors and actuators is outside of our sphere of influence. We have
equipped our electronics with such safety engineering features as to leave 85%
of the maximum permissible probability of hazardous faults for sensors and
actuators up to you. (This corresponds to the recommended load division in
safety engineering between sensing devices, actuating devices, and electronic
switching for input, processing, and output).
Note, therefore, that instrumentation with sensors and accouters bears a
considerable safety responsibility. Consider, too, that sensors and actuators do
not generally withstand proof-test intervals of 10 years according to IEC 61508
without considerable loss of safety.
The probability of hazardous faults and the rate of occurrence of hazardous faults
of a safety function must comply with an upper limit determined by a safety
integrity level (SIL). You will find a listing of values achieved by F-modules under
"Fail-Safe Performance Characteristics" in the technical specifications for
F-modules in Chapter 9.
To achieve SIL3 (AK6/Catefgory 4), suitably qualified sensors are necessary.
Warning
! • In order to guarantee accurate detection of the sensor signal by the F-DI
module, you must ensure that the sensor signals have a particular minimum
duration.
• For pulses to be detected with certainty, the time between two signal changes
(pulse duration) must be greater than the PROFIsafe monitoring time.
Table 6-2 Minimum Duration of the Sensor Signals to Allow Correct Acquisition by the
F-DI Module
Warning
! If the actuators are operated at voltages higher than 24 VDC (for example, 230
VDC) or if the actuators clear higher voltages, safe isolation must be ensured
between the outputs of a fail-safe output module and the components carrying a
higher voltage (in accordance with EN 50178).
This is generally the case for relays and contactors. Particular attention must be
paid to this aspect for semiconductor switching devices.
7.1 Introduction
Overview
This chapter provides information about the following topics:
• Reactions to faults in F-modules
• Diagnostics for F-modules in the event of a fault
Warning
! For channels that you set to "deactivated" in STEP 7, there is no diagnostic
reaction or error handling if a channel fault occurs, not even when such a channel
is affected indirectly by a channel group error ("Channel activated/deactivated“
parameter, see sections on special modules Sections 9.2 through 9.6).
Definition
Diagnostics are used to determine whether fail-safe module signal acquisition is
taking place without errors. Diagnostic information is assigned either to one
channel or to the entire F-module.
Warning
! Diagnostic functions should be activated or deactivated in accordance with the
application.
Slave Diagnostics
Slave diagnostics complies with the IEC 61784-1:2002 ED1 CP 3/1 standard. The
fail-safe electronic and power modules support slave diagnostics in exactly the
same way as the standard ET 200S modules.
You will find a description of the general configuration of slave diagnostics for
ET 200S and the fail-safe modules in the ET 200S Distributed I/O System manual.
A supplementary description of channel-related diagnostics for fail-safe modules is
presented below.
Channel-Related Diagnostics
As with the ET 200S, there are three bytes available for channel-related
diagnostics starting at byte 35 for each F-module. A maximum of 9 channel-related
diagnostic messages are possible per station. Channel-related diagnostics for fail-
safe modules are configured as follows:
7 6 5 4 3 2 1 0 Bit no.
Byte35 1 0
Note
In byte 35, bit 0 to 5, the module slot is encoded. The following applies:
Displayed number +1 = slot of the module (0 = slot 1; 1 = slot 2 etc.)
Note
Channel-related diagnostics are always updated to the current diagnostic function
in the diagnostic message frame. Subsequent, older diagnostic functions are not
deleted.
Remedy: Evaluate the valid current length of the diagnostic message frame in
STEP 7 using the RET_VAL parameter of SFC13.
8.1 Introduction
Overview
This chapter presents the following information about fail-safe modules:
• Information about the most important standards and approvals
• Information about the general technical specifications
CE Certification
The fail-safe modules of the ET 200S satisfy the requirements and safety
objectives of the following European Community directives and comply with
the harmonized European standards (EN) for programmable logic controllers
published in the Gazette of the European Community:
• 73/23/EEC ”Electrical Equipment Designed for Use within Certain
Voltage Limits” (low voltage directive)
• 89/336/EWG ”Electromagnetic Compatibility” (EMC Guideline)
• 94/9/EC "Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres" (Explosion Protection Guideline):
UL approval
CSA approval
or
or
Note
The nameplate of the specific module indicates the currently valid approvals.
FM approval
Warning
! There is a risk of personal injury or property damage.
In areas exposed to explosion hazard, personal injury or property damage can
occur if plug-in connections are disconnected during operation.
Before disconnecting plug-in connections in areas exposed to explosion hazard,
always deenergize the distributed I/O.
IEC 61131
The fail-safe modules of the ET 200S satisfy the requirements and criteria of
IEC 61131-2 (Programmable Controllers - Part 2: Equipment Requirements and
Tests).
PROFIBUS Standard
The ET 200S distributed I/O system is based on the
IEC 61784-1:2002 Ed1 CP 3/1 standard.
Shipbuilding Approval
Submitted to the following classification bodies:
(Exception: PM-D F DC24V PROFIsafe submitted only to GL (German Lloyd) )
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
Use in Industry
SIMATIC products are designed for use in industrial environments.
Introduction
This chapter presents information about immunity to interference of fail-safe
modules and about EMC conformity.
Definition of EMC
Electromagnetic compatibility is the ability of an electrical device to function in its
electromagnetic environment in a satisfactory manner without affecting this
environment.
Fail-safe modules also comply with the requirements of the EMC law for the
European internal market. As a requirement, the ET 200S distributed I/O system
must comply with the specifications and guidelines for electrical configuration.
Pulse-Shaped Interference
The following table presents the electromagnetic compatibility of fail-safe modules
with regard to pulse-shaped interference.
Note
Lightning protection measures always require a case-by-case examination of the
entire system. Nearly complete protection from overvoltages, however, can only
be achieved if the entire building surroundings have been designed for
overvoltage protection. In particular, this involves structural measures in the
building design phase.
Therefore, for detailed information regarding overvoltage protection, we
recommend that you contact your Siemens representative or a company
specializing in lightning protection.
Sinusoidal Interference
HF radiation of the device in accordance with IEC 61000-4-3:
• Electromagnetic HF field, amplitude modulated:
• HF coupling with signal lines and data lines, etc. complying with
IEC 61000-4-6, high frequency, asymmetric, amplitude-modulated:
Conditions of Use
Fail-safe modules are intended for use as permanently installed modules protected
from the elements. The conditions of use exceed the requirements of IEC 61131-2.
Fail-safe modules comply with the conditions of use of Class 3C3 in accordance
with DIN EN 60721 3-3 (use in locations with heavy traffic and in the immediate
vicinity of industrial systems with chemical emissions).
Restrictions
Fail-safe modules cannot be implemented in the following locations without
additional measures being taken:
• Locations with a high level of ionizing radiation
• Locations with severe operating conditions; for example, due to
- Dust
- Corrosive vapors or gases
• Systems that require special monitoring, such as:
- Electrical systems in particularly hazardous areas
An additional measure for implementing fail-safe modules can be, for example,
installing the ET 200S in cabinets.
Reduction of Oscillation
If fail-safe modules are subjected to sizable shock pulses or oscillation, you must
take appropriate measures to reduce acceleration and amplitude.
We recommend that you mount the ET 200S on cushioning material (for example,
on a rubber-metal vibration damper).
Test Voltages
Isolation stability is proven in routine testing with the following test voltages in
accordance with IEC 61131 Part 2:
Protection Class
Protection class I in accordance with IEC 60536 (VDE 0106, Part 1), i.e., ground
terminal required on DIN rail!
Type of Protection
Type of protection IP20 according to EN 60529 for all fail-safe modules, in other
words:
• Protection from contact with standard probes.
• Protection from foreign bodies larger than 12.5 mm in diameter is applicable.
• No special protection against water.
Zone 2
Explosionsgefährdete Bereiche werden in Zonen eingeteilt. Die Zonen werden
nach der Wahrscheinlichkeit des Vorhandenseins einer explosionsfähigen
Atmosphäre unterschieden.
Nachfolgend finden Sie wichtige Hinweise für die Installation der fehlersicheren
Module im explosionsgefährdeten Bereich.
Fertigungsort
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Hinweis
Module mit der Zulassung II 3 G EEx nA II T4 .. T5 dürfen nur in Dezentrale
Peripheriesysteme ET 200S der Gerätekategorie 3 eingesetzt werden.
Instandhaltung
Für eine Reparatur muss die betroffene Komponente an den Fertigungsort
geschickt werden. Nur dort darf die Reparatur durchgeführt werden.
Besondere Bedingungen
• Die fehlersicheren Module müssen in einen Schaltschrank oder ein metallisches
Gehäuse eingebaut werden. Diese müssen mindestens die Schutzart IP54
(nach EN 60529) gewährleisten. Dabei sind die Umgebungsbedingungen zu
berücksichtigen, in denen das Gerät installiert wird. Für das Gehäuse muss
eine Herstellererklärung für Zone 2 vorliegen (gemäß EN 50021).
• Wenn am Kabel bzw. an der Kabeleinführung dieses Gehäuses unter Betriebs-
bedingungen eine Temperatur > 70 °C erreicht wird oder wenn unter Betriebs-
bedingungen die Temperatur an der Aderverzweigung > 80 °C sein kann,
müssen die Temperatureigenschaften der Kabel mit den tatsächlich
gemessenen Temperaturen übereinstimmen.
• Die eingesetzten Kabeleinführungen müssen der geforderten IP-Schutzart und
dem Abschnitt 7.2 (gemäß EN 50021) entsprechen.
• Alle Geräte, einschließlich Schalter etc., die an den Ein- und Ausgängen von
fehlersicheren Modulen angeschlossen werden, müssen für den Explosions-
schutz Typ EEx nA oder EEx nC genehmigt sein.
• Es müssen Maßnahmen getroffen werden, dass die Nennspannung durch
Transienten um nicht mehr als 40 % überschritten werden kann.
• Umgebungstemperaturbereich: 0 °C bis 60 °C
• Innerhalb des Gehäuses ist an einem nach dem Öffnen gut sichtbaren Platz ein
Schild mit folgender Warnung anzubringen:
Warnung
Das Gehäuse darf nur kurze Zeit geöffnet werden, z. B. für visuelle Diagnose.
Betätigen Sie dabei keine Schalter, ziehen oder stecken keine Baugruppen und
trennen keine elektrischen Leitungen (Steckverbindungen).
Diese Warnung kann unberücksichtigt bleiben, wenn bekannt ist, dass keine
explosionsgefährdete Atmosphäre herrscht.
Zone 2
Hazardous areas are divided up into zones. The zones are distinguished according
to the probability of the existence of an explosive atmosphere.
Below you will find important information on the installation of fail-safe modules in a
hazardous area.
Production Location
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Note
Modules with II 3 G EEx nA II T4 .. T5 certification can only be installed in
ET 200S distributed I/O devices belonging to equipment category 3.
Maintenance
If repair is necessary, the affected component must be sent to the production
location. Repairs can only be carried there.
Special Conditions
• The fail-safe modules must be installed in a switch cabinet or a metal housing.
These must comply with the IP54 degree of protection as a minimum. The
environmental conditions under which the equipment is installed must be taken
into account. There must be a manufacturer's declaration for zone 2 available
for the housing (in accordance with EN 50021).
• If a temperature of > 70 °C is reached in the cable or at the cable entry of this
housing under operating conditions, or if a temperature of > 80 °C can be
reached at the junction of the conductors under operating conditions, the
temperature-related properties of the cables must correspond to the
temperatures actually measured.
• The cable entries used must comply with the required IP degree of protection
and Section 7.2 (in accordance with EN 50021).
• All devices (including switches, etc.) that are connected to the inputs and
outputs of fail-safe modules must be approved for EEx nA or EEx nC explosion
protection.
• Steps must be taken to ensure that the rated voltage through transients cannot
be exceeded by more than 40 %.
• Ambient temperature range: 0 °C to 60 °C
• A sign containing the following warning must be put up inside the housing in an
easily visible position when the housing is opened:
Warning
The housing can only be opened for a short time (e.g. for visual diagnostics). If
you do this, do not operate any switches, remove or install any modules or
disconnect any electrical cables (plug-in connections).
You can disregard this warning if you know that the atmosphere is not
hazardous (i.e. there is no risk of explosion).
Zone 2
Les environnements à risque d'explosion sont répartis en zones. Les zones se
distinguent par la probabilité de présence d'une atmosphère explosive.
Vous trouverez ci-après des remarques importantes pour l'installation des modules
de sécurité dans un environnement à risque d'explosion.
Lieu de production
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Nota
Les modules homologués II 3 G EEx nA II T4 .. T5 ne peuvent être utilisés
que dans des stations de périphérie décentralisée ET 200S de catégorie 3.
Entretien
Si une réparation est nécessaire, la composante concernée doit être expédiée au
lieu de production. La réparation ne doit être effectuée qu'en ce lieu.
Conditions particulières
• Les modules à sécurité intrinsèque doivent être logés dans une armoire de
commande ou un boîtier métallique. Ceux-ci doivent assurer au moins l'indice
de protection IP54. Il faut alors tenir compte des conditions d'environnement
dans lesquelles l'appareil est installé. Le boîtier doit faire l’objet d’une
déclaration de conformité du fabricant pour la zone 2 (selon EN 50021).
• Si dans les conditions d’exploitation, une température > 70 °C est atteinte au
niveau du câble ou de l’entrée du câble dans ce boîtier, ou bien si la
température au niveau de la dérivation des conducteurs peut être > 80 °C, les
capacités de résistance thermique des câbles doivent corespondre aux
températures effectivement mesurées.
• Les entrées de câbles utilisées doivent avoir le niveau de protection IP exigé et
être conformes au paragraphe 7.2 (selon EN 50021).
• Tous les appareillages (y compris les interrupteurs, etc.) raccordés aux entrées
et sorties de modules à sécurité intrinsèque doivent être homologués pour la
protection antidéflagrante type EEx nA ou EEx nC.
• Il faut prendre des mesures pour que la tension nominale ne puisse pas être
dépassée de plus de 40% sous l’influence de transitoires.
• Plage de température ambiante : 0 °C à 60 °C
• A l’intérieur du boîtier, il faut placer, à un endroit bien visible après ouverture,
une plaquette comportant l’avertissement suivant :
Avertissement
Ouvir le boîtier le moins longtemps possible, par exemple pour effectuer un
diagnostic visuel. Ce faisant, n’actionnez aucun commutateur, ne déconnectez
aucun module et ne débanchez pas de câbles électriques (connexions).
Le respect de cet avertissement n’est pas impératif s’il est certain que
l’environnement ne présente pas de risque d’explosion.
Zona 2
Las áreas con peligro de explosión se clasifican en zonas. Las zonas se
diferencian según la probabilidad de la existencia de una atmósfera capaz de sufrir
una explosión.
Lugar de fabricación
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Nota
Los módulos con la homologación II 3 G EEx nA II T4 .. T5 pueden
utilizarse únicamente en unidades periféricas descentralizadas ET 200S de la
categoría de equipo 3.
Mantenimiento
Para una reparación se ha de remitir el componente afectado al lugar de
fabricación. Sólo allí se puede realizar la reparación.
Condiciones especiales
• Los módulos de seguridad deben ir montados en un armario de distribución o
una caja metálica. Éstos deben garantizar como mínimo el grado de protección
IP54. Para ello se han de tener en cuenta las condiciones ambientales, en las
cuales se instala el equipo. La caja deberá contar con una declaración del
fabricante para la zona 2 (conforme a EN 50021).
• Si durante la operación se alcanzara una temperatura > 70° C en el cable o la
entrada de cables de esta caja o bien una temperatura > 80° C en la
bifurcación de hilos, deberán adaptarse las propiedades térmicas de los cables
a las temperaturas medidas efectivamente.
• Las entradas de cable utilizadas deben cumplir el grado de protección IP
exigido y lo expuesto en el apartado 7.2 (conforme a EN 50021).
• Todos los dispositivos –inclusive interruptores, etc.– conectados a las entradas
y salidas de módulos de alta disponibilidad deben estar homologados para la
protección contra explosiones del tipo EEx nA o EEx nC.
• Es necesario adoptar las medidas necesarias para evitar que la tensión
nominal pueda rebasar en más del 40 % debido a efectos transitorios.
• Margen de temperatura ambiente: 0 °C hasta 60 °C
• Dentro de la caja deberá colocarse en un lugar perfectamente visible tras su
apertura un rótulo con la siguiente advertencia:
Precaución
Abrir la caja sólo brevemente, p.ej. para el diagnóstico visual. Durante este
tiempo Ud. no deberá activar ningún interruptor, desenchufar o enchufar
módulos ni separar conductores eléctricos (conexiones enchufables).
Esta advertencia puede ignorarse si Ud. sabe que en la atmósfera existente no
hay peligro de explosión.
Zona 2
Le aree a pericolo di esplosione vengono suddivise in zone. Le zone vengono
distinte secondo la probabilità della presenza di un'atmosfera esplosiva.
Qui di seguito sono riportate delle avvertenze importanti per l'installazione delle
unità ad elevata sicurezza nell'area a pericolo di esplosione.
Luogo di produzione
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Avvertenza
Le unità con l'autorizzazione II 3 G EEx nA II T4 .. T5 possono essere
impiegate solo nelle apparecchiature di periferia decentrata ET 200S della
categoria di apparecchiature 3.
Manutenzione
Per una riparazione, il componente interessato deve essere inviato al luogo di
produzione. La riparazione può essere effettuata solo lì.
Condizioni particolari
• Le unità ad elevata sicurezza devono essere montati in un armadio elettrico o in
un contenitore metallico. Questi devono assicurare almeno il tipo di protezione
IP54. In questo caso bisogna tenere conto delle condizioni ambientali nelle
quali l'apparecchiatura viene installata. Per il contenitore deve essere presente
una dichiarazione del costruttore per la zona 2 (secondo EN 50021).
• Se nei cavi o nel loro punto di ingresso in questo contenitore viene raggiunta in
condizioni di esercizio una temperatura > 70 °C o se in condizioni di esercizio la
temperatura nella derivazione dei fili può essere > 80 °C, le caratteristiche di
temperatura dei cavi devono essere conformi alla temperatura effettivamente
misurata.
• Gli ingressi dei cavi usati devono essere conformi al tipo di protezione richiesto
e alla sezione 7.2 (secondo EN 50021).
• Tutte le apparecchiature, inclusi interruttori, ecc. che vengono collegati agli
ingressi/uscite di unità ad elevata sicurezza, devono essere stati omologati per
la protezione da esplosione tipo EEx nA o EEx nC.
• Devono essere prese delle misure per evitare che la tensione nominale possa
essere superata per più del 40% da parte di transienti.
• Campo termico ambientale: da 0 °C a 60 °C
• All’interno del contenitore va apportata, in un luogo ben visibile dopo l’apertura,
una targhetta con il seguente avvertimento:
Attenzione
Il contenitore può rimanere aperto solo per breve tempo, ad esempio per una
diagnostica a vista. In tal caso non azionare alcun interruttore, non disinnestare
o innestare unità e non staccare connessioni elettriche (connettori).
Non è necessario tenere conto di questo avvertimento se è noto che non c’è
un’atmosfera a rischio di esplosione.
Zone 2
Explosieve gebieden worden ingedeeld in zones. Bij de zones wordt
onderscheiden volgens de waarschijnlijkheid van de aanwezigheid van een
explosieve atmosfeer.
Productieplaats
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Opmerking
Modulen met de vergunning II 3 G EEx nA II T4 .. T5 mogen slechts
worden gebruikt in decentrale periferieapparaten ET 200S van de
apparaatcategorie 3.
Instandhouding
De te herstellen component moet voor reparatie naar de plaats van vervaardiging
worden gestuurd. Alleen daar mag de reparatie worden uitgevoerd.
Speciale voorwaarden
• De tegen fouten beveiligde modulen moeten worden ingebouwd in een
schakelkast of in een behuizing van metaal. Deze moeten minstens de
veiligheidsgraad IP54 waarborgen. Hierbij dient rekening te worden gehouden
met de omgevingsvoorwaarden waarin het apparaat wordt geïnstalleerd. Voor
de behuizing dient een verklaring van de fabrikant voor zone 2 te worden
ingediend (volgens EN 50021).
• Als aan de kabel of aan de kabelinvoering van deze behuizing onder
bedrijfsomstandigheden een temperatuur wordt bereikt > 70 °C of als onder
bedrijfsomstandigheden de temperatuur aan de adervertakking > 80 °C kan
zijn, moeten de temperatuureigenschappen van de kabel overeenstemmen met
de werkelijk gemeten temperaturen.
• De aangebrachte kabelinvoeringen moeten de vereiste IP-veiligheidsgraad
hebben en in overeenstemming zijn met alinea 7.2 (volgens EN 50021).
• Alle apparaten, schakelaars enz. inbegrepen, die worden aangesloten op de in-
en uitgangen van tegen fouten beveiligde modulen, moeten zijn goedgekeurd
voor de explosiebeveiliging type EEx nA of EEx nC.
• Er dienen maatregelen te worden getroffen, zodat de nominale spanning door
transiënten met niet meer dan 40 % kan worden overschreden.
• Omgevingstemperatuurbereik: 0 °C tot 60 °C
• Binnen de behuizing dient op een na het openen goed zichtbare plaats een
bord te worden aangebracht met de volgende waarschuwing:
Waarschuwing
De behuizing mag slechts voor korte tijd worden geopend, bijv. voor een visuele
diagnose. Bedien hierbij geen schakelaar, trek of steek geen modulen en
ontkoppel geen elektrische leidingen (steekverbindingen).
Deze waarschuwing kan buiten beschouwing blijven, indien bekend is dat er
geen explosieve atmosfeer heerst.
Zone 2
Eksplosionsfarlige områder inddeles i zoner. Zonerne adskiller sig indbyrdes efter
hvor sandsynligt det er, at der er en eksplosiv atmosfære.
Produktionssted
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Bemærk
Moduler med godkendelsen II 3 G EEx nA II T4 .. T5 må kun monteres i
decentralt periferiudstyr ET 200S - udstyrskategori 3.
Vedligeholdelse
Skal den pågældende komponent repareres, bedes De sende den til
produktionsstedet. Reparation må kun udføres der.
Særlige betingelser
• De fejlsikre moduler skal monteres i et kontaktskab eller et metalbelagt kabinet.
Disse skal mindst kunne sikre beskyttelsesklasse IP54. I denne forbindelse skal
der tages højde for de omgivelsestemperaturer, i hvilke udstyret er installeret.
Der skal være udarbejdet en erklæring fra fabrikanten for kabinettet for zone 2
(iht. EN 50021).
• Hvis kablet eller kabelindføringen på dette hus når op på en temperatur på
> 70 °C under driftsbetingelser eller hvis temperaturen på åreforegreningen kan
være > 80 °C under driftsbetingelser, skal kablernes temperaturegenskaber
stemme overens med de temperaturer, der rent faktisk måles.
• De benyttede kabelindføringer skal være i overensstemmelse med den
krævede IP-beskyttelsestype og afsnittet 7.2 (iht. EN 50021).
• Alle apparater, inkl. kontakter osv., der forbindes med ind- og udgangene til
fejlsikre moduler, skal være godkendt til eksplosionsbeskyttelse af type EEx nA
eller EEx nC.
• Der skal træffes foranstaltninger, der sørger for, at den nominelle spænding via
transienter ikke kan overskrides mere end 40 %.
• Omgivelsestemperaturområde: 0 °C til 60 °C
• I kabinettet skal der anbringes et skilt, der skal kunne ses, når kabinettet åbnes.
Dette skilt skal have følgende advarsel:
Advarsel
Kabinettet må kun åbnes i kort tid, f.eks. til visuel diagnose. Tryk i denne
forbindelse ikke på kontakter, træk eller isæt ikke komponenter og afbryd ikke
elektriske ledninger (stikforbindelser).
Denne advarsel skal der ikke tages højde for, hvis man ved, at der ikke er
nogen eksplosionsfarlig atmosfære.
Vyöhyke 2
Räjähdysvaarannetut alueet jaetaan vyöhykkeisiin. Vyöhykkeet erotellaan
räjähdyskelpoisen ilmakehän olemassa olon todennäköisyyden mukaan.
Valmistuspaikka
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Ohje
Rakenneryhmät hyväksynnän II 3 G EEx nA II T4 .. T5 kanssa saadaan
käyttää ainoastaan laitekategorian 3 hajautetuissa ulkopiirilaitteissa ET 200S.
Kunnossapito
Korjausta varten täytyy kyseinen komponentti lähettää valmistuspaikkaan. Korjaus
voidaan suorittaa ainoastaan siellä.
Erityiset vaatimukset
• Virhevarmat moduulit täytyy asentaa kytkentäkaappiin tai metalliseen koteloon..
Näiden täytyy olla vähintään kotelointiluokan IP54 mukaisia. Tällöin on
huomioitava ympäristöolosuhteet, johon laite asennetaan. Kotelolle täytyy olla
valmistajaselvitys vyöhykettä 2 varten (EN 50021 mukaan).
• Kun johdolla tai tämän kotelon johdon sisäänviennillä saavutetaan > 70 °C
lämpötila tai kun käyttöolosuhteissa lämpötila voi piuhajaotuksella olla > 80 °C,
täytyy johdon lämpötilaominaisuuksien vastata todellisesti mitattuja lämpötiloja.
• Käytettyjen johtojen sisäänohjauksien täytyy olla vaaditun IP-kotelointiluokan ja
kohdan 7.2 (EN 50021 mukaan) mukaisia.
• Kaikkien laitteiden, kytkimet jne. mukaan lukien, jotka liitetään virheiltä
suojattujen rakenneryhmien tuloille ja lähdöille, täytyy olla hyväksyttyjä tyypin
EEx nA tai EEx nC räjähdyssuojausta varten.
• Toimenpiteet täytyy suorittaa, ettei nimellisjännite voi transienttien kautta ylittyä
enemmän kuin 40 %.
• Ympäristölämpötila-alue: 0 °C ... 60 °C
• Kotelon sisälle, avauksen jälkeen näkyvälle paikalle, on kiinnitettävä kilpi, jossa
on seuraava varoitus:
Varoitus
Kotelo saadaan avata ainoastaan lyhyeksi ajaksi, esim. visuaalista diagnoosia
varten. Älä tällöin käytä mitään kytkimiä, vedä tai liitä mitään rakenneryhmiä,
äläkä erota mitään sähköjohtoja (pistoliittimiä).
Tätä varoitusta ei tarvitse huomioida, kun on tiedossa, että minkäänlaista
räjähdysvaarannettua ilmakehää ei ole olemassa.
Zon 2
Explosionsriskområden delas in i zoner. Zonerna delas in enligt sannolikheten att
en atmosfär med explosionsfara föreligger.
Tillverkningsort
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Anvisning
Komponentgrupper med godkännande II 3 G EEx nA II T4 .. T5 får endast
användas i decentrala periferienheter ET°200S från apparatgrupp°3.
Underhåll
Vid reparation måste den aktuella komponenten insändas till tillverkaren.
Reparationer får endast genomföras där.
Särskilda villkor
• De felsäkrade modulerna måste monteras i ett kopplingsskåp eller metallhus.
Dessa måste minst vara av skyddsklass IP54. Därvid ska omgivningsvillkoren
där enheten installeras beaktas. För kåpan måste en tillverkardeklaration för
zon 2 föreligga (enligt EN 50021).
• Om en temperatur på > 70°C uppnås vid husets kabel resp kabelinföring under
driftvillkor eller om temperaturen vid trådförgreningen kan vara > 80°C under
driftvillkor, måste kabelns temperaturegenskaper överensstämma med den
verkligen uppmätta temperaturen.
• De använda kabelinföringarna måste uppfylla kraven i det krävda IP-
skyddsutförandet och i avsnitt 7.2 (enligt EN 50021).
• Alla apparater, inklusive brytare osv, som ansluts till felsäkrade modulers in-
och utgångar, måste vara godkända för explosionsskydd av typ EEx nA eller
EEx nC.
• Åtgärder måste vidtas så, att märkspänningen ej kan överskridas med mer än
40°% genom transienter.
• Omgivningstemperatur: 0 °C till 60 °C
• När huset öppnats ska en skylt med följande varning monteras på ett tydligt
synligt ställe huset:
Varning
Huset får endast öppnas under kort tid, t ex för visuell diagnos. Använd därvid
inga brytare, lossa eller anslut inga enheter och frånskilj inga elektriska
ledningar (insticksanslutningar).
Ingen hänsyn måste tas till denna varning om det är säkert att det inte råder
någon explosionsfarlig atmosfär.
Zona 2
As áreas expostas ao perigo de explosão são divididas em zonas. As zonas são
diferenciadas de acordo com a probabilidade da existência de uma atmosfera
explosiva.
Local de produção
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Aviso
Componentes com a licença II 3 G EEx nA II T4 .. T5 só podem ser
aplicados em aparelhos periféricos descentralizados ET 200S da categoria de
aparelho 3.
Reparo
Os componentes em questão devem ser remetidos para o local de produção a fim
de que seja realizado o reparo. Apenas lá deve ser efetuado o reparo.
Condições especiais
• Os módulos sem defeito devem ser montados dentro de um armário do quadro
de comandos ou de uma caixa metálica. Estes devem garantir no mínimo o tipo
de proteção IP54. Durante este trabalho deverão ser levados em consideração
as condições locais, nas quais o aparelho será instalado. Para a caixa deverá
ser apresentada uma declaração do fabricante para a zona 2 (de acordo com
EN 50021).
• Caso no cabo ou na entrada do cabo desta carcaça sob as condições
operacionais seja atingida uma temperatura de > 70 °C, ou caso sob condições
operacionais a temperatura na ramificação do fio poderá atingir > 80 °C, as
caraterísticas de temperatura deverão corresponder às temperaturas realmente
medidas.
• As entradas de cabo utilizadas devem corresponder ao tipo exigido de
proteção IP e à seção 7.2 (de acordo com o EN 50021).
• Todos os aparelhos, inclusive as chaves, etc., que estejam conectadas em
entradas e saídas de módulos protegidos contra erro, devem possuir a licença
para a proteção de explosão do tipo EEx nA ou EEx nC.
• Precisam ser tomadas medidas para que a tensão nominal através de
transitórios não possa ser ultrapassada em mais que 40 %.
• Área de temperatura ambiente: 0 °C até 60 °C
• No âmbito da carcaça deve ser colocada, após a abertura, em um ponto bem
visível uma placa com a seguinte advertência:
Advertência
A carcaça deve ser aberta apenas por um breve período de tempo, por ex. para
diagnóstico visual. Não acione nenhum interruptor, não retire ou conecte
nenhum módulo e não separe nenhum fio elétrico (ligações de tomada).
Esta advertência poderá ser ignorada caso se saiba que não há nenhuma
atmosfera sujeita ao perigo de explosão.
Ζώνη 2
Οι επικίνδυνες για έκρηξη περιοχές χωρίζονται σε ζώνες. Οι ζώνες διαφέρουν
σύµφωνα µε την πιθανότητα ύπαρξης ενός ικανού για έκρηξη περιβάλλοντος.
Στη συνέχεια θα βρείτε σηµαντικές υποδείξεις για την εγκατάσταση των ασφαλών
σε περίπτωση βλάβης δοµικών συγκροτηµάτων σηµάτων σε επικίνδυνη για έκρηξη
περιοχή.
Τόπος κατασκευής
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Υπόδειξη
Τα δοµικά συγκροτήµατα µε την άδεια II 3 G EEx nA II T4 .. T5 επιτρέπεται
να τοποθετηθούν µόνο στην αποκεντρωµένη περιφερειακή συσκευή ET 200S της
κατηγορίας συσκευής 3.
Συντήρηση
Για µια επισκευή πρέπει να σταλθεί το αντίστοιχο εξάρτηµα στον τόπο κατασκευής.
Μόνο εκεί επιτρέπεται να γίνει η επισκευή.
Ιδιαίτερες προϋποθέσεις
• Τα ασφαλή σε περίπτωση βλάβης δοµικά συγκροτήµατα σηµάτων/
δοµοστοιχεία πρέπει να ενσωµατωθούν σε ένα ερµάριο ζεύξης ή σε ένα
µεταλλικό περίβληµα. Αυτά πρέπει να εξασφαλίζουν το λιγότερο το βαθµό
προστασίας IP54. Σε αυτήν την περίπτωση πρέπει να ληφθούν υπόψη οι
περιβαλλοντικές συνθήκες, στις οποίες θα εγκατασταθεί η συσκευή. Για το
περίβληµα πρέπει να προβλέπεται δήλωση του κατασκευαστή για τη ζώνη 2
(σύµφωνα µε το πρότυπο EN 50021).
• Εάν στο καλώδιο ή στην είσοδο του καλωδίου αυτού του περιβλήµατος κάτω
από συνθήκες λειτουργίας η θερµοκρασία ξεπεράσει τους 70 °C ή όταν κάτω
από συνθήκες λειτουργίας η θερµοκρασία στη διακλάδωση του σύρµατος
µπορεί να είναι µεγαλύτερη από 80 °C, πρέπει οι θερµοκρασιακές ιδιότητες των
καλωδίων να ταυτίζονται µε τις πραγµατικά µετρηµένες θερµοκρασίες.
• Οι χρησιµοποιούµενες εισόδοι καλωδίων πρέπει να συµµορφώνονται µε το
βαθµό προστασίας IP 54 στην ενότητα 7.2 (σύµφωνα µε το πρότυπο
EN 50021).
• Όλες οι συσκευές, συµπεριλαµβανοµένων διακοπτών κ.α., που συνδέονται στις
εισόδους και εξόδους δοµικών συγκροτηµάτων ασφαλών σηµάτων, πρέπει να
φέρουν εγκριµένη προστασία κατά έκρηξης τύπου EEx nA ή EEx nC.
• Πρέπει να ληφθούν µέτρα, να µην µπορεί να γίνει υπέρβαση της ονοµαστικής
τάσης µέσω αιφνίδιας µεταβολής της τάσης πάνω από 40 %.
• Περιοχή θερµοκρασίας περιβάλλοντος: 0 °C έως 60 °C
• Πρέπει να τοποθετηθεί µέσα στο περίβληµα σε ευδιάκριτο σηµείο µετά το
άνοιγµα µία πινακίδα µε την ακόλουθη προειδοποίηση:
Προειδοποίηση
Το περίβληµα επιτρέπεται να ανοίγει µόνο για µικρό χρονικό διάστηµα, π.χ. για
τη διενέργεια οπτικής διάγνωσης. Μην κάνετε χρήση διακοπτών, µην τραβάτε ή
εµβυσµατώνετε δοµικά συγκροτήµατα και µη διαχωρίζετε ηλεκτροφόρους
αγωγούς (εµβσυµατώσιµες συνδέσεις).
Η προειδοποίηση αυτή δε χρειάζεται να ληφθεί υπ’ όψιν, εάν είναι γνωστό ότι
δεν υφίσταται ατµόσφαιρα παρουσιάζουσα κίνδυνο έκρηξης.
9.1 Introduction
Overview
Fail-safe power modules and fail-safe digital modules are available for connecting
digital sensors or encoders and actuators or loads to ET 200S. This chapter
provides the following information for each fail-safe module:
• Properties and special features
• Front view, terminal assignment for terminal modules, and block diagram
• Wiring diagram and programmable parameters
• Diagnostic functions, including corrective measures
• Technical specifications
Warning
! The safety characteristics in the Technical Specifications apply for a proof-test
interval of 10 years and a repair time of 100 hours.
Order Number
6ES7 138-4CF01-0AB0
Properties
The PM-E F pm DC 24V PROFIsafe power module has the following properties:
• Two relays for connecting voltage buses P1 and P2, 10 A output current
• Two fail-safe digital outputs, P/M switching (current sourcing/sinking), 2 A
output current
• 24 VDC rated load voltage
• Suitable for solenoid valves, DC contactors, and indicator lamps
• Group fault display (SF; red LED)
• Status display for each output (green LED)
• Status display for load current power supply (PWR; green LED)
• Selectable diagnostics
• For achievable safety classes (safety integrity level), see following table
Table 9-1 Overview of Achievable Safety Classes (Safety Integrity Levels) with
PM-E F pm DC 24V PROFIsafe
Condition Achievable
AK/SIL/Category
ET 200S standard modules supplied by means of P1 and P2 AK4/SIL2/Category .3 on P1
and P2 and on DO 0 and
DO 1
DO 0 and DO 1 used, modules not supplied by means of P1 AK6/SIL3/Category 4 on DO
and P2 0 and DO 1
Warning
! Always connect the 24 VDC supply for the standard ET 200S modules on the
PM-E F pm DC 24V PROFIsafe. Otherwise, the outputs of DO modules may
exhibit safety-critical behavior.
Warning
! When supplying standard DO modules, always use the terminal modules to
supply the sensors or actuators (actuator feedback on the DO module).
Otherwise, the power module signals a short circuit and the load voltage of this
voltage group is interrupted.
Warning
! The digital electronic module 4DO DC 24V/0,5A (order no. 6ES7 132-4BD00-
0AA0) is the only standard ET 200S module released for safety-related shutdown
according to SIL2.
Warning
! Fail-safe activation of outputs of standard DO modules is not possible, but only
fail-safe deactivation . You must therefore take the following effects into account:
In the worst case situation, you must expect every possible fault/error that can
occur with the standard DO modules and the program controlling them for which
there is no direct error detection. For example, the PM-E F pm DC 24V
PROFIsafe power module does not detect external short circuits after L+ on the
outputs of standard DO modules.
All errors of the standard DO modules influence the process via final control
elements. The process must be made known to the F-CPU via sensors and a
suitable safety program.
The safety program must react in a safety-related and logically suitable fashion to
unwanted or potentially dangerous states in the process via the PM-E F pm DC
24V PROFIsafe and fail-safe output modules.
If you want to avoid the problems described above completely, we recommend that
you use P/M switching fail-safe electronic modules 4 F-DO DC 24V/2A PROFIsafe
with standard ET 200S power modules (see Section 9.6 and Table 3-3) instead of
standard DO modules.
Remedy:
• Use the PM-E F pp DC 24V PROFIsafe
• The value of the resistance between chassis and ground at the load end must
be greater than 100 kΩ
Output -
P2
Output
M driver
Central
Groun-
ding
M P1
Loa
M M-switch 1P5
Readback M bus
Figure 9-1 Connecting Non-Floating Loads (resistance exists between chassis and ground)
Cause
During the sensor supply tests of the 4/8 F-DI DC 24V PROFIsafe module, the
steep switching edge of the output driver can cause crosstalk with other inactive
output channels due to the coupling capacitance of the wire, for example on the
PM E F pm DC 24V PROFIsafe power module. In these channels, this can lead to
a response in the readback circuit. A short is detected leading to a safety-related
shutdown.
Remedy
• Use separate cables for F-DI modules and F-DO modules or standard DO
modules driven by a PM-E F pm DC 24V PROFIsafe
• Coupling relay or diodes in the outputs
• Turn off the sensor supply test if this is permitted by the required safety class
(safety integrity level).
Incoming Supply of the 24 VDC Supply for Electronic Modules with Process-
Related Functions
Depending on whether the electronic and load current supplies are electrically
isolated in the electronic modules with process-related functions (positioning,
counting), you must adhere to the following wiring instructions:
• If electrically isolated, provide an external 24 VDC feed for the electronic
module.
• If electrical isolation is not implemented, you must supply the electronic module
from the voltage bus P1 of the PM-E F pm DC 24V PROFIsafe power module.
AK4/SIL2/Category 3 is attainable in both cases.
Front View
PM-E F pm DC24V
Group error display - red
Warning
! The SF LED and the status displays of the outputs must not be evaluated for fail-
safe activities.
Terminal Assignment
The terminal assignment of the PM-E F pm DC 24V PROFIsafe power module for
the usable terminal modules TM-P30S44-A0 and TM-P30C44-A0 is shown in the
following figure and table.
AUX1
DO0 DO1
A A 9 13 P P
4 8
M M DO2 DO2
(supply) P P
3 7 11 15
A A DO2 DO2
AUX1 AUX1
4 8 12 16 M M
(supply)
Figure 9-3 Terminal Assignment of the TM-P30S44-A0 or TM-P30C44-A0 for PM-E F pm DC 24V
PROFIsafe
Terminal Designation
2 24 VDC 24 VDC rated load voltage for:
• Inserted power module,
• Corresponding voltage group,
• DO 0 and DO 1 and
• Voltage buses P1 and P2
3 M Ground
A AUX 1 Any terminal for PE or voltage bus up to the maximum rated load
4 voltage of the module
6 24 VDC 24 VDC rated load voltage for:
• Inserted power module,
• Corresponding voltage group,
• DO 0 and DO 1
• and voltage buses P1 and P2
7 M Ground
A AUX 1 Any terminal for PE or voltage bus up to the maximum rated load
8 voltage of the module
9 DO 0 P Terminals for fail-safe digital output 0 (P/M switching)
10 DO 0 M
11 DO 2 P Terminals (relay contacts) for fail-safe connection of voltage buses P1
12 DO 2 M and P2
P1 and P2 can also be used as DO 2 M and DO 2 P
13 DO 1 P Terminals for fail-safe digital output 1 (P/M switching)
14 DO 1 M
15 DO 2 P Terminals (relay contacts) for fail-safe connection of voltage buses P1
16 DO 2 M and P2
P1 and P2 can also be used as DO 2 M and DO 2 P
Caution
! If high currents can occur on DO 2 P and DO 2 M, both terminals 11 and 15
(DO 2 P) and terminals 12 and 16 (DO 2 M) must be wired in parallel.
Otherwise, the current loading could cause the terminals to heat up.
Block Diagram
Address switch
PWR P-switch
M 9
Processing logic
13
Readback
Backplane bus interface
10
SF
M
M-switch
14
M
Status of
the
Relay 5V output
12,16 M24
24
3,7
P1
P2
11,15 P24
2,6
Wiring Diagram
The three digital outputs each consist of one P-switch (current sourcing) DOx P
and one M-switch (current sinking) DOx M. They connect the load between the P
and M-switches. Both switches are always set so that voltage is applied to the load.
The power module is wired on the special terminal module.
P1 (M)
P1 P2
DO0 DO0 DO1 DO1 (M) (P) P2 (P)
L+ M (P) (M) (P) (M) DO2 DO2 DO3 M DO4 M DO5 M
K0 K1 K2 K3 K4 K5
L+ M
Warning
! To protect the relay contacts from overload, please use an external circuit
breaker for L+ on the PM-E F pm with the following properties: Circuit breaker
with characteristic B according to IEC 947-5-1, 10 A.
Relay Output DO 2
The relay output DO 2 connects the voltage L+ and M using one relay contact for
each. The voltage is fed outwards to the terminal module and to the internal
voltage buses P1 and P2. This results in two connection options that can be used
at the same time:
• A load can be connected directly to the terminal module (K2 in Figure 9-5).
• Electronic modules can be supplied by means of the internal voltage buses P1
and P2. In turn, loads can be connected to these modules (K3, K4, K5 in
Figure 9-5).
P1 (M)
P1 P2
DO0 DO0 DO1 DO1 (M) (P) P2 (P)
L+ M (P) (M) (P) (M) DO2 DO2 DO3 M DO4 M DO5 M
K1 K2 K3 K4
K1 K3
K2 K4
M M
L+ M
Figure 9-6 Wiring Diagram for Each of Two Relays on DO 0 and DO 1 of the PM-E F pm DC 24V
PROFIsafe
Warning
! When connecting two relays on one digital output, (as shown in the figure above),
the errors "wire break“ and "overload“ are detected only at the P-switch (not at
the M-switch).
The controlled actuator can no longer be switched off when there is a cross circuit
between the P and M-switches of the output.
Warning
! To avoid cross circuits between P and M-switches of a fail-safe digital output, you
should connect the relay on the between P and M-switches to protect against
cross circuits (for example with cables separately sheathed or in a separate cable
duct).
P1 (M)
P1 P2
DO0 DO0 DO1 DO1 (M) (P) P2 (P)
L+ M (P) (M) (P) (M) DO2 DO2 DO3 M DO4 M DO5 M
K1 K3
K1 K3
K2 K4
K2 K4
M M
L+ M
Figure 9-7 Wiring Diagram for Each of Two Relays on DO 0 and DO 1 of the PM-E F pm DC 24V
PROFIsafe
Note
If two relays are connected in parallel to one digital output (as shown in the figure
above), "wire break“ is detected only if the wire break disconnects both relays
from P or M. This diagnostics is not relevant to safety.
Parameters in STEP 7
The following table presents the parameters that can be assigned for the
PM-E F pm DC 24V PROFIsafe power module (see also Chapter 4).
Readback Time
Each output channel has its own selectable readback time. This time specifies the
maximum duration of the turn off test for the corresponding channel and therefore
also the readback time for turning off the channel.
You can set the following readback times: 1 ms, 5 ms, 10 ms, 50 ms, 100 ms,
200 ms and 400 ms.
You should set an adequately high readback time if the channel involved switches
high capacitive loads. If the readback time for a controlled capacitive load is set too
low, the output channel is passivated because the discharge of the capacitance
does not take place within the turn off test.
If the readback signals are incorrect, the "short circuit" error causes the passivation
of the output channel after the readback time elapses.
10.000,0
1.000,0
Capacitive load in µF
100,0
10,0
1,0
0,1
9 20 50 100 200 500 750 1000 1250 1500 1750 2000
Load current in m A
Figure 9-8 Relationship between Load Resistance and Connectable Load Capacitance for
PM-E F pm DC 24V PROFIsafe
Remedy:
1. Determine the load current and capacitance of the load.
2. Determine the operating point in the figure above.
3. If the operating point is above the curve, you must increase the load current
until the new operating point is below the curve by connecting a resistor in
parallel.
Diagnostic Functions
The following table presents an overview of the diagnostic functions of the
PM-E F pm DC 24V PROFIsafe power module. The diagnostic functions are
assigned either to one channel or the entire module.
Table 9-6 Causes of Errors and Corrective Measures for Diagnostic Messages of the
PM-E F pm DC 24V PROFIsafe
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 81 x 52
Weight Approx. 88 g
Module-Specific Data
Number of outputs
• Semiconductor outputs (P/M switching) 2
• Relay outputs (P-M switching) 1
Assigned address area
• In the I/O area for inputs 5 bytes
• In the I/O area for outputs 5 bytes
Length of cable
• Unshielded 200 m, maximum
• Shielded 200 m, maximum
Maximum achievable safety class
• Complying with IEC 1508, DIN VDE max. SIL3, AK6, Category 4: Contrains see
0801 and EN 954 Chapter 4
Fail-safe performance characteristics SIL3
• Low demand mode (average probability << 1.00 E-05
of failure on demand)
• High demand/continuous mode << 1.00 E-10
(probability of a dangerous failure per
hour)
Voltages, Currents, Potentials
Rated supply voltage L+ 24 VDC
• Permissible range 20.4 V to 28.8 V
• Power loss ride-through of L+ None
• Power loss ride-through of internal P5 5 ms
• Reverse polarity protection No
Technical Specifications
Aggregate current
• Horizontal installation
- Up to 40°C 10 A
- Up to 55°C 7A
- Up to 60°C 6A
• Vertical installation
- Up to 40°C 6A
Electrical isolation
• Between channels and backplane bus Yes
• Between channels and power supply No
• Between channels No
• Between channels/power supply and Yes
shield
Permissible potential difference between
• Shield and ET 200S bus connection 75 VDC/60 VAC
• Shield and I/O (DOs, P1/P2 buses) 75 VDC/60 VAC
• ET 200S bus connection and I/O (DOs, 250 VAC
P1/P2 buses)
Isolation in the series tested with
• Shield and ET 200S bus connection 500 VDC/1 min or 600 VDC/1 s
• Shield and I/O (DOs, P1/P2 buses) 500 VDC/1 min or 600 VDC/1 s
• ET 200S bus connection and I/O (DOs, 1500 VAC/1 min or 2545 VDC/1 s
P1/P2 buses)
Isolation in the type test tested with
• Shield and ET 200S bus connection 350 VAC/1 min
• Shield and I/O (DOs, P1/P2 buses) 350 VAC/1 min
• ET 200S bus connection and I/O (DOs, 2830 VAC/1 min
P1/P2 buses)
• Impulse current test between ET 200S 6000 VDC/5 positive and 5 negative pulses
bus connection and I/O (DOs, P1/P2
buses)
Current consumption
• From backplane bus 28 mA, maximum
• From load voltage L+ (without load) 100 mA, typical
Power dissipation of the module 4 W, typical
Status, Interrupts, Diagnostics
Status display • Green LED per channel
• Green LED for the load voltage
Diagnostic functions
• Group error display Red LED (SF)
• Diagnostic information can be displayed Possible
Technical Specifications
Data for Selecting an Actuator for the Semiconductor Outputs*
Output voltage
• For "1“ signal • Minimum L+ (-2.0 V)
• P-switch: min. L+ (-1,5 V), voltage drop
at M-switch:
max. 0.5 V
Output current for "1“ signal
• Rated value 2A
• Permissible range 20 mA to 2.4 A
For "0“ signal (residual current) 0.5 mA, maximum
Indirect control of load by means of interface
relay:
Residual current for "0“ signal
• P-switch 0.5 mA, maximum
• M-switch 4 mA, maximum
Load resistance range 12 Ω to 1 kΩ
Lamp load 10 W, maximum
Wire break monitoring (open load detection)
and overload monitoring
• Response threshold I < 4 to 19 mA
• Fault detection time Depending on the selected readback time
(see Chapter 13)
Parallel connection of 2 outputs Not possible
Control of a digital input Not possible
Switching frequency
• With resistive load 30 Hz, maximum
• With inductive load in accordance with 0.1 Hz, maximum
IEC 947-5-1, DC13
• With lamp load 10 Hz, maximum
Voltage induced on current interruption
limited to
• Semiconductor outputs L+ (-2x 47 V)
• Relay outputs P1/P2 (1 V)
Short-circuit protection of semiconductor Yes, electronic
outputs
• Response threshold of short circuit 5 A to 12 A
• Response threshold ext. M short circuit 5 A to 12 A
• Response threshold ext. P short circuit 25 A to 45 A
Overload protection of semiconductor Yes
outputs
• Response threshold I >2.6 A to 2.8 A
Technical Specifications
Data for Selecting an Actuator for the Relay Outputs*
Switching capacity and service life of the
contacts (at 24 VDC)
• Mechanical endurance (without load) Current No. of switching cycles
(typical)
0A 10 million
• For resistive load Current No. of switching cycles
(typical)
10 A 0.23 million
8A 0.3 million
6A 0.38 million
4A 0.5 million
2A 1.0 million
1A 2.0 million
• For inductive load in accordance with Current No. of switching cycles
IEC 947-5-1, DC13 (typical)
10 A 0.1 million
8A 0.15 million
6A 0.2 million
4A 0.3 million
2A 0.5 million
1A 1.0 million
• For lamp load Power No. of switching cycles
(typical)
100 W 0.12 million
Contact protection (internal) Internal readback circuit
• Between P and M relay output 39 V suppressor diode
Wire break monitoring No
Parallel connection of 2 outputs Not possible
Control of a digital input Not possible
Switching frequency
•
• With resistive load 2 Hz, maximum
• With inductive load in accordance with 0.1 Hz, maximum
IEC 947-5-1, DC13
• With lamp load 2 Hz, maximum
Short-circuit protection of output No, external miniature circuit breaker, "B"
characteristic (in accordance with
IEC 947-5-1), 10 A required
Time, Frequency
Internal preparation times See Chapter 13
Acknowledgment time in safety mode 4 ms minimum/8 ms maximum
Technical Specifications
Protection against Overvoltage
Protection of supply voltage L+ from surge
in accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
Protection of outputs from surge in
accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (DO to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 1 kV; 1.2/50 µs
(DO to PE, M to PE)
* For requirements for sensors and actuators, refer to Section 6.5
Order Number
6ES7 138-4CF40-0AB0
Properties
The PM-E F pp DC 24V PROFIsafe power module has the following properties:
• Two relays for connecting voltage bus P2, 10 A output current
• Relay contacts must be fused externally
• 24 VDC rated load voltage
• Suitable for solenoid valves, DC contactors, and indicator lamps
• Suitable for applications for which a grounded configuration is necessary or in
which a floating configuration cannot be guaranteed
• Group fault display (SF; red LED)
• Status display for voltage bus P2 (green LED)
• Status display for load current power supply (PWR; green LED)
• Selectable diagnostics
• For achievable safety classes (safety integrity level), see following table
Table 9-7 Overview of Achievable Safety Classes (Safety Integrity Levels) with the
PM-E F pp DC 24V PROFIsafe
Condition Achievable
AK/SIL/Category
ET 200S standard modules supplied by means of P2 AK4/SIL2/Category 3 on
P2
The relays are switched at least once in the second error entry AK6/SIL3/Category 4 on
time; no supply of ET 200S standard modules via P2 P2
Warning
! Always connect the 24 VDC supply for the standard ET 200S modules on the
PM-E F pp DC 24V PROFIsafe. Otherwise, the outputs of DO modules may
exhibit safety-critical behavior.
Warning
! When supplying standard DO modules, always use the terminal modules to
supply the sensors or actuators (actuator feedback on the DO module).
Otherwise, the power module signals a short circuit and the load voltage of this
voltage group is interrupted.
Warning
! For the PM-E F pp DC 24V PROFIsafe, the chassis cable to the terminal module
must be installed twice for safety reasons.
Otherwise if there was an interruption on a single chassis cable, a safety-related
shutdown of voltage bus P2 would not be possible.
Warning
! The digital electronic module 4DO DC 24V/0.5A (order no.
6ES7 132-4BD00-0AA0) is the only standard ET 200S module released for safety-
related shutdown according to SIL2.
Warning
! Fail-safe activation of outputs of standard DO modules is not possible, but only
fail-safe deactivation. You must therefore take the following effects into account:
In the worst case situation, you must expect every possible fault/error that can
occur with the standard DO modules and the program controlling them for which
there is no direct error detection. For example, the PM-E F pp DC 24V PROFIsafe
power module does not detect external short circuits after L+ on the outputs of
standard DO modules.
All errors of the standard DO modules influence the process via final control
elements. The process must be made known to the F-CPU via sensors and a
suitable safety program.
The safety program must react in a safety-related and logically suitable fashion to
unwanted or potentially dangerous states in the process via the
PM-E F pp DC 24V PROFIsafe and fail-safe output modules.
If you want to avoid the problems described above completely, we recommend that
you use P/M switching fail-safe electronic modules 4 F-DO DC 24V/2A PROFIsafe
with standard ET 200S power modules (see Section 9.6 and Table 3-3) instead of
standard DO modules.
Incoming Supply of the 24 VDC Supply for Electronic Modules with Process-
Related Functions
Depending on whether the electronic and load current supplies are electrically
isolated in the electronic modules with process-related functions (positioning,
counting), you must adhere to the following wiring instructions:
• If electrically isolated, provide an external 24 VDC feed for the electronic
module.
• If electrical isolation is not implemented, you must supply the electronic module
from the voltage bus P2 of the PM-E F pp DC 24V PROFIsafe power module.
AK4/SIL2/Category 3 is attainable in both cases.
Front View
PM-E F pp DC24V
Group error display - red
Warning
! The SF LED and the status displays of the outputs must not be evaluated for fail-
safe activities.
Terminal Assignment
The terminal assignment of the PM-E F pp DC 24V PROFIsafe power module for
the usable terminal modules TM-P30S44-A0 and TM-P30C44-A0 is shown in the
following figure and table.
AUX1
A A 9 13
4 8
DC24V DC24V
(supply) 2 6 10 14
M M
(supply) 3 7 11 15 P P
A A
AUX1 AUX1
4 8 12 16 M M
(supply)
Figure 9-10 Terminal Assignment of the TM-P30S44-A0 or TM-P30C44-A0 for PM-E F pp DC 24V
PROFIsafe
Terminal Designation
2 24 VDC 24 VDC rated load voltage for:
• Inserted power module,
• Corresponding voltage group and
• Voltage bus P2
3 M Ground
A AUX 1 Any terminal for PE or voltage bus up to the maximum rated load
4 voltage of the module
6 24 VDC 24 VDC rated load voltage for:
• Inserted power module,
• Corresponding voltage group and
• Voltage bus P2
7 M Ground
A AUX 1 Any terminal for PE or voltage bus up to the maximum rated load
8 voltage of the module
11 P Terminals (relay contacts) for fail-safe connection of voltage bus P2
12 M
15 P Terminals (relay contacts) for fail-safe connection of voltage bus P2
16 M
Caution
! If high currents can occur on DO 2 P and DO 2 M, both terminals 11 and 15 (P)
and terminals 12 and 16 (M) must be wired in parallel.
Otherwise, the current loading could cause the terminals to heat up.
Block Diagram
Address switch
PWR
Processing logic
Backplane bus interface
SF
M
Readback M
Status of the
Output 0
5V
12,16 M24
24 3,7
P1
P2
11,15 P24
Relay 2 Relay 1 2,6
Wiring Diagram
The power module is wired on the special terminal module.
P1 (M)
P2 P1
(P) (M) P2 (P)
L+ M DO3 M DO4 M DO5 M
K1 K2 K3 K4
L+ M
Warning
! To protect the relay contacts from overload, please use an external circuit
breaker for L+ on the PM-E F pp with the following properties: Circuit breaker with
characteristic B according to IEC 947-5-1, 10 A.
Relay output
The relay output connects the L+ voltage over two relay contacts. The connected
voltage is fed outwards to the terminal module and to the internal voltage buses P1
and P2. This results in two connection options that can be used at the same time:
• A load can be connected directly to the terminal module (K1 in Figure 9-12).
• Electronic modules can be supplied by means of the internal voltage buses P1
and P2. In turn, loads can be connected to these modules (K2, K3, K4 in
Figure 9-12).
Parameters in STEP 7
The following table lists the parameters that can be assigned for the PM-E F pp DC
24V PROFIsafe power module (see also Chapter 4).
Diagnostic Functions
The following table presents an overview of the diagnostic functions of the
PM-E F pp DC 24V PROFIsafe power module. The diagnostic functions are
assigned either to one channel or the entire module.
Table 9-12 Causes of Errors and Corrective Measures for Diagnostic Messages of the
PM-E F pp DC 24V PROFIsafe
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 81 x 52
Weight Approx. 80 g
Module-Specific Data
Number of outputs
• Relay outputs (PP switching) 1
Assigned address area
• In the I/O area for inputs 5 bytes
• In the I/O area for outputs 5 bytes
Length of cable
• Unshielded 200 m, maximum
• Shielded 200 m, maximum
Technical Specifications
Maximum achievable safety class
• Complying with IEC 1508, DIN VDE max. SIL3, AK6, Category 4: Constraints
0801 and EN 954 see Chapter 9.3
Fail-safe performance characteristics SIL3
• Low demand mode (average probability << 1.00 E-05
of failure on demand)
• High demand/continuous mode << 1.00 E-10
(probability of a dangerous failure per
hour)
Voltages, Currents, Potentials
Rated supply voltage L+ 24 VDC
• Permissible range 20.4 V to 28.8 V
• Power loss ride-through of L+ None
• Power loss ride-through of internal P5 5 ms
• Reverse polarity protection No
Total current of the relay output
• Horizontal installation
- Up to 40°C 10 A
- Up to 55°C 8A
- Up to 60°C 7A
• Vertical installation
- Up to 40°C 8A
Electrical isolation
• Between output and backplane bus Yes
• Between output and power supply No
• Between output/power supply and Yes
shield
Permissible potential difference between
• Shield and ET 200S bus connection 75 VDC/60 VAC
• Shield and I/O (DOs, P1/P2 buses) 75 VDC/60 VAC
• ET 200S bus connection and I/O (DOs, 250 VAC
P1/P2 buses)
Technical Specifications
Isolation in the series tested with
• Shield and ET 200S bus connection 500 VDC/1 min or 600 VDC/1 s
• Shield and I/O (DOs, P1/P2 buses) 500 VDC/1 min or 600 VDC/1 s
• ET 200S bus connection and I/O (DOs, 1500 VAC/1 min or 2545 VDC/1 s
P1/P2 buses)
Isolation in the type test tested with
• Shield and ET 200S bus connection 350 VAC/1 min
• Shield and I/O (DOs, P1/P2 buses) 350 VAC/1 min
• ET 200S bus connection and I/O (DOs, 2830 VAC/1 min
P1/P2 buses)
• Impulse current test between ET 200S 6000 VDC/5 positive and 5 negative pulses
bus connection and I/O (DOs, P1/P2
buses)
Current consumption
• From backplane bus 28 mA, maximum
• From load voltage L+ (without load) 100 mA, typical
Power dissipation of the module 4 W, typical
Status, Interrupts, Diagnostics
Status display • Green LED per channel
• Green LED for the load voltage
Diagnostic functions
• Group error display Red LED (SF)
• Diagnostic information can be displayed Possible
Data for Selecting an Actuator for the Relay Output*
Switching capacity and service life of the
contacts (at 24 VDC)
• Mechanical endurance (without load) Current No. of switching cycles
(typical)
0A 10 million
• For resistive load Current No. of switching cycles
(typical)
10 A 0.23 million
8A 0.3 million
6A 0.38 million
4A 0.5 million
2A 1.0 million
1A 2.0 million
Technical Specifications
• For inductive load in accordance with Current No. of switching cycles
IEC 947-5-1, DC13 (typical)
10 A 0.1 million
8A 0.15 million
6A 0.2 million
4A 0.3 million
2A 0.5 million
1A 1.0 million
• For lamp load Power No. of switching cycles
(typical)
100 W 0.12 million
Contact protection (internal) Internal readback circuit
• Between PP relay output and M 39 V suppressor diode
Wire break monitoring No
Parallel connection of 2 outputs Not possible
Control of a digital input Possible
Switching frequency
• With resistive load 2 Hz, maximum
• With inductive load in accordance with 0.1 Hz, maximum
IEC 947-5-1, DC13
• With lamp load 2 Hz, maximum
Short-circuit protection of output No, external miniature circuit breaker, "B"
characteristic (in accordance with
IEC 947-5-1), 10 A required
Time, Frequency
Internal preparation times See Chapter 13
Acknowledgment time in safety mode 4 ms minimum/8 ms maximum
Protection against Overvoltage
Protection of supply voltage L+ from surge
in accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
Protection of outputs from surge in
accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (DO to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 1 kV; 1.2/50 µs
(DO to PE, M to PE)
* For requirements for sensors and actuators, refer to Section 6.5
Order Number
3RK1 903-3BA00
Properties
The PM-D F DC 24V PROFIsafe power module has the following properties:
• 6 safety groups SG 1 through SG 6
• Output current of SG 1 through SG 6, each 3 A (total current 5 A)
• Rated load voltage DC 24 V per safety group
• Suitable for the supply of:
- Fail-safe motor starters F-DS1e-x, F-RS1e-x,
- Fail-safe connection multipliers F-CM,
- Fail-safe power/expansion modules PM-D F X1.
- Brake Control expansion modules xB1, xB2, xB3 and xB4
• Group fault display (SF; red LED)
• Status display per safety group (SG 1 through SG 6; green LED)
• Status display for load current power supply (PWR; green LED)
• Status display for electronic power supply (U1; green LED)
• Achievable safety class (safety integrity level) AK6/SIL3/Category 4
Condition Achievable
AK/SIL/Category
Fail-safe motor starters are expanded with the expansion AK4/SIL2/Category 3
modules:
• Brake Control xB3 and xB4
Power supply for: AK6/SIL3/Category 4
• Fail-safe motor starters F-DS1e-x and
F-RS1e-x only,
• Fail-safe connection multipliers F-CM
• Fail-safe power/expansion modules PM-D F X1.
Fail-safe motor starters are expanded with the expansion
modules:
Brake Control xB1 and xB2
Note
The safety classes (safety integrity levels) AK4/SIL2/Category 3 or
AK6/SIL3/Category 4 can only be achieved with the modules specified in the
"Condition" column. Configurations with other modules (for example motor starter
DS1-x/RS1x, DS1e-x/RS1e-x, DSS1e-x) are not permitted for safety-related
applications.
Front View
PM-D F
PROFIsafe
Group error display - red
DC24V DC24V
(supply)
M M
(supply)
Warning
! The SF LED and the status displays of the outputs must not be evaluated for fail-
safe activities.
Terminal Assignment
On the PM-D F DC 24V PROFIsafe, you connect only the 24 V DC load voltage
power supply and chassis. The power module is wired on the special terminal
module.
The following table shows the terminal assignment of the PM-D F DC 24V
PROFIsafe for the permitted terminal module TM-PF30S47-F1 (order number
3RK1 903-3AA00).
Terminal Designation
20 24 VDC 24 VDC rated load voltage for:
• Inserted power module and
• Voltage buses SG 1 through SG 6 and U 1
21 M Ground
27 24 VDC 24 VDC rated load voltage for:
• Inserted power module and
• Voltage buses SG 1 through SG 6 and U 1
28 M Ground
Block Diagram
M
SG_1...6
RL
Backplane bus interface
RL
U1
5V SF
24 V
20.27 P24 U1
M
21.28 M24
Figure 9-14 Block Diagram of the PM-D F DC 24V PROFIsafe
Parameters in STEP 7
The following table presents the parameters that can be assigned for the
PM-D F DC 24V PROFIsafe power module (see also Chapter 4).
Diagnostic Functions
The following table shows an overview of the diagnostic functions of the PM-
D F DC 24V PROFIsafe power module. The diagnostic functions are assigned
either to one channel or the entire module.
Table 9-17 Causes of Errors and Corrective Measures for Diagnostic Messages of the
D F DC 24V PROFIsafe
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 196,5 x 117,5
Weight Approx. 112 g
Module-Specific Data
Number of outputs (P/P switching) 6 safety groups (SG 1 through SG 6)
Internal power supply for bus U1
Assigned address area
• In the I/O area for inputs 5 bytes
• In the I/O area for outputs 5 bytes
Maximum achievable safety class
• Complying with IEC 1508, DIN VDE SIL3, AK6, Category 4
0801 and EN 954
Fail-safe performance characteristics SIL3
• Low demand mode (average probability << 1.00 E-05
of failure on demand)
• High demand/continuous mode << 1.00 E-10
(probability of a dangerous failure per
hour)
Technical Specifications
Voltages, Currents, Potentials
Rated supply voltage L+ 24 VDC
• Permissible range 21.6 V to 26.4 V
• Power loss ride-through of L+ None
• Power loss ride-through of internal P5 5 ms
• Reverse polarity protection No
Aggregate current of outputs
• Horizontal installation Brief/permanent
- Up to 40°C 10 A/5 A
- Up to 60°C 10 A/4 A
• Vertical installation Brief/permanent
- Up to 40°C 10 A/4 A
Electrical isolation
• Between channels and backplane bus Yes
• Between channels and power supply No
• Between channels No
• Between channels/power supply and Yes
shield
Permissible potential difference between
• Shield and ET 200S bus connection 75 VDC/60 VAC
• Shield and I/O (SGs, U 1 bus) 75 VDC/60 VAC
• ET 200S bus attachment and I/O (SGs, 250 VAC
U 1 bus)
Isolation in the series tested with
• Shield and ET 200S bus connection 500 VDC/1 min or 600 VDC/1 s
• Shield and I/O (SGs, U 1 bus) 500 VDC/1 min or 600 VDC/1 s
• ET 200S bus attachment and I/O (SGs, 1500 VAC/1 min or 2545 VDC/1 s
U 1 bus)
Isolation in the type test tested with
• Shield and ET 200S bus terminal 350 VAC/1 min
• Shield and I/O (SGs, U 1 bus) 350 VAC/1 min
• ET 200S bus terminal and I/O (SGs, 2830 VAC/1 min
U 1 bus)
• Surge test between ET 200S bus 6000 VDC/5 positive and 5 negative pulses
terminal and I/O (SGs, U 1 bus)
Current consumption
• From backplane bus 28 mA, maximum
• From load voltage L+ (without load) 100 mA, typical
Power dissipation of the module 4 W, typical
Status, Interrupts, Diagnostics
Status display • Green LED per SG
• Green LED for the electronics power
supply
• Green LED for the load voltage
Technical Specifications
Diagnostic functions
• Group error display Red LED (SF)
• Diagnostic information can be displayed Possible
Time, Frequency
Internal preparation times See Chapter 13
Acknowledgment time in safety mode 4 ms minimum/8 ms maximum
Protection against Overvoltage
Protection of supply voltage L+ from surge
in accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
Order Number
6ES7 138-4FA01-0AB0
Properties
The 4/8 F-DI DC 24V PROFIsafe digital electronic module has the following
properties:
• Eight inputs (AK4/SIL2/Category 3) or four inputs (AK6/SIL3/Category 3 or 4)
• 24 VDC rated input voltage
• Suitable for switches and 3 or 4-wire proximity switches (BEROs)
• Two short-circuit-proof sensor supplies for each of the four inputs
• External sensor supply possible
• Group fault display (SF; red LED)
• Status display for each input (green LED)
• One error display for each sensor supply (1VsF and 2VsF; red LED)
• Selectable diagnostics
Table 9-18 EM 4/8 F-DI DC 24V PROFIsafe: Power Modules for AK/SIL/Category
Front View
Terminal Assignment
The terminal assignment of the EM 4/8 F-DI DC 24V PROFIsafe for the usable
terminal modules TM-E30S44-01, TM-E30C44-01, TM-E30S46-A1, and
TM-E30C46-A1 is shown in the following figure.
A15
AUX1 AUX1 (PE) A3 A7 A11 AUX1 AUX1 (PE)
at TM-E...46-A1:
AUX 1 bus implemented. Connection to terminals A3 through A16 for any connection of
PE (individual grouping of sensor power supplies possible)
Figure 9-16 Terminal Assignment of TM-E...44-01/TM-E...46-A1 for EM 4/8 F-DI DC 24V PROFIsafe
Block Diagram
Address switch
1Vs 2VsF
M M
2,6,4,8 10,14,12,16 Vs2
* Vs1 *
1 9
5 13
3 11
7 M 15
Processing logic
Test
Backplane bus interface
Filter logic
Status
M
SF
5
M
24
P1 V
P2
* The representation of the NO contacts is as printed on the module. Generally, however, the
sensor contacts must be NC contacts (due to safe state of the process variables).
Parameters in STEP 7
The following table shows the parameters that can be assigned for the
EM 4/8 F-DI DC 24V PROFIsafe (see also Chapter 4).
Input Delay of 3 ms
Note
To avoid a safety-related shutdown, you must use shielded cables for the fail-
safe digital inputs and sensor supply when using an assigned input delay of
3 ms. Alternatively, you can assign an input delay of 15 ms.
Requirements
You have set the following:
• Sensor evaluation: "1oo2 evaluation" und
• Type of sensor: "2-channel equivalent" or "2-channel non-equivalent"
"Provide 0 Value"
The value "0" is immediately made available to the safety program in the F-CPU as
soon as a discrepancy is detected between the signals of the two affected input
channels.
If you assigned the parameter "Provide 0 value", the sensor-actuator response time
will not be affected by the discrepancy time.
Discrepancy Time
Here, you can specify the discrepancy time for each pair of channels. The value
entered is rounded to multiples of 10 ms.
Requirements
You have set the following:
• Sensor evaluation: "1oo2 evaluation" und
• Type of sensor: "2-channel equivalent" or "2-channel non-equivalent"
Requirements
Safety class?
Use Cases 1 to 3
1 2 3
See See See
Section 9.5.2 Section 9.5.3 Section 9.5.4
Figure 9-18 Selecting a Application – 4/8 F-DI DC 24V PROFIsafe Electronic Module
Warning
! The achievable safety class is dependent on the quality of the sensor and the
magnitude of the proof-test interval in accordance with IEC 61508 (interval for
external function test). If the quality of the sensor is lower than the quality
stipulated in the required safety class, the sensor must be applied redundantly
with a two-channel connection.
Table 9-20 EM 4/8 F-DI DC 24V PROFIsafe: Conditions for Achieving the
AK/SIL/Category
Note
You can operate the various inputs of an F-DI module simultaneously in
AK4/SIL2/Category 3 and in AK6/SIL3/Category 3 or 4. You only need to
interconnect and assign parameters for the inputs as shown in the following
sections.
Sensor Requirements
When using sensors for safety-related applications, please note the information in
Section 6.5 "Requirements for Sensors and Actuators“.
Sensor Supply
The EM 4/8 F-DI DC 24V PROFIsafe provides sensor supply Vs1 for inputs 0 to 3
and sensor supply Vs2 for inputs 4 to 7. The sensor supply can be provided
internally or externally.
8 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0 S1 S2 S3 S4 S5 S6 S7
L+ M
Figure 9-19 Wiring Diagram EM 4/8 F-DI DC 24V PROFIsafe – One sensor 1-channel connected,
internal
sensor power supply
8 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0 S1 S2 S3 S4 S5 S6 S7
L+ M
Figure 9-20 Wiring Diagram EM 4/8 F-DI DC 24V PROFIsafe – One sensor 1-channel connected,
external sensor power supply
Wiring Diagram for Application 2.1 – Connecting one channel of one sensor to
two inputs
One channel of a sensor is connected to two inputs of the F-module for each
process signal (1oo2 evaluation).
Note
If the voltage is supplied to the sensor by the F-DI module, you must use the
internal sensor power supply Vs1. Connection to Vs2 is not possible.
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
L+ M
Figure 9-21 Wiring Diagram EM 4/8 F-DI DC 24V – One channel of a sensor connected to two inputs,
internal power supply
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
L+ M
Figure 9-22 Wiring diagram EM 4/8 F-DI DC 24V – one channel of a sensor connected to two inputs,
external power supply
Warning
! To achieve AK6/SIL3/Category 3 using this wiring, you must use a sensor
qualified for this class.
Table 9-22 EM 4/8 F-DI DC 24V PROFIsafe: Fault Detection (Application 2.1)
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-25 Wiring Diagram EM 4/8 F-DI DC 24V – Two channels of two 1-channel sensors connected,
internal sensor power supply
Warning
! To achieve AK6/SIL3/Category 3 using this wiring, you must use a sensor
qualified for this class.
Table 9-23 EM 4/8 F-DI DC 24V PROFIsafe: Fault Detection (Application 2.2)
Note
If the voltage is supplied to the sensor by the F-DI module, you must use the
internal sensor supply Vs1. Connection to Vs2 is not possible.
4 F-DI
L+ M Vs1 DI0 * DI1 * DI2 * DI3 * Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-26 Wiring Diagram EM 4/8 F-DI DC 24V – Two channels of a non-equivalent sensor connected,
internal sensor power supply
4 F-DI
L+ M Vs1 DI0 * DI1 * DI2 * DI3 * Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-27 Wiring Diagram EM 4/8 F-DI DC 24V – Two channels of a non-equivalent sensor connected,
external sensor power supply
4 F-DI
L+ M Vs1 DI0 * DI1 * DI2 * DI3 * Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-28 Wiring Diagram EM 4/8 F-DI DC 24V – Two channels of two 1-channel sensors connected
non-equivalent, internal sensor power supply
Warning
! To achieve AK6/SIL3/Category 3 using this wiring, you must use a sensor
qualified for this class.
Table 9-24 EM 4/8 F-DI DC 24V PROFIsafe: Fault Detection (Application 2.3)
Sensor Supply
The EM 4/8 F-DI DC 24V PROFIsafe provides sensor supply Vs1 for inputs 0 to 3
and sensor supply Vs2 for inputs 4 to 7. The sensor must be supplied internally.
4 F-DI
L+ M Vs1 DI0 DI1 DI2 DI3 Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-29 Wiring Diagram EM 4/8 F-DI DC 24V PROFIsafe – Two channels of a 2-channel sensor
connected, internal sensor power supply
As an alternative, you can connect two 1-channel sensors (see Figure 9-25). In this
case, the same process variable is acquired with two mechanically separate
sensors.
Warning
! To achieve AK6/SIL3/Category 4 using this wiring, you must use a sensor
qualified for this class.
Note
You must use the internal sensor supply Vs1 to supply voltage to the sensor.
Connection to Vs2 is not possible.
4 F-DI
L+ M Vs1 DI0 * DI1 * DI2 * DI3 * Vs2 DI4 DI5 DI6 DI7
S0
S1
S2
S3
Figure 9-30 Wiring Diagram EM 4/8 F-DI DC 24V – Two channels of a non-equivalent sensor connected,
internal sensor power supply
Warning
! To achieve AK6/SIL3/Category 4 using this wiring, you must use a sensor
qualified for this class.
Table 9-25 EM 4/8 F-DI DC 24V PROFIsafe: Fault Detection (Applications 3.1 and 3.2)
Diagnostic Functions
The following table shows an overview of the diagnostic functions of the
EM 4/8 F-DI DC 24V PROFIsafe. The diagnostic functions are assigned either to
one channel or the entire module.
Note
If you have activated the short-circuit test for the F-DI module in STEP 7 and
are using only one of the two internal sensor supplies of the module (Vs1 or Vs2),
a channel M-short circuit is then detected for each of the four channels with a
sensor supply that is not used. Four "short-circuit" diagnostic functions are
generated in the diagnostic buffer of the F-module.
Table 9-27 Diagnostic Messages of the EM 4/8 F-DI DC 24V PROFIsafe, Causes of
Errors and Corrective Measures
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 81 x 52
Weight Approx. 78 g
Module-Specific Data
Number of inputs
• 1-channel 8, maximum
• 2-channel 4, maximum
Assigned address area
• I/O area for inputs 6 Byte
• I/O area for outputs 4 Byte
Length of cable
• Unshielded * max. 200 m
(at input delay 3 ms * and 15 ms)
• Shielded * max. 200 m
(at input delay 0.5 ms, 3 ms and 15 ms)
Technical Specifications
Maximum achievable safety class 1-channel 2-channel
• In accordance with IEC 61508 SIL2 SIL3
• In accordance with DIN VDE 0801 AK4 AK6
• In accordance with EN 954 Category 3 Category 4
Fail-safe performance characteristics SIL2 SIL3
• Low demand mode (average probability << 1.00 E-03 << 1.00 E-05
of failure on demand)
• High demand/continuous mode << 1.00 E-08 << 1.00 E-10
(probability of a dangerous failure per
hour)
Voltages, Currents, Potentials
Rated supply voltage L+ 24 VDC
• Permissible range 20.4 V to 28.8 V
• Power loss ride-through of L+ None
• Power loss ride-through of internal P5 5 ms
• Reverse polarity protection No
Number of simultaneously controllable
inputs
• Horizontal installation
- Up to 55°C 8 (with 28.8 V)
- Up to 60°C 8 (with 24 V)
- Up to 60°C 6 (with 28.8 V)
• Vertical installation
- Up to 40°C 8
Electrical isolation
• Between channels and backplane bus Yes
• Between channels and power supply No
• Between channels No
• Between channels/power supply and Yes
shield
Permissible potential difference between
• Shield and ET 200S bus connection 75 VDC/60 VAC
• Shield and I/O (DIs, P1/P2 buses) 75 VDC/60 VAC
• ET 200S bus connection and I/O 1500 VAC/1 min or 2545 VDC/1 s
(DIs, P1/P2 buses)
Technical Specifications
Isolation in the type test tested with
• Shield and ET 200S bus connection 350 VAC/1 min
• Shield and I/O (DIs, P1/P2 buses) 350 VAC/1 min
• ET 200S bus connection and I/O 2830 VAC/1 min
(DIs, P1/P2 buses)
• Impulse current test between ET 200S 6000 VDC/5 positive and 5 negative pulses
bus connection and I/O (DIs, P1/P2
buses)
Current consumption
• From backplane bus 28 mA, typical
• From load voltage L+ (without load) 120 mA, typical
Power dissipation of the module 4 W, typical
Status, Interrupts, Diagnostics
Status display
Inputs Green LED per channel
sensor supply Red LED per channel
Diagnostic functions
• Group error display Red LED (SF)
• Diagnostic information can be displayed Possible
Sensor Supply Outputs
Number of outputs 2
Output voltage
• Loaded Minimum L+ (-1.5 V)
Output current
• Rated value 300 mA
• Permissible range 0 mA to 300 mA
Permissible aggregate current of outputs 600 mA
Short-circuit protection Yes, electronic
• Operating value 0.7 A to 1.8 A
Data for Selecting a Sensor**
Input voltage
• Rated value 24 VDC
• For "1“ signal 15 V to 30 V
• For "0“ signal -30 V to 5 V
Input current
• For "1“ signal 3,7 mA, typical
Technical Specifications
Input delay* Assignable
(for all inputs together)
• For "0“ after "1“ Typically 0.5 ms (0.3 ms to 0.7 ms)
Typically 3 ms (2.6 ms to 3.4 ms)
Typically 15 ms (13 ms to 17 ms)
• For "1“ after "0“ Typically 0.5 ms (0.3 ms to 0.7 ms)
Typically 3 ms (2.6 ms to 3.4 ms)
Typically 15 ms (13 ms to 17 ms)
Input characteristic In accordance with IEC 1131, Type 1
Connection of 2-wire proximity switch Not possible
• Permissible quiescent current 0.6 mA, maximum
Time, Frequency
Internal preparation times See Chapter 13
Acknowledgment time in safety mode
• Short-circuit test activated
at input delay of 0.5 ms: min. 4 ms / max. 7 ms
at input delay of 3 ms: min. 4 ms / max. 12 ms
at input delay of 15 ms: min. 4 ms / max. 9 ms
• Short-circuit test deactivated 4 ms minimum/6 ms maximum
Minimum sensor signal duration See Table 6-2
Protection against Overvoltage
Protection of supply voltage L+ from surge
in accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
Protection of inputs and outputs from surge
stressing in accordance with IEC 61000-4-5
with external protection elements only
• Symmetrical (Vs, DI to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 1 kV; 1.2/50 µs
(Vs, DI to PE, M to PE)
* With an input delay of 0.5 ms, shielded cable must be used for the digital inputs and the sensor
supply.
At a 3 ms input delay, to avoid a safety shutdown of the fail-safe digital inputs and the sensor power
supply, you must use shielded cables if there is a risk of overvoltage on the lines (see Section 8.3).
Order Number
6ES7 138-4FB01-0AB0
Properties
The 4 F-DO DC 24V/2 A PROFIsafe digital electronic module has the following
properties:
• Four outputs, P/M switching
• 2 A output current
• 24 VDC rated load voltage
• Suitable for solenoid valves, DC contactors, and indicator lamps
• Group fault display (SF; red LED)
• Status display for each output (green LED)
• Selectable diagnostics
• Safety class SIL3 achievable
Load
Central
groun-
ding
M
M M-switch 1P5
Readback M output
Figure 9-31 Connecting Non-Floating Loads (resistance exists between chassis and ground)
Front View
Warning
! The SF LED and the status displays of the outputs must not be evaluated for fail-
safe activities.
Terminal Assignment
The terminal assignment of the EM 4 F-DO DC 24V/2 A PROFIsafe for the usable
terminal modules TM-E30S44-01, TM-E30C44-01, TM-E30S46-A1, and TM-
E30C46-A1 is shown in the following figure.
- - 3 7 11 15 - -
- - 4 8 12 16
- -
A15
AUX1 AUX1 (PE) A3 A7 A11 AUX1 AUX1 (PE)
DOx P and DOx M: Connection for fail-safe digital output (P/M switching)
at TM-E...46-A1:
AUX 1 bus implemented. Connection to terminals A3 to A16 for any connection of PE
(individual grouping of load current power supplies possible)
Block Diagram
Address switch
P-switch
1
9
2 13
Readback
Processing logic
6
10
Backplane bus interface
M-switch
14
M
Status of
the
Output
SF
5
M
24 V
P1
P2
Wiring Diagram
The four fail-safe digital outputs each consist of one P-switch (current sourcing)
DOx P and one M-switch (current sinking) DOx M. They connect the load between
the P and M-switches. Both switches are always set so that voltage is applied to
the load.
The wiring is carried out on an appropriate terminal module.
4 F-DO
DO0 DO0 DO1 DO1 DO2 DO2 DO3 DO3
L+ M (P) (M) (P) (M) (P) (M) (P) (M)
K0 K1 K2 K3
L+ M
4 F-DO
DO0 DO0 DO1 DO1 DO2 DO2 DO3 DO3
L+ M (P) (M) (P) (M) (P) (M) (P) (M)
K1 K2
K1
K2
M
L+ M
Figure 9-36 Wiring Diagram with 2 Relays to 1 F-DO of the EM 4 F-DO DC 24V/2A PROFIsafe
Warning
! When connecting two relays on one digital output, (as shown in the figure above),
the errors "wire break“ and "overload“ are detected only at the P-switch (not at
the M-switch).
The controlled actuator can no longer be switched off when there is a cross circuit
between the P and M-switches of the output.
Warning
! To avoid cross circuits between P and M-switches of a fail-safe digital output, you
should connect the relay on the between P and M-switches to protect against
cross circuits (for example with cables separately sheathed or in a separate cable
duct).
4 F-DO
DO0 DO0 DO1 DO1 DO2 DO2 DO3 DO3
L+ M (P) (M) (P) (M) (P) (M) (P) (M)
K1 K3
K1 K3
K2 K4
K2 K4
M M
L+ M
Figure 9-37 Wiring Diagram with 2 Relays in Parallel to 1 F-DO of the EM 4 F-DO DC 24V/2A
PROFIsafe
Note
If two relays are connected in parallel to one digital output (as shown in the figure
above), "wire break“ is detected only if the wire break disconnects both relays
from P or M. This diagnostics is not relevant to safety.
Parameters in STEP 7
The following table shows the parameters that can be assigned for the F-DO
module (see also Chapter 4).
Readback Time
Each output channel has its own selectable readback time. This time specifies the
maximum duration of the turn off test for the corresponding channel and therefore
also the readback time for turning off the channel.
You can set the following readback times: 1 ms, 5 ms, 10 ms, 50 ms, 100 ms,
200 ms and 400 ms.
You should set an adequately high readback time if the channel involved switches
high capacitive loads. If the readback time for a controlled capacitive load is set too
low, the output channel is passivated because the discharge of the capacitance
does not take place within the turn off test.
If the readback signals are incorrect, the "short circuit" error causes the passivation
of the output channel after the readback time elapses.
10.000,0
1.000,0
Capacitive load in µF
100,0
10,0
1,0
0,1
9 20 50 100 200 500 750 1000 1250 1500 1750 2000
Load current in m A
Figure 9-38 Relationship between Load Resistance and Switchable Load Capacitance for
EM 4 F-DO DC 24V/2A PROFIsafe
Remedy:
1. Determine the load current and capacitance of the load.
2. Determine the operating point in the figure above.
3. If the operating point is above the curve, you must increase the load current
until the new operating point is below the curve by connecting a resistor in
parallel.
Diagnostic Functions
The following table presents an overview of the diagnostic functions of the
EM 4 F-DO DC 24V/2 A PROFIsafe digital electronic module. The diagnostic
functions are assigned either to one channel or the entire module.
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 81 x 52
Weight Approx. 85 g
Module-Specific Data
Number of outputs (P-M switching) 4
Assigned address area
• I/O area for inputs 5 bytes
• I/O area for outputs 5 bytes
Length of cable
• Unshielded 200 m, maximum
• Shielded 200 m, maximum
Maximum achievable safety class
• In accordance with IEC 61508 SIL3
• In accordance with DIN VDE 0801 AK6
• In accordance with EN 954 Category 4
Fail-safe performance characteristics SIL3
• Low demand mode (average probability << 1.00 E-05
of failure on demand)
• High demand/continuous mode << 1.00 E-10
(probability of a dangerous failure per
hour)
Voltages, Currents, Potentials
Rated supply voltage L+ 24 VDC
• Permissible range 20.4 V to 28.8 V
• Power loss ride-through of L+ None
• Power loss ride-through of internal P5 5 ms
• Reverse polarity protection No
Aggregate current of outputs
• Horizontal installation
- Up to 40°C 6A
- Up to 55°C 5A
- Up to 60°C 4A
• Vertical installation
- Up to 40°C 4A
Technical Specifications
Electrical isolation
• Between channels and backplane bus Yes
• Between channels and power supply No
• Between channels No
• Between channels/power supply and Yes
shield
Permissible potential difference between
• Shield and ET 200S bus connection 75 VDC/60 VAC
• Shield and I/O (DOs, P1/P2 buses) 75 VDC/60 VAC
• ET 200S bus connection and I/O (DOs, 250 VAC
P1/P2 buses)
Isolation in the series tested with
• Shield and ET 200S bus connection 500 VDC/1 min or 600 VDC/1 s
• Shield and I/O (DOs, P1/P2 buses) 500 VDC/1 min or 600 VDC/1 s
• ET 200S bus connection and I/O (DOs, 1500 VAC/1 min or 2545 VDC/1 s
P1/P2 buses)
Isolation in the type test tested with
• Shield and ET 200S bus connection 350 VAC/1 min
• Shield and I/O (DOs, P1/P2 buses) 350 VAC/1 min
• ET 200S bus connection and I/O (DOs, 2830 VAC/1 min
P1/P2 buses)
• Impulse current test between ET 200S 6000 VDC/5 positive and 5 negative pulses
bus connection and I/O (DOs, P1/P2
buses)
Current consumption
• From backplane bus 28 mA, maximum
• From load voltage L+ (without load) 100 mA, typical
Power dissipation of the module 3.5 W, typical
Status, Interrupts, Diagnostics
Status display
Outputs Green LED per channel
Diagnostic functions
• Group error display Red LED (SF)
• Diagnostic information can be displayed Possible
Data for Selecting an Actuator*
Output voltage
• For "1“ signal • Minimum L+ (-2.0 V)
• P-switch: min. L+ (-1.5 V), voltage drop
at M-switch:
max. 0.5 V
Technical Specifications
Output current for "1“ signal
• Rated value 2A
• Permissible range 20 mA to 2.4 A
For "0“ signal (residual current) 0.5 mA, maximum
Indirect control of load by means of interface
relay:
For "0“ signal (residual current)
• P-switch 0.5 mA, maximum
• M-switch 4 mA, maximum
Load resistance range 12 Ω to 1 kΩ
Lamp load 10 W, maximum
Wire break monitoring (open load detection)
and overload monitoring
• Response threshold I < 4 to 19 mA
• Fault detection time Depending on the selected readback time
(see Chapter 13)
Parallel connection of 2 outputs Not possible
Control of a digital input Not possible
Switching frequency
• With resistive load 30 Hz, maximum
• With inductive load in accordance with 0.1 Hz, maximum
IEC 947-5-1, DC13
• With lamp load 10 Hz, maximum
Voltage induced on current interruption Typically L+ (-47 V)
limited to
Short-circuit protection of output Yes, electronic
• Response threshold (short circuit) 5 A to 12 A
• Response threshold (external M-short 5 A to 12 A
circuit)
• Response threshold (external P-short 25 A to 45 A
circuit)
Overload protection Yes
• Response threshold I >2.6 A to 2.8 A
Time, Frequency
Internal preparation times See Chapter 13
Acknowledgment time in safety mode 4 ms minimum/8 ms maximum
Technical Specifications
Protection against Overvoltage
Protection of supply voltage L+ from surge
in accordance with IEC 61000-4-5 with
external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
Protection of inputs and outputs from surge
stressing in accordance with IEC 61000-4-5
with external protection elements only
• Symmetrical (L+ to M) + 1 kV; 1.2/50 µs
• Asymmetrical + 2 kV; 1.2/50 µs
(L+ to PE, M to PE)
* For requirements for sensors and actuators, refer to Section 6.5
Introduction
This appendix describes the structure of diagnostic data in the system data. You
need to know this structure if you want to evaluate diagnostic data of fail-safe
modules in the standard user program.
Further Reading
The System and Standard Functions reference manual describes in detail the
principles of evaluating diagnostic data of F-modules in the standard user program
and describes the SFCs used for this.
Bytes 0 and 1
The following figure shows the content of bytes 0 and 1 of the diagnostic data.
7 6 5 4 3 2 1 0
Byte0 0 0 0 0 0
Module fault
0: F-module ok
1: F-module fault; bits 2 and 3 are
then also set
External fault
Channel fault exists
7 6 5 4 3 2 1 0
Byte1 0 0 0 1
Module class:
1000B for F-modules
7 6 5 4 3 2 1 0
Byte2 0 0 0 0 0 0 0 0 Always "0"
7 6 5 4 3 2 1 0
Byte3 0 0 0 0 0 0 0 0 Always "0"
Bytes 4 to 6
The following figure shows the content of bytes 4 to 6 of the diagnostic data.
7 6 5 4 3 2 1 0
Byte4 0
7 0
Byte6
Number of channels
8: EM 4/8 F-DI
4: EM 4 F-DO
3: PM-E F
1: PM-E F PP
6: PM-D F
7 6 5 4 3 2 1 0
Byte7
Figure 10-4 Byte 7 of the Diagnostic Data for the EM 4/8 F-DI DC24V PROFIsafe
7 6 5 4 3 2 1 0
Byte7 0 0 0 0
Figure 10-5 Byte 7 of the Diagnostic Data for EM 4 F-DO DC24V/2A PROFIsafe
7 6 5 4 3 2 1 0
Byte7 0 0 0 0 0
Figure 10-6 Byte 7 of the Diagnostic Data for PM-E F pm DC24V PROFIsafe
7 6 5 4 3 2 1 0
Byte7 0 0 0 0 0 0 0
Figure 10-7 Byte 7 of the Diagnostic Data for PM-E F pp DC24V PROFIsafe
7 6 5 4 3 2 1 0
Byte7 0 0
Figure 10-8 Byte 7 of the Diagnostic Data for PM-D F DC24V PROFIsafe
7 6 5 4 3 2 1 0
Byte8 0 0 0 0
Short circuit
Overload
Excess temperature
Wire break
7 6 5 4 3 2 1 0
Byte9 0 0 0 0 0 0 0
Internal error
7 6 5 4 3 2 1 0
Byte10 0 0 0 0 0
Parameter
Sensor voltage or load voltage is missing
Communication error
7 6 5 4 3 2 1 0
Byte11 0 0 0 0 0 0 0
Safety-related deactivation
F-DI module: Discrepancy error
F-DO module and PM-E F:
Switching frequency exceeded
Due to the different numbers of channels of the F-modules, data record 1 has
differing lengths:
• EM 4/8 F-DI DC24V PROFIsafe 40 bytes
• EM 4 F-DO DC24V/2A PROFIsafe 24 bytes
• PM-E F pm DC24V PROFIsafe 20 bytes
• PM-E F pp DC24V PROFIsafe 12 bytes
• PM-D F DC24V PROFIsafe 32 bytes
Below you will find the a dimension drawing for each of the following:
• Terminal modules TM-x30x4x-xx with PM-E F pm-, PM-E F pp-, F-DI- or F-DO
module inserted
• Terminal module TM-PF30S47-F1 with PM-D F module inserted
3
66,5
Supporting
standard rail
157
90,5
30 67
3 66,5
Supporting
132
standard rail
65,5
30
67
Figure 11-1 Dimension Drawing of Terminal Modules with PM-E F pm, PM-E F pp, F-DI or F-DO
Module Inserted
Introduction
The response times of ET 200S fail-safe modules are presented below. The
response times of fail-safe modules are included in the calculation of F-system
response time.
You will find information about the calculation of F-system response times in the
Safety Engineering in SIMATIC S7 system description.
Table 13-2 PM-E F pm DC24V PROFIsafe: Internal Conditioning Times of the P1/2
Channel
Table 13-6 EM 4/8 F-DI DC24V PROFIsafe: Maximum Response Time if a Fault Occurs
Note
The MS Excel files for calculating maximum response times (s7fcotib.xls or
s7ftimeb.xls) provided with the S7 Distributed Safety and S7 F/FH Systems
optional packages support calculation of the “maximum response time when a
fault is present” by increasing the reaction time by the amount of the
parameterized discrepancy time.
1oo1 Evaluation 1oo1 evaluation is a type of sensor evaluation in which one -> sensor is
connected to the F-module by means of a single channel.
1oo2 Evaluation -> Sensor evaluation method - In 1oo2 evaluation, two input channels
are occupied, either by one 2-channel sensor or two single-channel
sensors. The input signals are compared internally for equivalence or
non-equivalence.
A
Acknowledgment During the acknowledgement time, the -> F-I/O acknowledge the sign of
Time life specified by the -> F-CPU. The acknowledgement time enters into
the calculation of the -> monitoring time and -> reaction time for the
F-system as a whole.
AUX1 Bus Power modules allow the additional connection of a voltage (24 V DC)
that you can apply over the AUX(iliary) bus. AUX(iliary) buses can be
used individually as a protective conductor bus or they can be used to
supply additional voltage.
Channel fault This is a channel-specific error, such as a wire break or a short circuit.
In channel-specific passivation, the affected channel is either
automatically reintegrated or the F-module must be removed and
reinserted after the error has been eliminated.
Channel group The channels of a module are grouped together in a channel group.
Certain parameters in STEP 7 can only be assigned to channel groups,
rather than to individual channels.
Channel Number Channel numbers are used to uniquely identify the inputs and outputs of
a module and to assign channel-specific diagnostic messages.
Channel-Specific In this passivation method, when a -> channel fault occurs, only the
Passivation channel involved is passivated (method available in S7 F/FH systems
only). In the event of a -> module fault, all channels of the -> fail-safe
module are passivated.
CRC Signature The validity of the process values in the safety message frame, the
accuracy of the assigned address references, and the safety-related
parameters are ensured by means of a CRC signature contained in the
safety message frame.
D
Dark period Dark periods occur during switch-off tests and during complete bit
pattern tests. This involves test-related 0 signals being switched to the
output by the fail-safe output module while the output is active. The
output is then switched off briefly (dark period). A sufficiently slow ->
actuator does not respond and remains switched on.
Discrepancy Time Discrepancy time is a period of time configured for the -> discrepancy
analysis. If the discrepancy time is set too high, the times for fault
detection and -> fault reaction are extended unnecessarily. If the
discrepancy time is set too low, availability is decreased unnecessarily
because a discrepancy error is detected when, in reality, no error exists.
Fail-Safe Systems Fail-safe systems (F-systems) are systems that remain in a safe state or
immediately switch to another safe state as soon as particular failures
occur.
Fault reaction time The maximum fault reaction time for an F-system is the time between
the occurrence of any fault and a safe response at all affected fail-safe
outputs.
For -> F-System in total: The maximum fault reaction time is the time
between occurrence of any fault in any ->
F-I/O and a safe response at the relevant fail-safe output.
For digital inputs: The maximum fault reaction time is the time
between the occurrence of a fault and a safe response at the backplane
bus.
For digital outputs: The maximum fault reaction time is the time
between the occurrence of a fault and a safe response at the digital
output.
F-I/O F-I/O is a group designation for fail-safe inputs and outputs available in
SIMATIC S7 for integration in S7 Distributed Safety and S7 F/FH
systems. The following F-I/O modules are available:
• Fail-safe I/O module for ET 200eco
• S7-300 fail-safe signal modules (F-SMs)
• Fail-safe modules for ET 200S
• Fail-safe DP standard slaves (for S7 Distributed Safety only)
Motor Starter (MS) Motor starter is a general term referring to direct starters and reversing
starters. Motor starters are used to specify motor startup and direction
of rotation.
M-Switch In the ET 200S fail-safe modules, every fail-safe digital output consists
of a P-switch DOx P (current sourcing) and an M-switch DOx M (current
sinking). The load is connected between the P and M-switches. Both
switches are always set so that voltage is applied to the load.
N
Non-equivalent A nonequivalent -> sensor is a reversing switch that is connected to two
sensor inputs of an -> F-I/O (via 2 channels) in -> fail-safe systems (for -> 1oo2
evaluation of sensor signals).
P
Parameter Parameter assignment over PROFIBUS DP: Transfer of slave
Assignment parameters from the DP master to the DP slave
Parameter assignment of modules: Setting the module behavior
using the STEP 7 configuration software
Passivation If an -> F-I/O module detects a fault, it switches either the affected
channel or all channels to a -> safe state; that is, the channels of the
F-I/O module are passivated. The F-I/O signals the detected faults to
the -> F-CPU.
For an F-I/O with inputs, if passivation occurs, the F-system provides
fail-safe values for the safety program instead of the process values
pending at the fail-safe inputs.
For an I/O module with outputs, if passivation occurs, the F-system
transfers fail-safe values (0) to the fail-safe outputs instead of the output
values provided by the safety program.
Prewiring Prewiring means wiring the terminal modules before inserting the
electronic modules.
Process Image The process image is a component of the system memory of the CPU.
At the beginning of the cyclic program, the signal states of the input
modules are transferred to the process image of the inputs. At the end
of the cyclic program, the process image of the outputs are transferred
as a signal state to the DP slave.
Process safety The process safety time of a process is a time interval during which the
time process can be left on its own without risk to life and limb of the
operating personnel or damage to the environment.
Within the fault tolerance time, any type of F-system process control is
tolerated. That is, during this time, the -> F-system can control its
process incorrectly or it can even exercise no control at all. The fault
tolerance time depends on the process type and must be determined on
a case-by-case basis.
PROFIBUS PROcess FIeld BUS, process and fieldbus standard specified in IEC
61784-1:2002 Ed1 CP 3/1. This standard specifies functional, electric,
and mechanical properties for a bit-serial field bus system.
PROFIBUS is available with the following protocols: DP (= distributed
I/O), FMS (= Fieldbus Message Specification), PA (= Process
automation), or TF (= Technological functions).
PROFIsafe Every -> fail-safe module has a PROFIsafe address You must configure
Address the PROFIsafe address in STEP 7 HW Config and set it on the F-I/O
using a switch.
Proof-Test Interval A component must be set in the fail-safe state following the proof-test
interval. That is, it is replaced by an unused component or it is proven to
be completely error-free.
Reintegration Once a fault has been eliminated, the -> F-I/O must be reintegrated
(depassivated). The reintegration (switchover from fail-safe values to
process values) occurs either automatically or only after user
acknowledgement in the safety program.
For an F-I/O module with inputs, the process values pending at the fail-
safe inputs are provided again for the -> safety program after
reintegration. For an F-I/O module with outputs, the -> F-system again
transfers the output values provided in the safety program to the fail-
safe outputs.
Response time Response time starts with the detection of an input signal and ends with
the modification of a gated output signal.
The actual response time is between the shortest and the longest
response time. The longest response time must be used as a reference
for configuring a system. For fail-safe digital inputs, the response time
begins with a signal change at the digital input and ends when the
safety message frame is safely prepared at the backplane bus. For fail-
safe digital outputs, the response time begins with an incoming safety
message frame from the backplane bus and ends with a signal change
at the digital output.
For fail-safe digital inputs: the reaction time represents the time
between a signal change at the digital input and safe delivery of the
safety message frame on the backplane bus.
For fail-safe digital outputs: the reaction time represents the time
between an arriving safety message frame from the backplane bus and
the signal change at the digital output.
Reversing Starter A reversing starter is a -> motor starter that determines the rotational
direction of a motor. It comprises a circuit-breaker and two contactors.
S
Safe State The basic principle of the safety concept in F-systems is the existence
of a safe state for all process variables. For the digital F-I/O, the safe
state is, for example, the value "0".
Safety Class (AK) Safety level (AK) in accordance with DIN V 19250 (DIN V VDE 0801):
Safety classes are a way to categorize safety requirements for
preventing and remedying faults. With -> fail-safe modules, safety
requirement classes up to A6 can be used in -> safety mode.
Safety Function Safety function is a mechanism built into the -> F-CPU and -> F-I/O that
allows them to be used in -> S7 Distributed Safety or S7 F/FH systems.
IEC 61508: Function implemented by a safety system to ensure that the
system is kept in a safe state or brought to a safe state in the event of a
particular fault.
Safety Integrity The safety integrity level (SIL) is a safety class in accordance with
Level IEC 61508 and prEN 50129. The higher the safety integrity level, the
stricter the measures must be to prevent and eliminate systematic faults
and to remedy hardware failures.
Safety modules can be used in safety mode up to SIL3.
Safety Message In safety mode, data is transferred between the -> F-CPU and the
Frame -> F-I/O in a safety message frame.
Safety Mode Safety mode is the operating mode of the -> F-I/O that allows -> safety-
related communication by means of -> safety message frames.
ET 200S -> fail-safe modules are designed for operation only in safety
mode.
Sensors Sensors permit exact acquisition of digital and analog signals and exact
measurement of routes, positions, velocities, rotational speeds, weights,
etc.
Static parameters Static parameters can only be set when the CPU is in STOP mode and
cannot be changed by means of SFC (system function) while the user
program is running.
T
Terminal Module The ET 200S distributed I/O system is terminated with the terminal
module. If a terminal module is not inserted, the ET 200S is not ready
for operation.
V
Voltage Bus Voltage buses (P1 and P2) are two internal buses that supply the
(P1/P2) electronic modules with voltage. The voltage buses are fed by the
power module and are connected by means of the terminal module.
F G
F Configuration Pack ..................................... 4-1 General technical specifications .....................8-1
F modules ............................................. 2-2, 14-3 Guide to the manual
Address assignment in the F-CPU............. 5-1 To manual ..................................................1-5
available..................................................... 2-4
Configuration.............................................. 4-1
Dimension Drawings ................................ 11-1 H
Fault reaction ............................................. 7-2 H/F Competence Center.................................1-6
inserting and removing............................... 6-5
installing ..................................................... 5-5
Mounting Dimensions ................................ 5-5 I
Order Number ............................................ 1-1
Parameter assignment............................... 4-1 IEC 61131 ......................................................8-4
Parameter Length ...................................... 3-7 IM 151-7 F-CPU .............................................2-4
possible uses ............................................. 2-2 IM151-1 HIGH FEATURE...............................2-4
Response time ......................................... 13-1 Input delay.............................................6-6, 13-3
Use in F-systems ....................................... 2-3 EM 4/8 F-DI DC 24V.................................9-49
wiring ......................................................... 6-4 input signals
F_destination_address................................... 5-3 Capacitive crosstalk....................................9-6
EM 4 F-DO DC 24V/2 A........................... 9-83 Inserting
EM 4/8 F-DI DC 24V ................................ 9-49 F-Module ....................................................6-5
PM-D F DC 24V ....................................... 9-40 Installing
PM-E F pm DC 24V ................................. 9-13 F-modules ..................................................5-5
PM-E F pp DC 24V .................................. 9-30 Installing the chassis cable...........................9-24
F_Source_Address ........................................ 5-3 Interface module
Fail-safe automation system .......................... 2-2 applicable ...................................................2-4
Fail-Safe Modules ....................... See F-modules Interference
fail-safe performance characteristics ............. 9-1 pulse-shaped..............................................8-7
EM 4 F-DO DC 24V/2 A........................... 9-87 sinusoidal .................................................8-10
EM 4/8 F-DI DC 24V ................................ 9-72 Internal conditioning time..............................13-1
PM-D F DC 24V ....................................... 9-42 Internal error
PM-E F pm DC 24V ................................. 9-18 EM 4 F-DO DC 24V/2 A ...........................9-85
PM-E F pp DC 24V .................................. 9-33 EM 4/8 F-DI DC 24V.................................9-69
Fail-safe system............................ See F-system PM-D F DC 24V .......................................9-40
Fail-safe value output..................................... 7-2 PM-E F pm DC 24V..................................9-15
Fault detection PM-E F pp DC 24V...................................9-30
EM 4/8 F-DI DC 24V .....9-58, 9-61, 9-64, 9-68 react to .......................................................7-7
Fault reaction IP20 ..............................................................8-14
of F-modules .............................................. 7-2 Isolation test .................................................8-14
Fault response time ..................................... 14-3
Fault/Error types L
of F-modules .............................................. 7-7
F-copy license.............................................. 14-4 LED display
F-CPU.......................................................... 14-4 of faults.......................................................7-5
Addresses Occupied by Useful Data ......... 5-2 Line break.......................................................7-7
F-I/O............................................................. 14-4 Line cross section...........................................6-2
FM approval ................................................... 8-4 Load current power supply, dip
F-monitoring time ......................................... 14-4 PM-D F DC 24V .......................................9-40
EM 4 F-DO DC 24V/2 A........................... 9-83 Load current power supply, failure of
EM 4/8 F-DI DC 24V ................................ 9-49 PM-D F DC 24V .......................................9-40
PM-D F DC 24V ....................................... 9-40 Load voltage missing......................................7-7
PM-E F pm DC 24V ................................. 9-13 Loads, capacitive
PM-E F pp DC 24V .................................. 9-30 connecting .......................................9-13, 9-83
F-system ............................................... 2-2, 14-3
example configuration................................ 2-3
F-Systems............................................. 2-3, 14-4
M
Functional extra low voltage Machine protection
safe ............................................................ 6-2 applications in.............................................7-5
Fuse, external Manual
PM-E F pm DC 24V ................................. 9-10 Contents .....................................................1-5
PM-E F pp DC 24V .................................. 9-29 Manual Collection ...........................................1-4
Marking for Australia.......................................1-2
Maximum configuration
ET 200S with F-modules............................ 3-7
P
per voltage group ....................................... 3-8 Parameter
Missing external auxiliary supply EM 4 F-DO DC 24V/2 A ...........................9-83
EM 4 F-DO DC 24V/2 A........................... 9-85 EM 4/8 F-DI DC 24V.................................9-49
EM 4/8 F-DI DC 24V ................................ 9-69 PM-D F DC 24V .......................................9-40
PM-D F DC 24V ....................................... 9-40 PM-E F pm DC 24V..................................9-13
PM-E F pm DC 24V ................................. 9-15 PM-E F pp DC 24V...................................9-30
PM-E F pp DC 24V .................................. 9-30 Parameter assignment .................................14-5
Module diagnostics ........................................ 7-8 of F-modules ..............................................4-1
Module failure Parameter assignment error...........................7-7
reaction to .................................................. 7-7 EM 4 F-DO DC 24V/2 A ...........................9-85
Module fault ................................................. 14-4 EM 4/8 F-DI DC 24V.................................9-69
diagnostic message ................................... 7-7 PM-D F DC 24V .......................................9-40
Module replacement .................................... 14-4 PM-E F pm DC 24V..................................9-15
Modules PM-E F pp DC 24V...................................9-30
fail-safe ...................................................... 2-2 Parameter Length
Monitoring time ............................................ 14-4 of F-modules ..............................................3-7
EM 4 F-DO DC 24V/2 A........................... 9-83 Parameters
EM 4/8 F-DI DC 24V ................................ 9-49 static .........................................................14-8
PM-D F DC 24V ....................................... 9-40 Passivation ............................................7-2, 14-5
PM-E F pm DC 24V ................................. 9-13 channel-specific........................................14-2
PM-E F pp DC 24V .................................. 9-30 PG ...............................See Programming device
Motor starter................................................. 14-4 PM-D F DC 24V
Mounting dimensions block diagram ...........................................9-39
F-modules .................................................. 5-5 causes of errors and corrective
Mounting rails measures..............................................9-41
applicable................................................... 6-4 Diagnostic functions .................................9-40
M-Switch .................................... 9-10, 9-80, 14-4 fail-safe performance characteristics ........9-42
Fault/Error types .........................................7-7
front view ..................................................9-38
N Order Number ..........................................9-36
NAMUR recommendations parameters in STEP 7 ..............................9-40
requirements for power supply................... 6-3 Technical specifications............................9-42
Nominal line voltages................................... 8-14 Terminal assignment ................................9-39
Nonequivalence ........................................... 14-1 PM-D F DC24V ..............................................3-6
Non-equivalent sensor ................................. 14-4 PM-E 24 VDC.................................................3-6
Number of modules PM-E DC24..48V ............................................3-6
per ET 200S with F-modules...................... 3-7 PM-E DC24..48V/AC24..230V........................3-6
PM-E F DC 24V
acknowledgment time...............................9-44
O PM-E F pm DC 24V
acknowledgment time...............................9-21
Operation safety
block diagram .............................................9-9
of system ................................................... 2-1
causes of errors and corrective measures9-16
Optional package
Diagnostic functions .................................9-15
S7 distributed safety .................................. 4-1
fail-safe performance characteristics ........9-18
S7 F Systems............................................. 4-1
Fault/Error types .........................................7-7
Order numbers
F modules .................................................. 1-1 front view ................................................. 9-7
of accessories .......................................... 12-1 Order Number ............................................9-2
output signals parameters in STEP 7 ..............................9-13
Capacitive crosstalk ................................... 9-6 Readback Time ........................................9-13
Overload ........................................................ 7-7 Relay output .............................................9-10
EM 4 F-DO DC 24V/2 A......... 9-81, 9-82, 9-85 Technical specifications............................9-18
PM-E F pm DC 24V ................................. 9-11 Terminal assignment ..................................9-7
Overtemperature............................................ 7-7 Wiring diagram .........................................9-10
EM 4 F-DO DC 24V/2 A........................... 9-85 PM-E F pm DC24V.........................................3-6
EM 4/8 F-DI DC 24V ................................ 9-69
PM-D F DC 24V ....................................... 9-40
PM-E F pm DC 24V ................................. 9-15
PM-E F pp DC 24V .................................. 9-30
Name:
Siemens AG
Company:
A&D AS SM ID Position:
Postfach 1963
Street:
D-92209 Amberg
Postal code / Place:
Telefax: +49(9621)80-3103
Email:
mailto:doku@ad.siemens.de
Phone:
Fax:
Our goal is to provide you information with a high degree of quality and usability, and to continuously
improve the SIMATIC documentation for you. To achieve this goal, we require your feedback and
suggestions. Please take a few minutes to fill out this questionnaire and return it to me by Fax, e-mail or
by post.
We are giving out three presents every month in a raffle among the senders. Which present would you
like to have?
General Questions
1. Are you familiar with the SIMATIC Manual 3. Do you use Getting Starteds?
Collection?
yes no
yes no
if yes, which:
2. Have you ever downloaded manuals from the 4. How much experience do you have with the
internet? S7 Distributed Safety?
yes no Expert
Experienced user
Advanced user
Beginner
1. In which project phase do you use this Were able to find the required information?
document frequently?
yes no
Information Assembly
which was not:
Planning Commissioning
yes no
How satisfied are you with this document 7. What are your suggestions as regards the
contents of the document?
Totally satisfied not very satisfied
Satisfied