Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

BASIC WATER SIZING

Copyright © 2007 RsLogical, inc.


All Rights Reserved
1
SIZING THE WATER DISTRIBUTION SYSTEM

Water distribution systems that are sized properly will not only Tee back upstream to the Building control valve are assigned sfu’s in
provide water in sufficient volume for the fixtures to operate, but also a different manner than other parts of the system. That is because
reduce the chance for water hammer to occur in the system. these sections of pipe supply all the hot water sfu’s in the system and
Velocities exceeding 8 feet per second in the piping will cause the cold water sfu’s to any fixture downstream of the section of pipe
erosion and water hammer. you are assigning the load to. This will be explained in greater detail
later.
This training booklet will help you to understand how to size the
water supply system using the Pressure Available For Uniform Completing a Water Calculation Worksheet
Loss method. To do this you will need to have a copy of the WI
plumbing code and in particular Comm. 82.40. Tables 82.40-1 Page 9 illustrates the completed water calculation worksheet. Using
WATER SUPPLY FIXTURE UNITS FOR NONPUBLIC USE the Total sfu from Table 82.40-1, add the total sfu’s from each
FIXTURES and 82.40-3 CONVERSION OF WATER SUPPLY fixture and appliance in the dwelling. Find Table 82.40-1 on page 6.
FIXTURE UNITS TO GALLONS PER MINUTE will be used.
1 - Automatic Clothes Washer = 1.0 hot 1.0 cold 1.5 total
Pages 4 and 5 illustrate a first floor plan and basement plan of a 1 - Dishwashing Machine = 1.0 hot 0.0 cold 1.0 total
typical ranch style home. There are 1-1/2 baths in this dwelling. 2 – Hose Bibbs – ½” = 0.0 hot 6.0 cold 6.0 total
Page 11 contains an isometric drawing of the water supply system 1 – Kitchen Sink = 1.0 hot 1.0 cold 1.5 total
with the sfu loads and pipe diameters. Cold water lines are 1 - Laundry Tray = 1.0 hot 1.0 cold 1.5 total
illustrated with a bolder line than the hot water lines for easier 1 - Lavatory = 0.5 hot 0.5 cold 1.0 total
identification. Several points along the piping are lassoed with 1 - Water Closet = 0.0 hot 2.0 cold 2.0 total
numbered tags. The numbers in those tags are the sfu load in that 1 - Bathroom Group, W/BT = 2.0 hot 3.5 cold 4.0 total
section of pipe. Totals sfu’s 6.5 hot 15.0 cold 18.5 total

The first valve after the water service enters the building is the Note the total sfu’s is 18.5. In order to find the pressure loss in psig
Building Control Valve. In the case of an interior pressure tank, the in the water service and water meter if supplied, those sfu’s must first
Building Control Valve is the first valve downstream of the tank. be converted into gallons per minute. Table 82.40-3 on page 6 is
Building Control Valves shall be installed within 3 feet of developed provided to do this conversion. Notice the line between 10 and 20
length of where a water service first enters a building and within 3 sfu’s in the table. 18.5 sfu’s is not shown so you must interpolate the
feet of developed length downstream of an interior pressure tank. gpm. These are flush tank type water closets.

Another point of interest is the tee in the cold water line that connects 10 sfu’s = 8 gpm and 20 sfu’s = 14 gpm. The difference between 20
the water heater to the cold water supply. It is pointed out in the and 10 is 10 and the difference between 14 and 8 is 6. You must
isometric drawing on page 11. This tee is commonly referred to as divide the difference of 6 by 10 to find how much to add for every 1
the Transition Tee. Sections of cold water pipe from the Transition fixture unit over 10 sfu’s. Dividing 6 by 10 results in .6 for every 1
2
fixture unit over 10. There are 8.5 sfu’s over 10 so multiply .6 by This sample has a 5/8 water meter installed. Page 8 has Graph
8.5. .6 X 8.5 = 5.1 That means you add 5.1 gpm to 8 gpm and come A-82.40(7)-1 illustrated with the graph line extending up from 13.1
up with a conversion of 13.1 gpm demand of the building. gpm circled at the intersection of the graph line of a 5/8 meter. That
loss is 6.4 psig and is entered on line C. subtotal of the worksheet.
On the top of the water calculation worksheet there is a boxed in Subtracted from line B. the pressure available is 31.8 on line C.
area. Inside the box is the information required to find the loss in the subtotal.
service and the pressure available at the building control valve.
The tub valve is a pressure balance valve, which requires 20 psig to
There are other factors that affect the pressure at the building control operate so that is the controlling fixture. Subtracted from 31.8 the
valve. Difference in elevation, (6 ft), Length of the service, (70 ft.) remainder is 11.8 psig on line D. subtotal.
and the low pressure at the connection to the water main or exterior
pressure tank, (48 psig) The next step is the difference in elevation from the building control
valve to the controlling fixture, which is 12 ft. Multiplied 12 by .434
Pressure loss in the water service and there is pressure loss of 5.2 psig from the elevation difference.
That now leaves 6.6 psig on line E. subtotal.
Now that you know the gpm demand of the building, the pressure
loss in psig within the service can be determined by using one of the There is no device creating an addition loss to the controlling fixture
graphs in the Appendix of the code. This sample is going to use therefore 6.6 is transferred down to G. subtotal.
Graph A- 82.40 (7)-6 PEX Tubing ASTM F876. Find that graph
on page 7 of this booklet. The flow rate is located along and up the Determine Line G. by taking a measuring tape and measuring along
left side of the graph. The pressure loss due to friction (psig/100 ft of the piping starting at the building control valve all the way to the
pipe) is displayed along the bottom of the graph. controlling fixture. Include the fittings and into and out of the water
heater if the controlling fixture is not a cold only fixture.
By following the graph line located at 13.1 across the graph until it
intersects with the 1” pipe size line you will find a circle. Looking This sample is 76 ft for the developed length and equals 114 when
down the graph you will see that it is just over 10 psig/100 ft. multiplied by 1.5. The A value in this sample is rounded up to 6.
Actually it is 10.3 psig loss per 100 ft. of pipe. There is not a total of
100 ft in the service though. It is 70 ft in length. Therefore you Assigning Water Supply Fixture Units
multiply 10.3 by .70 and the result is 7.2 psig loss in the service.
That loss is entered on line 7. Then subtract it from the pressure in In the sample used in this booklet there are 6.5 hot sfu’s. Assign the
the water main (48) leaving 40.8 psig. sfu’s to the hot water piping first.

Next is the pressure loss or gain from the elevation difference To the left of the water heater there are 2 sfu’s. Those 2 units come
between the main and the building control valve. 6ft X .434 = 2.6 from 1 hot unit of the Kitchen Sink and 1 hot unit of the Dishwashing
psig loss on line 8. Subtract line 8 from line 7 subtotal and line 9 is Machine. To the right of the water heater there are 4.5 sfu’s. 2 from
38.2. Transfer 38.2 down to line B. the Bathroom Group, 1 from the Laundry Tray, 1 from the Automatic
Clothes Washer and .5 from the Lavatory in the powder room.
3
Now that you know there are 6.5 sfu’s on the hot water, you can There is a Dishwasher, Kitchen Sink and ½” Hose Bibb on the cold
determine the sfu’s on the cold water line that supplies the water past the water heater. You do not add the full value of the cold sfu to
heater. Starting at the water heater, you must assign the units the 6.5 hot sfu to determine the load on the upstream side of
backwards or upstream to the building control valve. That cold water Transition tee. Remember that fixtures other than lavatories have a
line on the upstream side of the Transition Tee not only supplies all total that is less than the hot and cold sfu combined. That’s because
the hot water units, it also supplies the cold water past the water the faucet port will not allow the full flow of both the hot and cold.
heater. But only the balance of the total sfu of the fixture is added But if either one is used alone you will get the full sfu flow. So you
from fixtures past the heater. In other words, the kitchen sink with a do not add 4 + 6.5 to find the load on the upstream side of the
total of 1.5 sfu’s has 1 sfu already included from the hot and you Transition tee. You only add the full 3 sfu from the Hose Bibb
only add .5 from the cold. (because there is no hot) and the .5 sfu that is the balance of the
kitchen sink total. Remember that 1 sfu is already on the upstream
Notice that there are 4 sfu’s on the cold water line to the left of the side of the Transition tee from the hot of the Sink. Therefore 10 sfu
heater or past it. 3 sfu’s come from the ½ inch hose bibb and 1 sfu is the load on the point.
from the cold of the kitchen sink. Remember now that pipe is past
the Transition Tee so it only supplies the cold water to those fixtures. Notice that the tag with 5.5 is the full load of the cold sfu’s because
This may confuse you because to the right of the heater or upstream that cold line does not serve the water heater. Tags with 13, 15.5 and
of the Transition Tee, the pipe supplies 10 sfu’s. You can’t add the 18.5 are lassoed around the cold water line that serve the water
4 cold units past the heater to the 6.5 hot units to determine the load heater. Therefore only the balance of the total sfu’s less all the hot
upstream of the Transition Tee because the total of the Kitchen Sink sfu’s from fixtures served by that pipe is added to the total hot sfu’s
is 1.5 not 2. Therefore you have 6.5 from the hot, 3 from the hose to determine the load in the tagged section.
bibb and .5 or the balance of the total of the Kitchen sink.

The rest of the cold sfu’s from fixtures that connect to the cold line The last step is to size the distribution piping by using the tables
back to the building control valve are added in the same manner. provided in Comm.82.40. This sample home is going to use CPVC
Hose bibbs do not have hot sfu, so the total value is added. The cold Tubing ASTM D2846 for the distribution piping so Table 82.40-8
branches that come off the cold to the water heater are assigned the has been included on page 10.
full value of the cold because they only serve the cold to those
fixtures. A dark line is provided under the pressure available for uniform loss
in the first column and stretches across the table. These are FT or
The sample drawing on the next page is an example of a water flush tank fixtures in the system, which means the maximum load on
distribution system in a 1-½ bath ranch home. There are 18.5 total the sections of each size of pipe shall not exceed the sfu’s listed just
water supply fixture units. Count them yourself by using Table above the dark line. 7.0 are the maximum sfu’s for 3/4 inch diameter
82.40-1 (Nonpublic Use Fixtures). Notice that there are 6.5 hot pipe and 15.5 is the maximum sfu’s for 1 inch diameter piping.
sfu’s. That is the sfu you start with at the transition tee to the heater.
The pipe diameters required at the changes are shown on the
isometric plan on page 11.
4
5
6

1
1
1

1
18.5

1
7
8
9
10
11
12

Basic Water Sizing

Exercise
Copyright © 2007 RsLogical, Inc.
All Rights Reserved
13
Basic Water Sizing
Exercise

Contents

Page no:

13 Instructions
14 1st Floor plan of exercise house
15 Basement plan of exercise house
16 Isometric drawing of the water distribution system
17 Tables 82.40-1 and 82.40-3
18 Water Calculation Worksheet
19 Water Calculation Worksheet
20 Graph 82.40(7)-7; PE Copper Tube Size
21 Graph 82.40(7)-1; Water Meters
22 Table 82.40-8; CPVC tubing ASTM D2846
Instructions
This is Exercise 1 of Basic Water Sizing. Inside this packet are the tables, graphs, drawings and worksheets you will need to complete this test.
Fill out the water calculation worksheet from the information below. Label the sfu’s and sizes at the tags of this exercise. When Exercise 1 been
completed, log onto your test at rslogical.com and complete the questions there.

Use the following information to complete the water calculation worksheet:

Low pressure at the water main; 50 psig;


Water service from the main to the lot line is 1-1/4 inch PE copper tube size 35 ft in length
Water service from the lot line to the building control valve is 1-inch PE copper tube size 75 ft in length;
Difference in elevation between the main and the building control valve; 5 ft;
3/4 Water meter;
Pressure required at the controlling fixture, pressure balance tub valve; 20psig
Elevation from the building control valve to the controlling fixture; 12 ft
Developed length from the building control valve to the controlling fixture; 80 ft
Water distribution material is CPVC Tubing ASTM D2846
14
15
16
17
18
19
20
21
22

You might also like