Chimney Dia HT
Chimney Dia HT
1. The maximum heat output at the heater outlet is 2, 00,000 kcal/hr.-each x 1no.
4. Burner – Oil fired pressure jet, Forced draught, Spark ignited –Fully automatic
ON-OFF -Type.
5. Completing the combustion and pushing the flue gasses out of the heater is
independently done by the Mechanical Forced draught Fan as such there is always
positive pressure at the heater flue gas outlet-As such chimney is not needed for
producing INDUCED DRAUGHT but is needed only for venting the
combustibles out from the premises at safer elevation. Height is considered as
approved by local pollution authority or at least it should be higher than the
highest structure in the locality in a radius of 300 Mtrs. The highest structure is
users own factory shed.
6. The diameter and height are selected such that induced draught produced by the
chimney takes care of the draught loss thro it.
Where:
Q – Quantity of flue gas in m3/sec.
________________
V - Velocity of flue gas in mtrs/sec.= _/ 2 g H ( Tg / Ta – 1)
_____________________________
V= _/ 2 x 9.81 x 20 (290 + 270 /30+270 -1) = 18.44mt/sec. is below 30
therefore
is OK.
the locality. The highest building structure is users own factory shed.
__________
Now Diameter D1 = __/ 4 x 0.140 / 3.14 x 0.6 x18.44 = 0.127mtr
End.
----------------------------------------