The document contains the results of ratio and insulation resistance tests on spare VT (GAB South-Spitskop line). The ratio test shows the measured voltages (VS1 and VS2) at different test voltages (VP) compared to the theoretical voltages. The percentage error between the measured and theoretical voltages is also provided. The insulation resistance test lists the resistance readings after 30 seconds and 60 seconds for different phases and terminals, as well as the dielectric absorption ratios.
The document contains the results of ratio and insulation resistance tests on spare VT (GAB South-Spitskop line). The ratio test shows the measured voltages (VS1 and VS2) at different test voltages (VP) compared to the theoretical voltages. The percentage error between the measured and theoretical voltages is also provided. The insulation resistance test lists the resistance readings after 30 seconds and 60 seconds for different phases and terminals, as well as the dielectric absorption ratios.
The document contains the results of ratio and insulation resistance tests on spare VT (GAB South-Spitskop line). The ratio test shows the measured voltages (VS1 and VS2) at different test voltages (VP) compared to the theoretical voltages. The percentage error between the measured and theoretical voltages is also provided. The insulation resistance test lists the resistance readings after 30 seconds and 60 seconds for different phases and terminals, as well as the dielectric absorption ratios.