Low-Loss Header
Please file in Service Binder
Working on the equipment Ensure main power supply to Ensure that the installation
The installation, adjustment, service, equipment, the heating system, and all literature of other applicable
and maintenance of this product must external controls has been deactivated. components of the Vitodens
be done by a licensed professional Close main gas supply valve. Take 200 boiler is referenced.
heating contractor who is qualified and precautions in all instances to avoid
experienced in the installation, service, accidental activation of power during
and maintenance of hot water boilers. service work.
There are no user serviceable parts on
the boiler, burner, or control.
Product Information
When used in conjunction with Viessmann boilers, the low-loss header acts as
hydraulic break, decoupling boiler and system circuits from each other. The
low-loss header increases operational efficiency. In addition, the low-loss header
helps eliminate debris from the heating system.
The common supply temperature sensor located of the low-loss header connects
to the Vitocontrol-S controller ensuring optimum staging of the boilers and
accurate control of system supply water temperatures.
Please refer to the respective section for installation steps of your low-loss header.
120 V, 60 Hz, 1 PH
120 V, 60 Hz, 1 PH
120 V, 60 Hz, 1 PH
120 V, 60 Hz,
1 PH
Boiler 1* Boiler 2 Boiler 3 Boiler 4 Vitocontrol-S
WB2A
Viessmann 2-wire
4
3
2
1
Boiler
BUS
Boiler
Boiler
Boiler
KM-BUS
KM-BUS
KM-BUS
KM-BUS
20-A
20-A
20-A
20-A
21
HK1
System
Common supply pump
M
temperature sensor
21
DHW tank Low-loss
header
module.
2
System Layout (Vitodens 200, WB2B boilers)
Vitocontrol-S
WB2B
Common
Supply
Temperature
Sensor M M
DHW Tank
Low-Loss
Header
Legend
Vitodens 200, WB2B boiler Expansion tank
(maximum of 4 boilers) Fill line system
Power / pump module
(120 V / 60 Hz)
Boiler pump (field supplied)
(120 V, 8 A max.)
DHW circulating pump (field
supplied)
IMPORTANT WARNING
This installation example depicts a If a DHW storage tank other than a
possible piping layout for multiple Viessmann Vitocell 100 or 300 tank
is used, the installer must verify
Vitodens 200-W, WB2B boilers
proper operation of the Viessmann
equipped with Viessmann System
DHW tank temperature sensor with
Technology. Please note that this
the original manufacturer of the tank.
example is based on a simplified
Viessmann strongly recommends the
conceptual drawing only! installation of a temperature
Piping and necessary componentry tempering valve in the DHW supply
must be field verified. line.
A low water cut-off (LWCO) must be
installed where required by local codes.
5458 697 v1.0
3
4
Vitocontrol-S
MW1
High mass
radiant floor
Sensor
Main supply
PRV PRV
P
Main return
S
Floor-mounted
Low Loss Header
contractor.
field is the responsibility of the heating
Proper installation and functionality in the
installed where required by local codes.
A low water cut-off (LWCO) must be
be field verified.
Piping and necessary componentry must
conceptual drawings only!
the following examples are simplified
a possible piping layout. Please note that
The following installation example depicts
Vitotronic 100 GC1 Outdoor temperature sensor
IMPORTANT
Boiler pump (field supplied) Common supply temperature
DHW circulating pump (field supplied) sensor (strap-on) supplied with
System heating pump (field supplied) boiler control
Low-loss header (floor-mounted) Optional immersion sensor
with optional insulation jacket location (order separately
DHW storage tank PN 7450641)
Expansion tank Drain connection
Fill line system P Air vent
A C
X1 X2
X1 X2
B D
Front View
Side View
Legend
Boiler supply
Boiler return
System supply
System return
Drain / clean-out opening
Anchor bolt holes
Top View
5
Technical Specifications (continued)
6
Installation Steps
Legend
Air vent
Common supply temperature
sensor well (immersion sensor) *
Common supply temperature sensor
(strap-on sensor) *
Low-loss header
Flange of low-loss header, ANSI
standard
Drain connection, 2” NPT male
Low-loss header label
Note:
All counter flanges shall be ANSI
standard (field supplied).
5458 697 v1.0
7
Electrical Connection - Vitocontrol-S (WB2A)
WARNING
When extending wire, there is the
possibility of exposure to
electromagnetic interference. Avoid
running wires beside or near high
voltage 120/240 VAC conductors.
If proximity to high voltage
conductors cannot be avoided, use
stranded, twisted pair or shield
design wire. Ensure that only one
end of the shielding is grounded.
See Vitocontrol-S
Installation, Start-up/Service
Instructions
5458 697 v1.0
8
Electrical Connection (WB2B boilers only)
For multiboiler applications refer
IMPORTANT to Vitocontrol-S, WB2B
Installation and Service
The following applies only to Vitodens Instructions.
200, WB2B Series boilers in
single-boiler applications with Vitotronic
200, HO1 controls.
X3
2.
Fig. 2
1.
7 6 5 4 3 2 1
X3
5458 697 v1.0
Fig. 3
9
Electrical Connection (Vitocontrol-S WB2B)
2.
3.
1.
X7
B 145
3 2 1
C C
Vitotronic 100
10
Electrical Connection
*
*Immersion or strap-on sensor depending
on application and boiler/control models.
5458 697 v1.0
11
Technical Data
*1 Low-loss header temperature sensor - standard equipment of Vitocontrol-S; for use in multiple-boiler applications
*2 For system ∆t < 20 °F use low-loss header sizes for ∆t 20 °F
" Low-loss header must be used in all applications where the system flow rate exceeds the maximum or minimum boiler flow rate.
5458 697 v1.0
12
Technical Data (continued)
WB2B 60 2 15.4 30.8 System Flow Rate 38.8 31.0 25.9 22.2 19.4 GPM Yes *1
3498 6995 8812 7050 5875 5036 4406 L/h
LLH required yes yes yes yes yes
LLH Model 160/80 120/80 120/80 120/80 120/80
WB2B 60 3 15.4 46.2 System Flow Rate 58.2 46.6 38.8 33.3 29.1 GPM Yes *1
3498 10493 13219 10575 8812 7554 6609 L/h
LLH required yes yes yes yes yes
LLH Model 200/120 200/120 160/80 120/80 120/80
WB2B 60 4 15.4 61.6 System Flow Rate 77.6 62.1 51.7 44.3 38.8 GPM Yes *1
3498 13991 17625 14100 11750 10071 8812 L/h
LLH required yes yes yes yes yes
LLH Model 200/120 200/120 200/120 160/80 160/80
WB2B 80 2 35 70 System Flow Rate 52.0 41.6 34.7 29.7 26.0 GPM Yes *1
7949 15899 11810 9448 7874 6749 5905 L/h
LLH required yes yes yes yes yes
LLH Model 200/120 160/80 160/80 160/80 160/80
WB2B 80 3 35 105 System Flow Rate 78.0 62.4 52.0 44.6 39.0 GPM Yes *1
7949 23848 17716 14173 11810 10123 8858 L/h
LLH required yes yes yes yes yes
LLH Model 200/120 200/120 200/120 200/120 160/80
WB2B 80 4 35 140 System Flow Rate 104.0 83.2 69.3 59.4 52.0 GPM Yes *1
7949 31797 23621 18897 15747 13498 11810 L/h
LLH required yes yes yes yes yes
LLH Model 250/150 250/150 200/120 200/120 200/120
WB2B 105 2 35 70 System Flow Rate 70.0 56.0 47.0 40.0 35.0 GPM Yes *1
7949 15899 15899 12719 10599 9085 7949 L/h
LLH required yes yes yes yes yes
LLH Model 200/120 200/120 200/120 160/80 160/80
WB2B 105 3 35 105 System Flow Rate 105.0 84.0 70.0 60.0 53.0 GPM Yes *1
7949 23848 23848 19078 15899 13627 11924 L/h
LLH required yes yes yes yes yes
LLH Model 250/150 250/150 200/120 200/120 200/120
WB2B 105 4 35 140 System Flow Rate 140.0 112.0 93.0 80.0 70.0 GPM Yes *1
7949 31797 31797 25438 21198 18170 15899 L/h
LLH required yes yes yes yes yes
LLH Model 300/200 250/150 250/150 200/120 200/120
*1 Low-loss header temperature sensor - standard equipment of Vitocontrol-S, WB2B; for use in multiple-boiler applications
5458 697 v1.0
" Low-loss header must be used in all applications where the system flow rate exceeds the maximum or minimum boiler flow rate.
13
14
16