Tag name Tag Type


Master Controller
251300_RWTReturnWaterTemp.property.Present_Value.value BACnet_AI
251300_SATSupplyAirTemp.property.Present_Value.value BACnet_AI
251300_FATFreshAirTemp.property.Present_Value.value BACnet_AI
251300_SAPSupplyAirPressure.property.Present_Value.value BACnet_AI
251300_FADFreshAirDamperFB.property.Present_Value.value BACnet_AI
251300_2-WayCoolingValveFB.property.Present_Value.value BACnet_AI
251300_SFVFDSpeedFeedback.property.Present_Value.value BACnet_AI
251300_RADReturnAirDamperFB.property.Present_Value.value BACnet_AI
251300_SpaceCO2Sensor-1.property.Present_Value.value BACnet_AI
251300_2-WayCoolingValveControl.property.Present_Value.value BACnet_AO
251300_SFVFDSpeedControlCMD.property.Present_Value.value BACnet_AO
251300_FADFreshAirDamperControl.property.Present_Value.value BACnet_AO
251300_RADReturnAirDamperControl.property.Present_Value.value BACnet_AO
251300_TempSetpoint.property.Present_Value.value BACnet_AV
251300_CO2LevelSetpoint.property.Present_Value.value BACnet_AV
251300_PressureSetpoint.property.Present_Value.value BACnet_AV
251300_TempSetpointOccupied.property.Present_Value.value BACnet_AV
251300_TempSetpointUnOccupied.property.Present_Value.value BACnet_AV
251300_CO2Average.property.Present_Value.value BACnet_AV
251300_ReturnAirTemp.property.Present_Value.value BACnet_AV
251300_slave.property.Present_Value.value BACnet_AV
251300_SFVFDOnOffStatus.property.Present_Value BACnet_BI
251300_SFCurrentSwitch.property.Present_Value BACnet_BI
251300_SFVFDTripStatus.property.Present_Value BACnet_BI
251300_SFVFDEnableDisableCMD.property.Present_Value BACnet_BO
251300_AHUStartStop.property.Present_Value BACnet_BV
251300_SFAutoSwitchPosition.property.Present_Value BACnet_BV
251300_AHUGraphicsOverride.property.Present_Value BACnet_BV
251300_AHUGraphicsStartStop.property.Present_Value BACnet_BV
251300_SFManualSwitchPosition.property.Present_Value BACnet_BV
251300_Alarm.property.Present_Value BACnet_BV
251300_FlowAlarm.property.Present_Value BACnet_BV
251300_FireAlarm.property.Present_Value BACnet_BV
251300_TempCOModulation.property.Present_Value BACnet_Loop
251300_CO2LevelCOModulation.property.Present_Value BACnet_Loop
251300_PressureCOModulation.property.Present_Value BACnet_Loop
251300_AHUWeeklySchedule.property.Present_Value BACnet_Schedule
251300_SFHOASwitchMV.property.Present_Value BACnet_MSV
Slave Controller
251301_RATReturnAirTemp.property.Present_Value.value BACnet_AI
251301_SpaceCO2Sensor-2.property.Present_Value.value BACnet_AI
251301_SFAutoSwitchPosition.property.Present_Value BACnet_BI
251301_SFManualSwitchPosition.property.Present_Value BACnet_BI
251301_Pre-FilterStatus.property.Present_Value BACnet_BI
251301_Final-FilterStatus.property.Present_Value BACnet_BI
VFD Controller
251302_AnalogInput53.property.Present_Value.value BACnet_AI
251302_AnalogInput54.property.Present_Value.value BACnet_AI
251302_Terminal42OutputBusControl.property.Present_Value.value BACnet_AO
251302_Pulseout#27BusControl.property.Present_Value.value BACnet_AO
251302_Pulseout#29BusControl.property.Present_Value.value BACnet_AO
251302_InputReference1.property.Present_Value.value BACnet_AV
251302_InputReference2.property.Present_Value.value BACnet_AV
251302_OutputSpeed.property.Present_Value.value BACnet_AV
251302_PIDFeedback.property.Present_Value.value BACnet_AV
251302_MotorCurrent.property.Present_Value.value BACnet_AV
251302_Power.property.Present_Value.value BACnet_AV
251302_MotorThermal.property.Present_Value.value BACnet_AV
251302_OperatingHours.property.Present_Value.value BACnet_AV
251302_RunningHours.property.Present_Value.value BACnet_AV
251302_kWhCounter.property.Present_Value.value BACnet_AV
251302_MotorVoltage.property.Present_Value.value BACnet_AV
251302_Frequency.property.Present_Value.value BACnet_AV
251302_Torque.property.Present_Value.value BACnet_AV
251302_DCLinkVoltage.property.Present_Value.value BACnet_AV
251302_HeatsinkTemp_.property.Present_Value.value BACnet_AV
251302_InverterThermal.property.Present_Value.value BACnet_AV
251302_Setpoint1.property.Present_Value.value BACnet_AV
251302_BusFeedback1.property.Present_Value.value BACnet_AV
251302_Setpoint2.property.Present_Value.value BACnet_AV
251302_BusFeedback2.property.Present_Value.value BACnet_AV
251302_Setpoint3.property.Present_Value.value BACnet_AV
251302_BusFeedback3.property.Present_Value.value BACnet_AV
251302_LastAlarm.property.Present_Value.value BACnet_AV
251302_FaultCode.property.Present_Value.value BACnet_AV
251302_PIDStartSpeed.property.Present_Value.value BACnet_AV
251302_OnReferenceBandwidth.property.Present_Value.value BACnet_AV
251302_PIDProportionalGain.property.Present_Value.value BACnet_AV
251302_PIDIntegralTime.property.Present_Value.value BACnet_AV
251302_PIDDifferentiationTime.property.Present_Value.value BACnet_AV
251302_PIDDiff_GainLimit.property.Present_Value.value BACnet_AV
251302_SensorlessReadout.property.Present_Value.value BACnet_AV
251302_DigitalinputTerm33.property.Present_Value BACnet_BI
251302_DigitalinputTerm32.property.Present_Value BACnet_BI
251302_DigitalinputTerm29.property.Present_Value BACnet_BI
251302_DigitalinputTerm27.property.Present_Value BACnet_BI
251302_DigitalinputTerm19.property.Present_Value BACnet_BI
251302_DigitalinputTerm18.property.Present_Value BACnet_BI
251302_DigitalinputTerm37.property.Present_Value BACnet_BI
251302_DigitalOutputTerm27.property.Present_Value BACnet_BO
251302_DigitalOutputTerm29.property.Present_Value BACnet_BO
251302_Relay1.property.Present_Value BACnet_BO
251302_Relay2.property.Present_Value BACnet_BO
251302_RUNSTOPCommand.property.Present_Value BACnet_BV
251302_REF1REF2Select.property.Present_Value BACnet_BV
251302_FaultResetCommand.property.Present_Value BACnet_BV
251302_RUNSTOPMonitor.property.Present_Value BACnet_BV
251302_OKFAULTMonitor.property.Present_Value BACnet_BV
251302_HANDAUTOReference.property.Present_Value BACnet_BV
251302_Warning.property.Present_Value BACnet_BV
251302_Trip.property.Present_Value BACnet_BV
251302_Triplock.property.Present_Value BACnet_BV
251302_Coasting.property.Present_Value BACnet_BV
251302_CWCCW.property.Present_Value BACnet_BV
251302_Jog.property.Present_Value BACnet_BV
251302_Reset.property.Present_Value BACnet_BV
251302_ResetKWhCounter.property.Present_Value BACnet_BV
251302_ResetRunningHoursCounter.property.Present_Value BACnet_BV
251302_RevStatus.property.Present_Value BACnet_BV
251302_Speed=reference.property.Present_Value BACnet_BV
251302_BusControl.property.Present_Value BACnet_BV
251302_Running.property.Present_Value BACnet_BV
251302_Ramp1Ramp2.property.Present_Value BACnet_BV
251302_SmartLogicControllerState.property.Present_Value BACnet_MSV
251302_ActiveSetup.property.Present_Value BACnet_MSV
Mentioned in MTS
Tag name

Water Temperature Sensor


Air temperature sensor
Space CO2 Sensor
Air Pressure Sensor
Damper Feedback
2way valve Feedback
2 Way valve Control
Damper Control
Supply Fan VFD ensable/disable command
Supply Fan VFD Feedback
Supply Fan VFD Control
Supply Fan VFD ON/OFF status
Supply Fan Current Switch
Supply Fan VFD Trip Status
H.O.A Switch
Filter Status
Smoke Detector
VFD Software Interface
251302_MotorCurrent.property.Present_Value.value
251302_MotorThermal.property.Present_Value.value
251302_RunningHours.property.Present_Value.value
251302_kWhCounter.property.Present_Value.value
251302_MotorVoltage.property.Present_Value.value
251302_DCLinkVoltage.property.Present_Value.value
251302_HeatsinkTemp_.property.Present_Value.value
251302_InverterThermal.property.Present_Value.value
Mentioned in MTS
Tag Type Tag is Taken

Analogue Input Yes


Analogue Input (3) Yes
Analogue Input (2) Yes
Analogue Input Yes
Analogue Input (2) Yes
Analogue Input Yes
Analogue Output Yes
Analogue Output (2) Yes
Binary Output (1) Yes
Analogue Input Yes
Analogue Output Yes
Binary Input Yes
Binary Input Yes
Binary Input Yes
Binary Input (2) Yes
Binary Input (2) Yes
Binary Input (2) Yes
Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
Software Interface Yes
To be used by I2BS ( and not mentioned in MTS but exist in the scan)
Tag name

251300_TempSetpoint.property.Present_Value.value
251300_CO2LevelSetpoint.property.Present_Value.value
251300_PressureSetpoint.property.Present_Value.value
251300_TempSetpointOccupied.property.Present_Value.value
251300_TempSetpointUnOccupied.property.Present_Value.value
251300_CO2Average.property.Present_Value.value
251300_slave.property.Present_Value.value
251300_AHUStartStop.property.Present_Value
251300_AHUGraphicsOverride.property.Present_Value
251300_AHUGraphicsStartStop.property.Present_Value
251300_Alarm.property.Present_Value
251300_FlowAlarm.property.Present_Value
251300_FireAlarm.property.Present_Value
251300_TempCOModulation.property.Present_Value
251300_CO2LevelCOModulation.property.Present_Value
251300_PressureCOModulation.property.Present_Value
251300_AHUWeeklySchedule.property.Present_Value
251300_SFHOASwitchMV.property.Present_Value
251302_AnalogInput53.property.Present_Value.value
251302_AnalogInput54.property.Present_Value.value
251302_Terminal42OutputBusControl.property.Present_Value.value
251302_Pulseout#27BusControl.property.Present_Value.value
251302_Pulseout#29BusControl.property.Present_Value.value
251302_InputReference1.property.Present_Value.value
251302_InputReference2.property.Present_Value.value
251302_OutputSpeed.property.Present_Value.value
251302_PIDFeedback.property.Present_Value.value
251302_Power.property.Present_Value.value
251302_OperatingHours.property.Present_Value.value
251302_Frequency.property.Present_Value.value
251302_Torque.property.Present_Value.value
251302_Setpoint1.property.Present_Value.value
251302_BusFeedback1.property.Present_Value.value
251302_Setpoint2.property.Present_Value.value
251302_BusFeedback2.property.Present_Value.value
251302_Setpoint3.property.Present_Value.value
251302_BusFeedback3.property.Present_Value.value
251302_LastAlarm.property.Present_Value.value
251302_FaultCode.property.Present_Value.value
251302_PIDStartSpeed.property.Present_Value.value
251302_OnReferenceBandwidth.property.Present_Value.value
251302_PIDProportionalGain.property.Present_Value.value
251302_PIDIntegralTime.property.Present_Value.value
251302_PIDDifferentiationTime.property.Present_Value.value
251302_PIDDiff_GainLimit.property.Present_Value.value
251302_SensorlessReadout.property.Present_Value.value
251302_DigitalinputTerm33.property.Present_Value
251302_DigitalinputTerm32.property.Present_Value
251302_DigitalinputTerm29.property.Present_Value
251302_DigitalinputTerm27.property.Present_Value
251302_DigitalinputTerm19.property.Present_Value
251302_DigitalinputTerm18.property.Present_Value
251302_DigitalinputTerm37.property.Present_Value
251302_DigitalOutputTerm27.property.Present_Value
251302_DigitalOutputTerm29.property.Present_Value
251302_Relay1.property.Present_Value
251302_Relay2.property.Present_Value
251302_RUNSTOPCommand.property.Present_Value
251302_REF1REF2Select.property.Present_Value
251302_FaultResetCommand.property.Present_Value
251302_RUNSTOPMonitor.property.Present_Value
251302_OKFAULTMonitor.property.Present_Value
251302_HANDAUTOReference.property.Present_Value
251302_Warning.property.Present_Value
251302_Trip.property.Present_Value
251302_Triplock.property.Present_Value
251302_Coasting.property.Present_Value
251302_CWCCW.property.Present_Value
251302_Jog.property.Present_Value
251302_Reset.property.Present_Value
251302_ResetKWhCounter.property.Present_Value
251302_ResetRunningHoursCounter.property.Present_Value
251302_RevStatus.property.Present_Value
251302_Speed=reference.property.Present_Value
251302_BusControl.property.Present_Value
251302_Running.property.Present_Value
251302_Ramp1Ramp2.property.Present_Value
251302_SmartLogicControllerState.property.Present_Value
251302_ActiveSetup.property.Present_Value
t mentioned in MTS but exist in the scan)
Tag Function Tag to be taken or not
Tag Exist in the scan but not mentioned in the MTS
Duplicated Tag one time as software tag and another as physical interface