ANNEXURE-2

Local Station- UPS

Sr.No Equipment Description Power Req No of Unit Actual


Consumption
1 HMI PC 300 3 900
2 Disturbance Recorder 100 1 100
3 Ethernet Switches 40 6 240
4 TFT Monitors 60 3 180
5 Laser Color Printer 190 2 380
6 GPS Time Sync Equipment 15 1 15
7 Gateway 15 2 30
TOTAL 1845 W

Power Factor = 0.8

KVA Requirement = 2.30625 kVA

Considering 85% Efficiency


And avg. diversity factor = 1273.05 W
Of 0.6 of UPS

Hence, Load on battery(W) = 1280 W