Professional Documents
Culture Documents
State of Capacitors in Multiple Feeders For CVR
State of Capacitors in Multiple Feeders For CVR
State of Capacitors in Multiple Feeders For CVR
Test Conditions: Assume that the customer load reduction is proportional to the
Cases with voltage limit violations are unacceptable.
The upper voltage limits at all secondary terminals are 5%, and
The LTC step is 0.625%
Sub-condition 1: The errors of volt/var control execution due to LTC bandwidth, a
See Cases 1 through 5
Sub-condition 2: The error in execution of the volt/var control is ±1% of the nomi
the LTC controller bandwidth, measurement and modeling error
Hence, the upper voltage limits are reduced by 1% (4%), and the
See Cases 6 through 10
The summary results of the cases are presented in the table below. More detailed inform
Questions for
Sub-condition 1 1 Is case 1 acceptable?
A. Yes
B. No
2 Is case 2 acceptable?
A. Yes
B. No
3 What is the best that can be done by the LTC control only, if all capacitors are OFF?
4 What is the best that can be done by the LTC control only, if all capacitors are ON?
5 Can, in this case, a better CVR solution be found with some capacitors being OFF ?
8 Under which CVR-watt factors is Case 5 the most benefitial? (the increase of losses due to
A. 1.0
B. 0.8
C. 0.6
9 Under which CVR-watt factors is Case 5 the most benefitial for the customers?
A. 1.0
B. 0.7
C. 0.5
Questions for 9 Can the voltage violations be eliminated by LTC control only, if all capacitors are OFF?
Sub-condition 2
A. Yes
B. No
10 What is the best that can be done by the LTC control only, if all capacitors are OFF?
12 Under which CVR-watt factors is Case 10 the most benefitial? (the increase of losses due t
A. 1.0
B. 0.7
C. 0.6
13 Under which CVR-watt factors is Case 10 the most benefitial for the customers?
A. 1.0
B. 0.7
C. 0.5
Condition 2
7
10
11
12
an LTC. Each feeder has 10 load nodes and two switched capacitors.
d reduction is proportional to the average secondary voltage (across all feeder and all nodes).
tions are unacceptable.
secondary terminals are 5%, and the lower voltage limits are -5% of the nominal voltages
execution due to LTC bandwidth, as well as, measurement and modeling errors are ignored.
table below. More detailed information can be found in the HELP Sheet
Minimum
Loss increase voltage deviation
Average Maximum due to
voltage voltage capacitors
deviation over violation per OFF, % of total
all nodes<% node, % load
A
B
A
B
A
B
C
A
B
C
A
thin standard limits B
thin standard limits and the load reduction exceeds the increase in losses C
A
B
C
A
B
C
A
B
A
B
C
nly, if all capacitors are ON?
A
B
C
A
B
C
A
B
C
1.002761
1.004143
1.005527
1.006913
LTC boost = 0
Case 1 All capacitors are OFF
Initial secondary voltages deviations from nominal voltage, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -2.70 -0.46 -4.67 -2.22 -3.76 -5.05 -3.32
2 -0.62 -0.48 -2.65 -2.35 -4.66 -5.43 -4.25
3 -4.10 -1.50 -5.33 -3.08 -3.86 -5.68 -3.84
4 -4.20 -2.59 -5.53 -3.68 -4.01 -6.22 -3.98
5 -3.75 -2.10 -4.79 -3.00 -6.05 -6.57 -5.97
6 -5.03 -4.41 -5.88 -5.02 -4.23 -3.75 -4.36
7 -4.50 -5.23 -5.10 -5.50 -6.20 -3.79 -6.23
8 -5.53 -4.89 -6.06 -5.14 -4.40 -3.59 -4.55
9 -4.70 -5.02 -5.15 -5.19 -6.38 -3.56 -6.44
10 -6.02 -5.17 -6.41 -5.27 -4.52 -3.55 -4.75
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -6.0 -5.2 -6.4 -5.5 -6.4 -6.6 -6.4
MaxNodeVo -0.6 -0.5 -2.6 -2.2 -3.8 -3.6 -3.3
Case1a Initial voltage deviations beyond low and high voltage limits, %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.00 0.00 0.00 0.00 0.00 0.05 0.00
2 0.00 0.00 0.00 0.00 0.00 0.43 0.00
3 0.00 0.00 0.33 0.00 0.00 0.68 0.00
4 0.00 0.00 0.53 0.00 0.00 1.22 0.00
5 0.00 0.00 0.00 0.00 1.05 1.57 0.97
6 0.03 0.00 0.88 0.02 0.00 0.00 0.00
7 0.00 0.23 0.10 0.50 1.20 0.00 1.23
8 0.53 0.00 1.06 0.14 0.00 0.00 0.00
9 0.00 0.02 0.15 0.19 1.38 0.00 1.44
10 1.02 0.17 1.41 0.27 0.00 0.00 0.00
Average voltage violation between maximum and minimum violations
Maximum voltage violation between maximum and minimum violations
LTC boost = 0
Case 2 All capacitors are ON
Initial secondary voltage deviation from nominal voltage, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -2.4 -0.1 -4.3 -1.9 -3.4 -4.7 -3.0
2 0.0 0.2 -2.0 -1.7 -4.0 -4.8 -3.6
3 -3.1 -0.5 -4.4 -2.1 -2.9 -4.7 -2.9
4 -2.9 -1.3 -4.2 -2.4 -2.7 -4.9 -2.7
5 -2.1 -0.5 -3.2 -1.4 -4.5 -5.0 -4.4
6 -3.1 -2.5 -4.0 -3.1 -2.3 -1.8 -2.4
7 -2.5 -3.2 -3.1 -3.5 -4.2 -1.8 -4.2
8 -3.4 -2.8 -4.0 -3.1 -2.3 -1.5 -2.5
9 -2.5 -2.8 -3.0 -3.0 -4.2 -1.4 -4.2
10 -3.7 -2.9 -4.1 -3.0 -2.2 -1.3 -2.5
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -3.7 -3.2 -4.4 -3.5 -4.5 -5.0 -4.4
MaxNodeVo 0.0 0.2 -2.0 -1.4 -2.2 -1.3 -2.4
Case2a Initial voltage deviations beyond low and high voltage limits, %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Average voltage violation between maximum and minimum violations
Maximum voltage violation between maximum and minimum violations
LTC_boost 1.875 %
Case 3. All capacitors are OFF
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -0.83 1.42 -2.80 -0.35 -1.89 -3.18 -1.44
2 1.25 1.39 -0.77 -0.47 -2.79 -3.56 -2.37
3 -2.23 0.38 -3.46 -1.21 -1.99 -3.80 -1.97
4 -2.33 -0.71 -3.66 -1.80 -2.14 -4.34 -2.11
5 -1.87 -0.23 -2.92 -1.12 -4.17 -4.69 -4.09
6 -3.15 -2.54 -4.01 -3.14 -2.36 -1.87 -2.48
7 -2.62 -3.35 -3.22 -3.63 -4.33 -1.91 -4.35
8 -3.66 -3.01 -4.18 -3.26 -2.53 -1.72 -2.68
9 -2.83 -3.14 -3.28 -3.32 -4.50 -1.69 -4.56
10 -4.14 -3.29 -4.53 -3.39 -2.64 -1.68 -2.87
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -4.1 -3.4 -4.5 -3.6 -4.5 -4.7 -4.6
MaxNodeVo 1.3 1.4 -0.8 -0.3 -1.9 -1.7 -1.4
Case3a Initial voltage deviations beyond low and high voltage limits, %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Average voltage violation between maximum and minimum violations
Maximum voltage violation between maximum and minimum violations
LTC_boost 0%
Case 4. All capacitors are ON
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -2.4 -0.1 -4.3 -1.9 -3.4 -4.7 -3.0
2 0.0 0.2 -2.0 -1.7 -4.0 -4.8 -3.6
3 -3.1 -0.5 -4.4 -2.1 -2.9 -4.7 -2.9
4 -2.9 -1.3 -4.2 -2.4 -2.7 -4.9 -2.7
5 -2.1 -0.5 -3.2 -1.4 -4.5 -5.0 -4.4
6 -3.1 -2.5 -4.0 -3.1 -2.3 -1.8 -2.4
7 -2.5 -3.2 -3.1 -3.5 -4.2 -1.8 -4.2
8 -3.4 -2.8 -4.0 -3.1 -2.3 -1.5 -2.5
9 -2.5 -2.8 -3.0 -3.0 -4.2 -1.4 -4.2
10 -3.7 -2.9 -4.1 -3.0 -2.2 -1.3 -2.5
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -3.7 -3.2 -4.4 -3.5 -4.5 -5.0 -4.4
MaxNodeVo 0.04 0.17 -2.0 -1.4 -2.2 -1.3 -2.4
Case4a Initial voltage deviations beyond low and high voltage limits, %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Average voltage violation between maximum and minimum violations
Maximum voltage violation between maximum and minimum violations
Case 5 Some capacitors are OFF
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -2.6 -0.3 -4.3 -2.1 -3.4 -4.7 -3.0
2 -0.4 -0.2 -2.0 -2.1 -4.0 -4.8 -3.6
3 -3.8 -1.2 -4.4 -2.7 -2.9 -4.7 -2.9
4 -3.8 -2.1 -4.2 -3.2 -2.7 -4.9 -2.7
5 -3.2 -1.6 -3.2 -2.5 -4.5 -5.0 -4.4
6 -4.4 -3.8 -4.0 -4.4 -2.3 -1.8 -2.4
7 -3.8 -4.5 -3.1 -4.8 -4.2 -1.8 -4.2
8 -4.7 -4.1 -4.0 -4.3 -2.3 -1.5 -2.5
9 -3.8 -4.1 -3.0 -4.3 -4.2 -1.4 -4.2
10 -5.0 -4.2 -4.1 -4.3 -2.2 -1.3 -2.5
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -5.0 -4.5 -4.4 -4.8 -4.5 -5.0 -4.4
MaxNodeVo -0.4 -0.2 -2.0 -2.1 -2.2 -1.3 -2.4
CX1 OFF OFF ON OFF ON ON ON
CX2 ON ON ON ON ON ON OFF
Loss
increase,
% of load 0.07 0.07 0.07 0.04
Voltage deviations from voltage limits, %. Positive numbers mean violation of upper
Case5a limits, and negative numbers mean violations of lower limits)
Negative numbers mean voltage violations.
Feeder #
Node #
1 2 3 4 5 6 7
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10 0.02 0.00 0.00 0.00 0.00 0.00 0.00
Average voltage deviation across secondary terminals of all feeders
Initial voltage deviations beyond low and high voltage limits with correction for
Case6 uncertainty , %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.0 0.0 0.0 0.0 0.0 0.1 0.0
2 0.0 0.0 0.0 0.0 0.0 0.4 0.0
3 0.0 0.0 0.3 0.0 0.0 0.7 0.0
4 0.0 0.0 0.5 0.0 0.0 1.2 0.0
5 0.0 0.0 0.0 0.0 1.0 1.6 1.0
6 0.0 0.0 0.9 0.0 0.0 0.0 0.0
7 0.0 0.2 0.1 0.5 1.2 0.0 1.2
8 0.5 0.0 1.1 0.1 0.0 0.0 0.0
9 0.0 0.0 0.2 0.2 1.4 0.0 1.4
10 1.0 0.2 1.4 0.3 0.0 0.0 0.0
Average voltage violation between maximum and minimum violations
Maximum voltage violation between maximum and minimum violations
Error 0.0
Initial voltage deviations beyond low and high voltage limits with correction for
Case7 uncertainty , %.
Absolute values
Feeder #
Node #
1 2 3 4 5 6 7
1 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2 0.0 0.0 0.0 0.0 0.0 0.0 0.0
3 0.0 0.0 0.0 0.0 0.0 0.0 0.0
4 0.0 0.0 0.0 0.0 0.0 0.0 0.0
5 0.0 0.0 0.0 0.0 0.0 0.0 0.0
6 0.0 0.0 0.0 0.0 0.0 0.0 0.0
7 0.0 0.0 0.0 0.0 0.0 0.0 0.0
8 0.0 0.0 0.0 0.0 0.0 0.0 0.0
9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Average voltage violation between maximum and minimum violations
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
Error 0.0
LTC_boost 3.125
Case 8 All capacitors are OFF
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 0.42 2.67 -1.55 0.90 -0.64 -1.93 -0.19
2 2.50 2.64 0.48 0.78 -1.54 -2.31 -1.12
3 -0.98 1.63 -2.21 0.04 -0.74 -2.55 -0.72
4 -1.08 0.54 -2.41 -0.55 -0.89 -3.09 -0.86
5 -0.62 1.02 -1.67 0.13 -2.92 -3.44 -2.84
6 -1.90 -1.29 -2.76 -1.89 -1.11 -0.62 -1.23
7 -1.37 -2.10 -1.97 -2.38 -3.08 -0.66 -3.10
8 -2.41 -1.76 -2.93 -2.01 -1.28 -0.47 -1.43
9 -1.58 -1.89 -2.03 -2.07 -3.25 -0.44 -3.31
10 -2.89 -2.04 -3.28 -2.14 -1.39 -0.43 -1.62
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
Voltage deviations from voltage limits, %. Positive numbers mean violation of upper
Case 8a limits, and negative numbers mean violations of lower limits)
Negative numbers mean voltage violations.
Feeder #
Node #
1 2 3 4 5 6 7
1 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2 0.0 0.0 0.0 0.0 0.0 0.0 0.0
3 0.0 0.0 0.0 0.0 0.0 0.0 0.0
4 0.0 0.0 0.0 0.0 0.0 0.0 0.0
5 0.0 0.0 0.0 0.0 0.0 0.0 0.0
6 0.0 0.0 0.0 0.0 0.0 0.0 0.0
7 0.0 0.0 0.0 0.0 0.0 0.0 0.0
8 0.0 0.0 0.0 0.0 0.0 0.0 0.0
9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Average voltage violation between maximum and minimum violations
Error 0.0
LTC_boost 1.25 %
Case9 All capacitors are ON
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -1.1 1.1 -3.1 -0.6 -2.2 -3.5 -1.7
2 1.3 1.4 -0.7 -0.4 -2.8 -3.5 -2.3
3 -1.9 0.7 -3.1 -0.9 -1.6 -3.5 -1.6
4 -1.7 0.0 -3.0 -1.1 -1.5 -3.7 -1.4
5 -0.9 0.7 -1.9 -0.1 -3.2 -3.7 -3.1
6 -1.9 -1.2 -2.7 -1.9 -1.1 -0.6 -1.2
7 -1.3 -2.0 -1.9 -2.3 -3.0 -0.6 -3.0
8 -2.2 -1.6 -2.7 -1.8 -1.1 -0.3 -1.2
9 -1.3 -1.6 -1.7 -1.8 -2.9 -0.1 -3.0
10 -2.5 -1.6 -2.9 -1.7 -1.0 0.0 -1.2
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
Voltage deviations from voltage limits, %. Positive numbers mean violation of upper
Case9a limits, and negative numbers mean violations of lower limits)
Negative numbers mean voltage violations.
Feeder #
Node #
1 2 3 4 5 6 7
1 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Average voltage deviation across secondary terminals of all feeders
LTC_boost 1.5
Case 10 Some capacitors are OFF
Voltages deviations from nominal voltage after LTC boost, %
Feeder #
Node #
1 2 3 4 5 6 7
1 -1.1 0.9 -2.8 -0.6 -2.2 -3.2 -1.5
2 1.1 0.9 -0.8 -0.6 -2.8 -3.3 -2.1
3 -2.3 -0.1 -3.3 -1.2 -1.8 -3.2 -1.4
4 -2.3 -1.2 -3.3 -1.7 -1.8 -3.4 -1.2
5 -1.7 -0.7 -2.3 -1.0 -3.6 -3.5 -2.9
6 -2.9 -3.0 -3.2 -2.9 -1.5 -0.3 -0.9
7 -2.3 -3.8 -2.4 -3.3 -3.5 -0.3 -2.7
9 -3.2 -3.5 -3.4 -2.8 -1.7 0.0 -1.0
10 -2.3 -3.6 -2.5 -2.8 -3.7 0.1 -2.7
Average voltage deviation across secondary terminals of all feeders
Minimum voltage deviation across secondary terminals of all feeders
Maximum voltage deviation across secondary terminals of all feeders
MinNodeVo -3.2 -3.8 -3.4 -3.3 -3.7 -3.5 -2.9
MaxNodeVo 1.1 0.9 -0.8 -0.6 -1.5 0.1 -0.9
CX1 OFF OFF ON OFF ON ON ON
CX2 ON OFF OFF ON OFF ON OFF
Loss
increase,
% of load 0.04 0.10 0.04 0.07 0.04 0.04
Voltage deviations from voltage limits, %. Positive numbers mean violation of upper
Case 10a limits, and negative numbers mean violations of lower limits)
Negative numbers mean voltage violations.
Feeder #
Node #
1 2 3 4 5 6 7
1 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2 0.0 0.0 0.0 0.0 0.0 0.0 0.0
3 0.0 0.0 0.0 0.0 0.0 0.0 0.0
4 0.0 0.0 0.0 0.0 0.0 0.0 0.0
5 0.0 0.0 0.0 0.0 0.0 0.0 0.0
6 0.0 0.0 0.0 0.0 0.0 0.0 0.0
7 0.0 0.0 0.0 0.0 0.0 0.0 0.0
8 0.0 0.0 0.0 0.0 0.0 0.0 0.0
9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Average voltage deviation across secondary terminals of all feeders
Table A
Contribution of voltage by Benefit =
voltage, % CXs by nodes, %
Cx1 Cx2 -0.43
8 0.2 0.1 -0.3448
-4.24 0.4 0.2 -0.2586
-4.66 0.6 0.3
-4.85 0.9 0.4 -0.47
-5.14 1.1 0.5 -0.37861
-5.80 1.3 0.6 -0.28396
-3.11 1.3 0.7
-3.25 1.3 0.8 -0.47
-3.04 1.3 0.9 -0.33129
-3.02 1.3 1.0 -0.23663
-3.02 Average contribution of
-4.35 voltage by Cxs per feeder, %
-6.57 CX1 CX2
-0.46 0.96 0.57
-5.8 Loss reduction by Cxs per
-3.0 feeder, % of total load
0.065 0.035
ge limits, %.
8
0.00
0.00
0.00
0.14
0.80
0.00
0.00
0.00
0.00
0.00
0.25
1.57
oltage, %
8
-3.9
-4.0
-3.9
-3.8
-4.2
-1.2
-1.3
-1.0
-0.8
-0.7
-2.82
-4.97
0.17
-4.2
-0.7
ge limits, %.
8
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
st, %
8
-2.37
-2.78
-2.97
-3.26
-3.93
-1.23
-1.37
-1.16
-1.15
-1.15
-2.48
-4.69
1.42
-3.9
-1.1
ge limits, %.
8
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
st, %
8
-3.9
-4.0
-3.9
-3.8
-4.2
-1.2
-1.3
-1.0
-0.8
-0.7
-2.82
-4.97
0.17
-4.2
-0.7
ge limits, %.
8
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.000
0.00
st, %
8
-4.0
-4.2
-4.2
-4.3
-4.7
-1.8 savings due to Cxs 0.43
Total loss increase 0.27
-2.0
-1.8
-1.7
-1.7
-3.3
-5.0
-0.2
-4.7
-1.7
ON
OFF
0.04
8
0.0
0.0
0.0
0.1
0.8
0.0
0.0
0.0
0.0
0.0
0.78
1.57
8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.00
0.00
0.00
st, %
8
-1.12
-1.53
-1.72
-2.01
-2.68
0.02
-0.12
0.09
0.10
0.10
-1.23
-3.44
2.67
8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.00
st, %
8
-2.6
-2.8
-2.6
-2.6
-3.0
0.1
0.0
0.3
0.4
0.5
-1.57
-3.72
1.42
8
0.0
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.0
st, %
8
-2.7
-3.0
-3.1
-3.3
-3.9
-0.9
-1.0
-0.6
-0.5
-2.04
-3.88
1.12
-3.9
-0.5
OFF
ON
0.07 0.37
8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.00
-0.43
0.3 -0.13
0.3 -0.04
0.301658 0.04
0.37 -0.10
0.37 -0.01
0.37 0.09
0.185 -0.29
0.185 -0.15
0.185 -0.05