7SA522 Relay Calculations

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Designed by MSETCL EHV testing Dn.

Panvel

220000 V Ghatghar BOISAR


18.45 km
6.3 km TARAPUR

CTR = 400 / 1 400 VAPI


PTR = 66000 / 110 600 14.32 km

Protected Line parameters: Conductor size = 0.4 ACSR

Z1 = 0.191 + j 0.3810 = 0.42619 63.37483


Z0 = 0.3400 + j 1.2510 = 1.29638 74.79527

Z0/Z1 = = 3.04175 11.42045

Zone 1 reach = 80 % of protected line


Zone 2 reach = 50 % of adjacent shortest line
Zone 3 reach = 50 % of adjacent longest line

Ratio of Secondary to Primary Impedance =CTR/PTR = 0.67

General Line Data :

Address 1105 = Line Angle


= tan-1(XL/RL)
= 63.37 = Address 1211 = Angle of inclination of Distance Chara.

Address 1110 = per unit length reactance

= (CTR/PTR) x XL
= 0.2540