CIRCUIT
LOAD DESCRIPTION QTY. WATTS VOLTS AMPS
TOTAL CKT SIZE OF WIRE AND CONDUIT ALL ELECTRICAL WORKS AND INSTALLATIONS TO BE UNDERTAKEN HEREIN SERVICE ENTRANCE M KILOWATT METER
NO. AMPS SHALL CONFORM WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL
BREAKER
CODE, NATIONAL ELECTRICAL CODE, RULES AND REGULATIONS OF THE ENFORCING PANEL BOARD GROUND
3 6.52 A 15 A USE 2.0 mm² WIRE AT 15mm Ø CONDUIT AUTHORITY AND THE LOCAL POWER UTILITY COMPANY.
LIGHTING OUTLET(L.O.) 15 1500 W 230 6.52 A CIRCUIT HOME RUN S (1,2,3) SWITCH (NUMERIC DENOTES GANG)
NE
A. RIGID METALLIC PIPE (RMP) FOR SERVICE
NW
ENTRANCE.
W E
B . PVC PIPE SCHEDULE 40 FOR BRANCH CIRCUITS.
CIRCUIT QTY. TOTAL CKT SIZE OF WIRE AND CONDUIT
NO. LOAD DESCRIPTION WATTS VOLTS AMPS AMPS
SE
SW
BREAKER
ALL WIRING INSTALLATIONS TO BE UNDERTAKEN HEREIN SHALL BE UNDER THE
2 16 A 30 A USE 3.5 mm² WIRE AT 15mm Ø CONDUIT DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER. S
ET
ACU UNIT OUTLETS (ACU) 1HP
STRE
2 3680 W 230 16 A
NDO
CONVENIENCE OUTLET (C.O.) 4 800 W 230 3.48 A
SEGU
4 3.48 A 20 A USE 3.5 mm² WIRE AT 15mm Ø CONDUIT
5 MATA
LAM
STRE
ET
SPARE
ET
STRE
TOTAL CONNECTED LOAD 41 8380 W 230 36.44 A 60 A
NDO
SEGU
SINGLE LINE DIAGRAM
RISER DIAGRAM
LOAD COMPUTATION
MERC
URY
DRUG
TOTAL CONNECTED LOAD = [ (PB1)18.7A + (PB2) 36.44A ] X 100% D.F. TO C STOR NEMO
OTAB E HARD
WARE
A TO C
NET COMPUTED LOAD = 57.64 A ITY
THEREFORE:
USE 14.0 mm² WIRE AT 25mm Ø RSC PIPE