Professional Documents
Culture Documents
MSB SLD
MSB SLD
1
Use 1 x 1C x AWG #1/0 Earth cable
MCC -1
! " !
! " !
600V
MCCB
300AF/,
4 x 1C x 350 MCM, Copper, non-armoured
!
!
300AT, 3P
THHN Cable in 2-1/2-inch RSC
2
Use 1 x 1C x AWG #3/0 Earth cable
MCC -2
!
Diagram for detail
!
Max DL : 161.5 kVA
SF & MMF FEED PUMPS
!
600V
MCCB
500AF/ ,
4 x 1C x 600 MCM, Copper, non-armoured
500AT, 3P
THHN Cable in 3-inch RSC
3
MCC -3
#
Diagram for detail
SeaWater/Desal Pumps
!
600V
MCCB
MCC- 4
Use 1 x 1C x AWG #1/0 Earth cable
$
(Fact ory-Supplied)
!!
600V
MCCB
#
MCC- 5
"
600V
600V
%
2500A, 4P
1
F
600V
600 V
MCCB
60 0V
MCCB
(50HP)
SPARE 1
60 0V
MCCB
100AF/ ,
75AT, 3 P
13
(50HP)
SPARE 2
60 0V
MCCB
100AF/ ,
75AT, 3 P
14
(50HP)
SPARE 3