Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

The Effects of Harmonics on Differential Relay for a Transformer

J.M.HO & C.C.Liu


Electrical Engineering Dept. Chung-Yuan U.
Chung-Li, Taiwan
Summary
The applications of nonlinear devices according to these theorems, but they
such as rectifiers, converters, power supplies, don’t focus on the situation that the pollutions
and other devices in utilizing solid state of harmonics enter the differential protective
switching have been increased in industries equipments. We aim at this problem and
during recent years. These induce a lot of analyze it.
harmonics in the voltage and the current, and According to the simulation results, we
therefore deteriorate the power quality. This know that most CT doesn’t perform well at
quality deterioration causes the power loss frequency domain. The magnetizing inrush
increasing, resonance problem, insulation current of the transformer and the saturation
deterioration and even safety problem for phenomenon of the CT may cause some
system apparatus. The protective equipments mistakes to the relay operations. These make
may work at normal situation. But they may the real test very difficult. So we ignore the
not protect accordantly when the pollutions of magnetizing inrush current of the transformer
harmonics exist in the system. It is necessary and the saturation phenomenon of the CT. The
to analyze the effects of harmonics to the tests are conducted with two conditions,
protective equipments. internal faults and external faults. Each test is
This paper aims at analyzing and with different harmonic components, including
probing into the influences of harmonics to the 3rd harmonic components, the 5th harmonic
differential relays. It analyzes and compares components etc, and the summations of
the mathematic models, which are constructed different order of harmonic components. From
by using EMTP and the test results. the real test results, we learn that the trip time
There are many factors to be considered of differential relay doesn’t always increase
in transformer differential protection designing with frequencies or harmonics. There is a
and practicing. This paper only analyzes the nonlinear region. Beside the nonlinear region,
influential phenomenon of harmonics to the trip time is proportion to frequencies and
differential relay, ignoring the magnetizing harmonics, or the relay doesn’t trip anymore.
inrush current of the transformer and the When internal faults happen, the harmonic
components will delay the trip time of
differential relay. This will affect power
saturation phenomenon of the CT; we system very much. The relay will not trip
study the tripping time of the differential relay when 3rd harmonic are more than 66.66% of
under different working frequencies and fundamental component. The most important
harmonics. point is that the trip time will delay when
Because of the pollution of harmonics, harmonics enter the equipments. In addition,
there are many differential relays designed in the differential relay will become not so
order to solve these problems, but they are all sensitive if working frequencies are not
designed on the condition that the 2nd fundamental frequency. So the harmonics
harmonic component of inrush current does affect the differential relay a lot. The results of
not less than 15% of fundamental component this research can provide the valuable
at normal situation. And the fault current, references and assistance in applying and
which involve dc component, should have its designing of protective system..
highest value of 2nd harmonic fewer than 7%
of fundamental component. We can distinguish
inrush current and fault current in according to
these two different characteristics. The
differential relays are always designed
The Effects of Harmonics on Differential Relay for a Transformer

J.M.HO & C.C.Liu


Electrical Engineering Dept. , Chung-Yuan U, Chung-Li, Taiwan

I. Abstract
The use of nonlinear devices such as rectifiers,
converters, power supplies, and other devices utilizing I in I out
solid state switching have been increased in industry
during recent years. These equipments have deteriorated Protection
the power quality. This deterioration causes the equipment
increasing of power loss, resonance problem, insulation
deterioration, and even safety problem for system
apparatus.
This paper aims at analyzing and probing into the I op
influences of harmonics on a differential relay. First it
probes the operation of a CT in frequency domain. Then,
it analyzes and compares the mathematic model, which is Figure 1(a) Normal or outer fault situation
constructed by using EMTP, and the test results. I F1 IF2
There are many factors to be considered in
differential protection design and application for a
Protection
transformer. This paper only analyzes the influential equipment
phenomenon of harmonics to differential relay.
The results of this research can be valuable
references for applying and designing differential relay
I op = I F 1 + I F 2
protection.

Figure 1(b) Inner fault situation


II. Purpose
Because of the pollution of harmonics, there are
According to the capacity and the importance of
many differential relays designed in order to solve these
the transformer, the protection scheme may have
problems, but they are all designed on the condition that
different types. But the differential protection is
the 2nd harmonic component of inrush current does not
mainly used to protect large power transformers or
less than 15% of fundamental component at normal
some of the important power distribution transformers
situation. And the fault current, which involve dc
with capacities less than 10MVA[2]. This paper
component, should have its highest value of 2nd harmonic
focuses on the differential relay for a transformer.
fewer than 7% of fundamental component. Then we can
2.The equivalent circuit of CT
distinguish inrush current and fault current according to
If the current ratio between the primary and
these two different characteristics. The differential relays
secondary side is 1:N2, the equivalent circuits of the CT
are always designed according to these assumptions, but
can be shown as Figure 2. It is often that RP and XP are
they don’t focus on the situation that the pollutions of
far smaller than Rs and Xs, even at system fault. So they
harmonics enter the differential protective equipments
can be neglected. The equivalent circuits are shown as in
[1].
Figure 2 and 3.

III. The testing methods and results


1.Principles of the differential protection
The differential protection is a primary protection
for power equipments, which depends on the difference
value between the input and output currents. The Figure 2 The equivalent circuits with primary resistance
protection method will not only fit a lot of power
equipments but also be the first aid to important power
equipments. The protection theorems of the differential
relay are shown in Figure 1(a) and Figure 1(b).
must be included, especially the transient state analysis.
For example, the inrush current, resonant, and saturation
should be concerned.
The 9th order mathematical model constructed by
M.Poljak is shown as below (4):

 (l − δ )
Figure 3 The equivalent circuits without primary
 cδ
resistance i1 =  c1 + 0 B − c3 B 3 + c5 B 5 − c7 B 7 + c9 B 9  ×
 l − δ  N2
ZM and Zb mean the excitation and burden
impedance of the CT, respectively. Figure 4 shows the 
voltage and current vectors of the CT. The accuracy of
the CT mainly depends on the quantity and the angle Where:
between primary current and secondary current [3]. At c0-c9:core material volume factors
steady state, the Ratio Error and the Phase-Angle Error :the air gap length of the core(m)
of the CT can be shown as in Equation 1 and Figure 4,
respectively.
l : the average length of magnetic (m)
N2: the winding turns of the secondary
N 2 ⋅ IS B: the magnetic flux density (T)
Ratio Error = (1)
Ip
As shown in Figure 5, EMTP has built a single-
phase saturation core transformer model. It consists of an
equivalent circuit on an ideal transformer. The - I data
can’t be get directly, so a program offered by EMTP is
needed to transfer the V-I characteristic of CT to - I
data. Besides, it can use the Type-96 from EMTP to
construct equivalent circuit [5].

Figure 4 The voltage and current vectors of CT


Where:
VS: the voltage on secondary
IM: the magnetic current
Ie: the excitation current
Ip: primary current
Is: the secondary current

3.The distribution model of CT by EMTP


The simulation problem of the transformer is the
nonlinear characteristic of magnetic core, which means
the B/H curve. The model of CT is often regarded as a
single-valued nonlinear inductance and neglecting the Figure 5 The equivalent circuit of CT by EMTP
hysteresis phenomenon. In order to increase the
accuracy, the hysteresis phenomenon of the transformer
The characteristic of CT(

The current of CT
Frequency

(a) The burden at secondary side is zero

The characteristic of CT(

The current of CT
Frequency

(b)The burden at secondary side is 0.5Ÿ


Figure 6 The excitation curve of 10/5 CT
Figure 7 The characteristic of CT (primary side voltage
is 120V)
Because EMTP can’t directly use the characteristic
curve of V-I, the V-I curve must be transfered to - I data
4.The experiment of the differential relay
by the program called SATURA. The characteristic of V-
I curve of 10/5 CAPV-type CT is shown as in Figure
6[6]. To build Type-96 symbol, the -I data are a. The experiment layout:
constructed by SATURA and the hysteresis curve is
created by HYSDAT[7]. The simulation results are
shown as in Table 1 and Figure 7.

Table 1 The characteristic of the CT

Working frequency
50 60 120 300 540 660
of CT (Hz)

Current on the
5.12 5.01 5.00 4.85 4.61 4.38
secondary side (A)

Working frequency
1000 2K 3K 4K 5K
of CT (Hz)

Current on the
4.06 3.62 3.2 2.9 2.8
secondary side (A)

Figure 8 The system block diagram


From these, one can see secondary current decreasing as
frequency increasing for a fixed primary current in 10
amperes. And the burden also affect the characteristic, The experiment layout is shown as in Figure 8.
with larger burden, the accuracy of ratio becomes worse. And the results are shown in table 2 to Table 5.
The working voltage F3 means
3rd harmonics (33.33%)
The working voltage F5 means
3rd harmonics (33.33%) and 5th harmonics (20%)

The working voltage F7 means


3rd harmonics (33.33%) , 5th harmonics (20%) and
7th harmonics (14.28%)
The working voltage F9 means at fault situations, the differential current in the tripping
3rd harmonics (33.33%) , 5th harmonics (20%) , 7th coil increases, the differential ratio increases, and the
harmonics (14.28%) and 9th harmonics (11.1%) relay will trip. Table 4 shows results of the tripping time
of the differential relay at the inner faults. Table 5 shows
The phase differences in above are all zero degree. the results of the tripping time of the differential relay at
the outer faults.

b. The simulation and testing of differential


protection Table 4 The tripping time of the differential relay at the
inner faults
(1) The simulation results for inner faults: Tripping Tripping
F. Tripping F. Tripping
With the setting as in Table 2 current current
(HZ) time (ms) (HZ) time (ms)
Table 2 The design example of differential relay (A) (A)
for inner fault 60 970 6.14 F3 928 6.18
The rate current of the Primary 2.89A 120 1150 6.17 F5 920 6.21
simulation transformer Secondary 5A 180 ’ 5.88 F7 940 6.14
I1/I2=2.9/1.45 240 ’ 5.77 F9 956 6.12
CT current ratio
I3/I4=5.01/5 300 ’ 5.69
The current from the high 360 ’ 5.59
1.45A
voltage side
420 ’ 5.59
The current from the low
5A *The tripping time is counted by oscilloscope
voltage side
CT tap 5-5

Table 5 The tripping time of the differential relay at the


(2) The simulation results for outer faults:
outer faults
Use same circuit but reserving the output CT. And
using settings as in Table 3 Frequency Tripping time Tripping current
. (HZ) (ms) (A)
Table 3 The design example of differential relay 60 2980 2.58
for outer fault 120 ’ 2.54
180 ’ 2.51
The rate current of the Primary 2.89A 300 ’ 2.49
simulation transformer Secondary 5A 240 ’ 2.49
300 ’ 2.47
CT current ratio
I1/I2=2.9/2.24 420 ’ 2.47
I3/I4=5.01/5 F3 2900 2.54
F5 3380 2.54
The current from the high F7 3620 2.48
2.24A
voltage side F9 4360 2.42
*The tripping time is counted by oscilloscope
The current from the low
5A
voltage side
IV. Conclusions
CT tap 5-5 According to the simulation results, we know that
most CT doesn’t perform well at all frequency ranges.
The magnetizing inrush current of the transformer and
the saturation phenomenon of the CT may cause some
mistakes to the relay operations. These make the real test
very difficult. So we ignore the magnetizing inrush
current of the transformer and the saturation
phenomenon of the CT. The tests are conducted with two
C.The experiment results: situations, internal faults and external faults. Each test is
When the system is at normal situation, the ratio with different harmonic components, including the 3rd
between the load current and differential current doesn’t harmonic components, the 5th harmonic components, and
change. Therefore, the tripping coil will not operate. But etc, and summations of different harmonic components.
From real test results, we learn that the tripping time of
differential relay doesn’t always increase with frequency
increasing or harmonic contents increasing. There is a
nonlinear region, beside the nonlinear region, the
tripping time is proportion to frequencies and harmonic
contents, or the relay doesn’t trip anymore. When
internal faults happen, the harmonic components will
delay the tripping time of differential relay, this will
affect power system very much. The relay will doesn’t
trip when 3rd harmonic are more than 66.66% of
fundamental component. The most important point is
that the tripping time will be delayed when harmonics
enter the equipments. In addition, the differential relay
will become not so sensitive if working frequencies are
not at fundamental frequency. The results of this research
can provide valuable references and assistance in
applying and designing of differential protective system.

V. References

1.H.Z.LEE The experience of differential protection for


transformer The Electricity
magazine No.11th P109~P116, 1996.

2.American National Standard, "Guide for Protective


Relay Application to power Transformer, "ANSI/IEEE
C37.91-1985.

3.R.D.,Power System Protection Reference


Manual,pp.66-102(1982)

4.Poljak, M. and N. Kolibas, " Computation of Current


Transformer Transient Performance," IEEE Trans. on
Power Delivery, Vol.3,No.4, pp.635-645(1988)

5.Kezunovic, M.,C. Wfromem and F. Phillips,"


Experimental Evaluation of EMTP-Based Current
Transformer Models For Protective Relay Transient
Study," IEEE Trans. on Power
Delivery,Vol.9,No.l,pp405-413(1994)

6.The technical support from Shyh Lin Electricity.

7.Leuven,K.U.,EMTP Center, Alternative Transients


Program-Rule Book, Leuven EMTP Center,
Belgium,(1987)

You might also like