FireMaster® FireBarrier™ 135

Datasheet Code 7-9-04 E MSDS Code 102-13-EURO


© 2009 Morgan Thermal Ceramics, a business within the Morgan Ceramics Division of The Morgan Crucible Company plc

DESCRIPTION FEATURES
®
FireMaster FireBarrier™ products are cementitious materials  2 versions available: one for sprayed application
designed for a variety of fire protection applications requiring and one for cast application
strong and weather resistant exterior finishes.  Very low spraying wastage during installation – less than
1% of weight
FireBarrier™ 135 is available in two different dry powder versions  Fast and easy to install - one, single layer
used for either spayed or cast application. The dry powder is application
mixed with water, either in a spray machine for sprayed
 High adhesion strength - eight times greater than
application, or directly when cast into shapes. The cast version
product weight
allows linings to be pre-formed when spray application is not
convenient or practical.  High quality surface finish that can be painted

 FireBarrier 135 (*Patent No. 98830682.5)


Consisting of a unique formulation of Morgan Thermal Ceramics
®
refractory technology. FireMaster FireBarrier™ when mixed
with water can be applied by spray equipment to a variety of  Refractory product capable of repeated exposure to
substrates. 1350°C
Comprehensively fire tested in over 11 fire tests for
®
FireMaster FireBarrier™ 135 is suitable for cellulosic and fire protection of tunnels
hydrocarbon fires and has been fire tested in high-rise EU MED approved A60 steel floating floor system
hydrocarbon fires of up to 1350°C.
APPLICATIONS
®
FireMaster FireBarrier™135 has been successfully fire tested to • Tunnel fire protection (concrete linings, escape
IMO A 754(18), ISO 834, Hydrocarbon modified (HCM) and RWS refuges, ventilation shafts)
fire curves. • A60 floating floors in ships
• Structural steel fire protection

www.morganthermalceramics.com
05 :2012 Page 1 of 3
FireMaster® FireBarrier™ 135
MAIN PROPERTIES
General Properties
Standard Cast

 Temperature limit °C 1350 1350

 Weight of dry material/m required of


3
kg 1050 1210
construction
3
 Installed density kg/m 1550 -
3
 Long term density kg/m 1180 1235
3
 Dry density kg/m 1100 1065

 Cold crushing strength ASTM C-133 (after 3 days curing) MPa 3.0 5.4
ASTM C-133

(after 28 days curing) MPa 9.0 8.8

(after 3 days curing + drying) MPa 4.0 4.2

Water to mix % 50 38-40

Fire Protection Properties


• Class A1 Reaction to Fire in accordance with EN 13501-1 : 2002 CSI Registration No. 0202/04
• Non combustible material According to IMO RES. A.799 (19) MED B 520509CS
IMO RES. MSC61 (67)-FTP code, IMO MSC/Circ.1120

The values given herein are typical values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
They are supplied as a technical service and are subject to change without notice. Therefore, the data contained herein should not be used for specification purposes.
Check with your Thermal Ceramics office to obtain current information.

www.morganthermalceramics.com
05 :2012 Page 2 of 3
FireMaster® FireBarrier™ 135

Physical Properties - FireBarrier 135


• Adhesion strength ASTM E-736/06 (On steel surface) KPa >49.5
(On concrete surface) KPa >45.1
• Tensile strength SN-EN 1542 (After 7 days) MPa 0.7
(After 28 days) MPa 1.1
• Modulus of elasticity (After setting) MPa 4.05
(After 28 days) MPa 4.05
High Temperature Performances
• Thermal conductivity (ISO 8302 : 1991) at 50°C W/m.K 0.267
mean temperature of:
200°C W/m.K 0.194
500°C W/m.K 0.169
Specific Heat (EN 821-2) at 50°C j/kg.K 704
at 100°C j/kg.K 806
at 500°C j/kg.K 678
Chemical Composition SiO2 % 28.2
AI2O3 % 43.5
CaO Total % 24.4
Fe2O3 % 1.5
TiO2 % 0.8
MgO + K2O + Na2O3 % 1.6

Availability and Packaging


In bags of 25kg weight supplied to site and ready to mix with water. Also available in large 1000kg bags supplied shrink-
wrapped on pallets. Pallet dimensions 1390mm x 1090mm x 1000mm. Gross weight of pallet 1030kg.

The values given herein are typical values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
They are supplied as a technical service and are subject to change without notice. Therefore, the data contained herein should not be used for specification purposes.
Check with your Thermal Ceramics office to obtain current information.

www.morganthermalceramics.com
05 :2012 Page 3 of 3