CHGT

CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

Range of adjustable pitch aerofoil blade, axial flow cabinet fans designed for smoke extraction in fire conditions and certified F400 (CE
marked). Fan casing manufactured from heavy gauge galvanised sheet steel internally lined with 25mm thickness fireproof fibreglass acoustic
insulation (M0). All models incorporate separate high grade diecast aluminium blades locked within a pressed sheet steel hub F400(CE marked)
motors are IP55 class H insulation. Brand S&P model CHGT/4-450-6/38-0.55kW-F400-3-230/400V-50Hz-50Hz-IE2 for an airflow 5,900 m³/h and
static pressure 116 Pa.

Theoretical Working Point Performance Chart


Airflow 6,000 m³/h
Output Power Static Pressure Efficiency
Static Pressure 120 Pa
System Curve
Temperature 20 °C
180 0.6 100
Altitude 0m
Density 1.2 kg/m³ 90
160
Frequency 50 Hz
0.5
Voltage 3-230/400V-50Hz 80
140
Working Point
70
Airflow 5,900 m³/h 120 0.4

Total Efficiency (%)


Static Pressure (Pa)
Static Pressure 116 Pa
60

Output Power
Dynamic pressure 64 Pa 100
Total Pressure 180 Pa 0.3 50
Shaft power 0.501 kW 80
Tot efficiency 58.9 % 40
Outlet speed 10.3 m/s 60 0.2
Fan speed 1436 rpm 30
Specific Fan Power 0.40 W/l/s 40
Max shaft power 0.503 kW 20
0.1
Construction 20 10
Diameter 450 mm
Blades 6 0 0.0 0
Weight 58.50 kg 0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Angle 38° Q- Airflow (m³/h)
Certification F400
Motor Characteristics
Number of poles 4 Sound Performance
Motor Power 0.55 kW
Voltage 3-230/400V-50Hz 63 125 250 500 1k 2k 4k 8k Overall
FLC 2.2 A / 1.3 A Inlet (LwA) 46 58 65 71 72 71 66 58 77
IP Rating IP55 Inlet LpA @ 1.5m 31 43 50 56 57 56 51 43 62
Motor insulation class H
Motor Certification F400
Motor Efficiency IE2
Drawing

A B C D E F

567,6 473 483 40 563 317

1/4/2017, 5:00:30 AM Page 1 of 6


CHGT
CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

Performance Chart

Output Power Static Pressure Efficiency System Curve


180 0.6 100

160 90
0.5
80
140

70
120 0.4

Total Efficiency (%)


Static Pressure (Pa)

60

Output Power
100
0.3 50
80
40
60 0.2
30
40
20
0.1
20 10

0 0.0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Q- Airflow (m³/h)

200

150
Static Pressure (Pa)

100

50

10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32° 34° 36° 38°
0
0.6
0.5
Output Power

0.4
0.3
0.2
0.1
0.0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Q- Airflow (m³/h)

1/4/2017, 5:00:30 AM Page 2 of 6


CHGT
CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

Drawing

A B C D E F
567,6 473 483 40 563 317

1/4/2017, 5:00:30 AM Page 3 of 6


CHGT
CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

Accessories
5402052200 - ACOP RECT CHGT/CGT 450 F400 474 x 474
Rectangular flexible connector.

A B C
474 474 130

5137131700 - CVD/450 CGT/CHGT


Wire protection guards for mounting on the inlet or discharge sides
of the cabinets.

□A B C
474 341.5 70

1/4/2017, 5:00:30 AM Page 4 of 6


CHGT
CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

Sound Performance
63 125 250 500 1k 2k 4k 8k Overall
Inlet (LwA) 46 58 65 71 72 71 66 58 77
Inlet LpA @ 1.5m 31 43 50 56 57 56 51 43 62

1/4/2017, 5:00:30 AM Page 5 of 6


CHGT
CHGT/4-450-6/38-0.55KW-F400-3-230/400V-50HZ-50HZ-IE2

ErP Data Warnings


Motor absorbed current may vary slightly depending on motor installed
ᶯ[%] MC EC N VSD Manufacturer REF

33.4 C Static N40.9 + S&P PV031783T38

[kW] [m3/h] [Pa] Speed SR

0.645 4,990 156 1437 1

ᶯ[%] Maximum efficiency ᶯ[%]

MC Instalation type

EC Category efficiency

N N

VSD Variable speed drive

Manufacturer Manufacturer

REF Product code

[kW] Input power at optimum efficiency point (kW)

[m3/h] Airflow at optimum efficiency point [m3/h]

[Pa] Pressure at optimum efficiency point [Pa]

Speed Speed at optimum efficiency point

SR Specific Ratio

1/4/2017, 5:00:30 AM Page 6 of 6