Perhitungan Lossess Dan Drop Voltage
Perhitungan Lossess Dan Drop Voltage
data pembangkit
tegangan (V) 22000
daya semu (Va) 15000000
cos phi 0.85ASUMSI
sin phi 0.5
frekuensi (Hz) 50
Drop tegangan (%∆U) 0.04
L (H/km) Xl
0.000289 0.090746
0.000299 0.093886
3. Cable Impedance
4. Drop Voltage
Diameter(mm2) ∆U %∆U
240 411.21609471 1.8691641
630 598.97826116 2.7226285
5. Losses Saluran
Kapasitas
Diamater (mm2) Losses Satuan Saluran
630 192114.20777Wat 15 MW
240 58005.497514Wat 5 MW
Rac(ohm/km)
0.144075
0.0530196