HOYT RESIDENCE UNIT #1
Salt Lake City, Utah
Project:
Floor Loads
Dead Load 12 psf CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
BUILDING SKETCH
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
Deflection Criteria
Floor: L/360 Total, L/480 Live
TEL 801.372.2950
MATERIALS AND EQUIPMENT REQUIRED TO COMPLETE THE WORK Kenneth E. Wheadon ABR Engineering T1.1 PROJECT COVER SHEET S0.1 GENERAL STRUCTURAL NOTES
CALLED FOR, INDICATED OR REASONABLY IMPLIED BY THEM, 10 South 300 East
1194 East Crystal Avenue S1.1 FOOTING AND FOUNDATION PLAN
INCLUDING PARTITIONING, MECHANICAL AND ELECTRICAL WORK, C-1 Civil Drawings Not Included in this set S2.1
SLC, Utah 84106 American Fork, Utah 84003 FLOOR FRAMING PLAN
AIR CONDITIONING AND ALL OTHER ITEMS DESCRIBED. FAILURE - submitted separately (AS REQUIRED) S2.2 ROOF FRAMING PLAN
TO SHOW DETAILS OR REPEAT ON ANY DRAWINGS THAT FIGURES, t: (801) 466-6296 t: (801) 691-2296 Ryan B. Alder, P.E., S.E. S3.1 FIRST LEVEL SHEARWALL / HOLDOWN PLAN
NOTES OR DETAILS GIVEN ON ANOTHER DRAWING SHALL NOT ken@crsa-us.com Ryan@ABR-eng.com Ryan@ABR-Eng.com
M: 801.691.2296
N1.0 GENERAL NOTES
S3.2 SECOND LEVEL SHEARWALL / HOLDOWN PLAN
RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO PERFORM contact: Ken Wheadon contact: Ryan Alder, S.E. www.ABR-Eng.com
SD1 STRUCTURAL DETAILS
A2.1 FIRST LEVEL PLAN
Client:
THE WORK (AT NO ADDITIONAL COST) AS IF SHOWN ON EACH
Contractor
A2.2 SECOND LEVEL PLAN
AND EVERY DRAWING. Draftsman A2.3 ROOF PLAN Project Info: Custom Plan
Drawing Information:
Project Number:
Project Manager:
Project Engineer
1101-001-17
DLG
Date: 05-22-2018
BUILDING AND ZONING DEPARTMENT. A9.1 SECOND LEVEL FLOOR FINISH PLAN 2 - -
3 - -
4 - -
CONTRACTOR SHALL BE REQUIRED TO CARRY COMPREHENSIVE E1.0 FIRST LEVEL ELECTRICAL / LIGHTING PLAN 5 - -
LIABILITY INSURANCE AT HIS OWN EXPENSE. E1.1 SECOND LEVEL ELECTRICAL / LIGHTING PLAN Sheet Title:
T1.0
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
GENERAL EXITING REQUIREMENTS ELECTRICAL PLUMBING
1. The following was compiled with the intent of summarizing some of the 1. At least one exit door minimum 3’-0" wide and 6’-8” in height with side hinges shall be provided for 1. All electrical installations shall comply with the 2015 International Residential Code, and 2014 NEC 1. All plumbing installations shall comply with 2015 International Plumbing Code.
construction requirements for single family dwelling and townhouse dwelling unit. R311 Code requirements
construction. The following information has been referenced from the 2. Provide location for gas meters in an area that is protected from snow and ice damage. lMC 15-2.3-4
2015 International Residential Code and the Utah State Amendments 2. All hallways shall not be less than 36” in width. R311.6 2. All receptacles serving kitchen countertops, in garages, baths, unfinished basements and outside (J)
to the International Codes and the National Electrical Code. receptacles shall be GFCI protected. -IRC E3902
(The actual code should be used for the exact wording, details and requirements) 3. Hallways and all other habitable rooms shall have a ceiling height of 7’-0" minimum. R305 3. Provide anti-scald device. The hot water supplied to bathtubs and whirlpool tubs shall be limited to a
3. Lights in closets must comply with the clearance dimensions of IRC E4003.12 maximum temperature of 120° f by a water temperature limiting device that conforms to ASSE
1. Construction documents are valid for a single use at the project location and shall not be reused, copied, 4. All sleeping rooms and basements shall have at least one operable, exterior window or door for 1070. Except where such protection is otherwise provided by a combination of tub/shower valve in
or reproduced without written approval from DG Drafting & Design. emergency escape and rescue. these egress units shall be operable from the inside without special tools. 4. Electrical panels must comply with IRC E3405.2 for 30" by 36" minimum working space and 6'-6" accordance with IRC P2708.3
minimum headroom.
2. All submittals and changes to plans shall be approved by the designer prior to being submitted THE FOLLOWING SHALL APPLY PER R310 4. Provide water closets with a flow rate of not more than 1.6 gallons per flush. IRC P2903.2
to the building official for approval. Engineer to approve all structural changes. 5. Provide smoke detectors conforming to IRC section R314. All levels, all bedrooms, access to all
1. Minimum 5.7 sq. ft. net clear opening of windows. (5 sq. ft. for windows on ground floor) minimum net bedrooms and in all rooms with sloped ceilings next to halls serving bedrooms. IRC R314.3 All 5. Provide showerheads with a flow rate of note more than 2.5 gpm. IRC P2903.2
3. Contractor / Owner shall review and verify all notes, dimensions, locations, etc. prior to any phase of clear opening height of 24” detectors shall be hard-wired, interconnected, and have battery backup. IRC R314.4
construction, any existing structures shall be field verified and shall take presidence over any existing 6. Provide (minimum of 2) non-freeze type backflow prevented hose bibs. IRC P2902.3, P2603.6
drawings. contractor shall notify designer of any discrepancies, omissions, or conflicts between the 2. Minimum net clear opening width of 20” 6. Provide at least two outside grade level receptacles. One in the front yard and one in the rear yard. IRC
various elements of the working drawings and/or specifications before proceeding with any work E3801.7 7. Hose bib connections are to be equipped with an atmospheric or pressure type vacuum breaker.
involved. 3. Maximum finished sill height of 44” above finished floor. P2903.2
7. All branch circuits that supply electrical outlets in bedrooms need to be provided with Arc-fault
4. It is the Contractor's and all Subcontractors' responsibility to perform their trades and duties in 4. Window wells for egress windows shall have a minimum net clear opening of 9 sq. ft. with a min. protection. NEC 210-12 8. All plumbing vents passing through the roof to be minimum 3" pipe, and as direct as possible from
conformance with the procedures and requirements as stated in the 2015 INTERNATIONAL dimension of 36” wide and minimum 44” in depth. the main drain to the open air above the roof. IRC P3103.2
RESIDENTIAL CODE 8. Carbon monoxide detectors shall be installed on each habitable level of a dwelling unit equipped with a
5. Egress windows are allowed under decks and porches if it allows window to be fully opened and provides fuel burning appliance and in dwelling units with attached garages. IRC R315.1 Shall be interconnected 9. Provide expansion tank on the culinary water system. IRC P2903.4
5. Fire sprinklers shall be built to NFPA 13R or 13 shall also be built to NFPA 13D (as required per location) a path not less than 36” in height directly to out to yard. with smoke detectors as amended by state
fire sprinkler layout shall be designed by others therfore a defferred submittal. (Sprinkler requirements 10. Provide location of access for whirlpool type tubs. No grouted tile access. IRC P2720.1
per local Building Official) GLAZING 9. Electrical panel to be 200 amp (Electrician to verify)
11. Showers shall be finished to a height of not less than 72 inches above the floor. Material shall be
6. All construction debris shall be removed prior to final inspection. Construction debris shall be secured at 1. Glazing in doors shall be (tempered) safety glazing. R308.4 10. Electrical panel is not to be installed in bathrooms, fire rated garage walls or closets may not be located nonabsorbent. IRC R307.2 © COPYRIGHT 2017:
all stages of construction to prevent traveling from job site. behind a door or in a room that may be locked and have proper working clearances. NEC 110 REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
2. Glazing within a 24” arc of either edge of a door when closed shall be (tempered) safety glazed if the 12. Provide a floor drain by the water heater. Show a metal pan under the water heater or steam shower PURPOSE IS STRICTLY PROHIBITED
7. Special inspections required by the local Building Official or the International Residential Code are the bottom edge is less than 60” off the ground. R308.4 11. Pacificorp requires that the main electrical service entrance must be within 10'-0" of the front corner of equipment if located on a wood floor. IRC P2801.5
responsibility of the Owner or Contractor. the house. electrical meter must be on the side of the house. electrical service entrance cannot be
3. Glazing panels larger than 9 sq. ft located less than 18” above or within 36” horizontally of a floor or located over a window well or within 3'-0" of gas meter. 13. Provide 21" clearance in front of water closet. Show a full 30" wide finished space for water closet.
8. Printed dimensions shall take precedence over scales shown on construction documents. The registered walking surface shall be (tempered) safety glazed. R308.4 IRC R307.1
NATURAL LIGHT & VENTILATION 17. Small wall sections 2'-0" or wider (includes between doors) require an outlet. ATTIC PLUMBING
4. Building location must comply with all regulations of the city ordinances.
1. All habitable rooms shall be provided with minimum window area shall equal not less than 8% of the ATTIC ELECTRICAL 1. Condensate drain and secondary drain 1/8" per ft. min. slope with supports every 4'. On retrofit units
5. Buildings closer than 5 ft. to property line shall be of 1-hr construction without
doors or windows. floor area of the room unless artificial light is provided capable of producing an average illumination of 6 both drains may run to the exterior.
foot candles over the area of the room at a height of 30 inches. R303.1 1. Switched light and receptacle near the unit with switch near attic access scuttle. Duplex receptacles may
not be upward. 2. Gas line air test if more than 6' of new gas line piping is added. 10 lbs./15 min.
6. Eaves, overhangs and projections cannot be less than 2 ft. from the property line and
must be of 1-hr. If within 3 ft. of the property line. R302.1 2. All habitable rooms shall be provided with natural ventilation equaling 4% of the floor area shall be
through windows, doors, louvers or other approved openings to the outdoors unless an approved 2. Air conditioner condenser to be provided wit a separate dedicated circuit and have a disconnect (fused or 3. Gas shut-off within 3' of unit.
mechanical ventilation system is provided capable of producing 0.35 air changes per hour in the room or "HACR" breaker) in sight of the unit and readily accessible (Within 50')
7. No stumps, roots, or organic material shall be present in soil at the area of the building.
Project:
a whole-house mechanical ventilation system is installed. R303.1 4. Gas supply flexes connectors are not allowed to pass through the equipment housing.
3. Identify breaker at meter panel/proper conductor size.
8. Water meters cannot be located in driveways, approaches, sidewalks
3. Room and areas requiring mechanical ventilation other than bathrooms provide an approved mechanical FIREPLACE
CONTRACTOR & ALL SUB
ventilation system capable of producing 0.35 air changes per hour. R303.1 4. All electrical wiring within six feet of the attic access scuttle must be secured and protected by a guard
9. Buildings cannot be located on any easements or right of ways10.Site shall be graded such that the CONTRACTORS WORKING ON THIS
strip. 1. Masonry fireplaces: combustible material shall not be placed within 2 inches of fireplace smoke PROJECT TAKE FULL LIABILITY OF
ground slopes away from the foundation at least 6” in the first 10’ of the foundation. R401.3 THESE PLANS AND SHALL
4. Bathrooms shall be provided with ventilation from a window with a minimum area of 3 sq. ft., not less chamber or chimney walls. Combustible material shall not be placed within 6 inches of the fireplace THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
10. Any retaining wall over 4 feet in height from the bottom of the footing to the top of the wall must be an than 1 ½ sq. ft. operable. or provide exhaust fan capable of (5) air changes per hour. The fan must MECHANICAL opening. No such combustible material within 12 inches of the fireplace opening shall project more NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
approved design with engineers details included. R404.5 exhaust outside not less than 3” from any opening. R303.3 than 1/8" for each 1" distance from such an opening. -IRC R1003.12
1. All mechanical installations shall comply with the 2015 International Mechanical Code and 2015
TEL 801.372.2950
input. The one opening must be in the top 12 inches of the room. Show minimum 1 inch clearance 3. Chimneys shall extend at least 2 feet higher than any portion of a building within 10 feet, but shall
13. Roof runoff shall be collected and discharged well outside of the backfill limits, and at least 10’ from the
structure 7. All attic areas shall be provided with attic ventilation of not less than 1 sq. ft. per 150 sq. ft. of attic area around equipment at sides and rear of the appliance. Minimum 6 inch clearance in front of the appliance. not be less than 3 feet above the point where the chimney passes through the roof. IRC figure
or 1 sq. ft. per 300 sq. ft. if 50% to 80% of the ventilation is provided in the top 3’ of the attic area and IRC G2407.6.2 (304.6.2) R1001.1 (fireplace and chimney details)
14. Homes located in potential flood areas will be required to have elevation certificates prior to and after the rest is provided from soffit vents. R806
completion of construction. R106.1.3 4. Each gas appliance shall have a shut-off valve within 6 feet of the appliance and shall be installed STAIRWAY & GUARDRAILS
FOOTINGS AND FOUNDATIONS upstream of the union, connector or quick disconnect device it serves. IRC G2420.5.1
1. Stairways shall not be less that 36" in clear width at all points above the permitted handrail height
1. Perimeter footing is to be continuous and must extend 36” below the frost line minimum. (Depth is 5. Fuel-burning appliances, including fireplaces, are not permitted to be installed in sleeping rooms, and shall not project more than 4.5" on either side. IRC R311.7.1 Handrails must be installed on all
FIRE SEPARATION BETWEEN HOUSE AND GARAGE
measured from the bottom of the footing to finished grade) R403.1.2 & 403.1.4 bathrooms, or toilet rooms unless the appliances are direct vent appliances. See IRC G2406.2 and IMC stairs with 4 or more risers IRC R311.7.7 Handrails shall return to wall or terminate into newel
303.3 for more information and the list of exceptions. posts or safety terminals. IRC R311.7.7.2 hand railings shall not be less than 34" above nose of
22. Fire separation between the house and garage with material approved for 1-hr. fire resistive construction
on the garage side. R302.6 2. Foundation walls are to extend at least 6” above the finished grade or 4” above grade with masonry tread no more than 38" above nose of tread. IRC R311.7.7.1 Handrail shall have a diameter not less
veneer. R404.1.6 6. Fuel-fired water heaters shall not be installed in a room used as a storage closet. Non-direct-vent water than 1 1/4" and no more than 2". -IRC R311.7.7.3
Client:
heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air
23. A common method of providing 1-hr. fire protection to these framing members is to use 5/8” type
3. Foundation sill plate shall be treated wood or foundation grade redwood. R317 will not be taken from the living space. IRC M2005.2 2. Guardrails shall be not less than 34" in height. IRC R312.2 Open railing shall have intermittent rails
“X” sheetrock on the garage side of the studs and ceiling joists nailed 7” on center or screwed 12” on
center. ICBO ES #1602 spaced such that a 4" spherical object cannot pass through. IRC R312.3 Project Info: Custom Plan
4. Connections of the structure to the foundation shall be adequate to transfer forces. 7. Appliances having an ignition source shall be elevated such that the source of ignition is not less than 18
A. Anchor bolts must be min. 1/2” inches above the floor in garages. Rooms or spaces that are not part of the living space of a dwelling
24. Fire resistive construction of the separation shall be both horizontal and vertical. Common walls between ROOFING
B. Hold downs shall be as required by the engineer or as for alternate braced wall panels. unit and that communicate with a private garage through openings shall be considered to be part of the
the house and the garage must be completely protected. All structural members supporting the fire
garage. IRC M1307.3 1. Roofing material must have an approval from an approved testing agency. Roof slope will determine
separation shall also be fire protected, this includes bearing walls, columns and beams. R309.2
5. All footings shall be designed to minimize differential settlement. Footing shall be the type of roofing material that may be used. Roofing must be installed exactly as intended by the
placed on soils approved by the soils engineer and follow all recommendations included in the soils 8. Appliances located in a garage or carport shall be protected from impact by automobiles. IRC M1307.3.1
25. Any door between the house and the garage must be solid wood 1-3/8” thick tight fitting doors or a 20 approval agency. Asphalt shingles installed on roofs less than 4/12 pitch must be over an approved
min. labeled door (closer not required) R302.5.1 report. R401.4.1 and R403.1 water shield. Asphalt shingles cannot be installed on roofs with less than a 2/12 pitch. R905.2
A. Where footings are dug rather than formed the soil shall be stable enough to maintain near vertical 9. Vapor retarder in accordance with ASTM E 96, or aluminum foil with a minimum thickness of 2 mils shall
edge without sluffing or forms must be used. be installed on the exterior of insulation on cooling supply ducts that pass through unfinished areas such
26. 22”x30” attic access door located in the garage ceiling shall be of 1hr. fire resistive construction 2. Ice and water shield shall be installed at all eaves and valleys, it shall extend from the eave edge to
B. Exterior and interior footings may be inspected at the same time or separately. as crawl spaces, attics, unheated garages, etc. -M1601.4.5
5/8” sheetrock or 7/16” OSB min. Access doors shall be latched. All latches shall be screwed into a solid 24” inside the exterior wall. R905.2
member. "Not into sheetrock only" R302.6 All footings, including interior footings placed with the basement slab, must be inspected and approved
prior to concrete placement. if poured monolithically with the floor the footing must be 18” deep from 10. If gas pipe system is over 4 ounces pressure provide a gas piping schematic for the system. Clearly
3. Step flashing shall be used where the roof meets a vertical surface. Counter flashing shall be installed
the top of the slab. R403.1.4 identify the operating pressure, type of piping material, size of the gas pipe, lengths of the piping runs,
27. Duct penetrations shall be minimum 26 gage sheet metal with no openings into the garage. R302.5.2 at all roof and wall junctures. R905.2
capacity of each appliance in btu's/hour or cubic feet of gas per hour, identify the brand and location of
CRAWL SPACE each regulator, and venting of each regulator. IRC R106.1.1
28. Under no circumstances shall a door be permitted between the garage and a sleeping room. R302.5.1
1. Wood beams & girders shall NOT be located within 12” of exposed ground and floor joists not less than 11. Room and areas requiring mechanical ventilation other than bathrooms provide an approved mechanical
ROOM DIMENSIONS/MISCELLANEOUS
18” unless they are of treated material. R317 ventilation system capable of producing 0.35 air changes per hour. IRC R303.1
Stamp:
1. Ceiling height is required to be a minimum of 7’-0” in all rooms, halls and basements. the bottom of all
2. A Min. 18”x 24” crawl space shall be provided. R408.3 12. Provide 6" clearance on combustion air side of furnace room and 30" working space in front of all heating Drawing Information:
beams, girders, ducts or other obstructions may be 6’-4”. Sloped ceilings require the minimum height for
controls. 3" min. all other sides. Project Number: 1101-001-17
more than ½ of the room. R305 Project Manager: DLG
3. If furnace is located in the crawl space the access shall be min. 22”x 30” or the size of the equipment if Project Engineer
2. Houses shall have at least one room not less than 120 sq. ft. of floor area. Other habitable rooms except larger within 20’ of the furnace. M1305.1.4 Date: 05-22-2018
Revision:
kitchens shall have area of not less than 70 sq. ft. R304
PRELIMINARY
4. Crawl space ventilation shall be provided by an approved mechanical means or opening in the exterior MRK DESCRIPTION DATE
3. Habitable rooms other than kitchens shall have a minimum dimension of not less than 7’-0". R304 wall. the openings shall be a min. of 1 sq. ft. per 150 sq. ft. of area under the floor. The openings shall 1 - -
be located within 3’ of the corners and shall provide cross ventilation. R408.2 2 - -
4. Exterior walls shall provide the building with a weather-resistive exterior wall envelope. IRC R703.1 3 - -
provide weather-resistive barrier flashing details for windows, door and other openings in the building 4 - -
DRAWINGS
5 - -
Sheet Title:
N1.0
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
528 SQ. FEET
FIRST LEVEL FLOOR PLAN 506 SQ. FEET GARAGE
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
22'-0"
* NOTE:
WINDOWS/DOORS ON LEFT OR RIGHT ELEVATIONS OF UNIT SHALL BE INSTALLED ON STREET FACING
UNITS ONLY. NO WINDOWS/DOORS ON END UNITS TO BE INSTALLED IF WITHIN 5'-0" FROM ANOTHER UNIT
OR WITHIN 5'-0" OF PROPERTY LINE. FIELD VERIFY CONDITIONS.
12" 20'-0" 12"
6'-0"
6'-0"
INSTALL PER MANUFACTURERS
- SPECIFICATIONS
VENT FOR FIREPLACE
(VERIFY EXACT ROUTING
*
WITH MECHANICAL /
100 106
STRUCTURAL DRAWINGS)
1'-61 2"
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
TEMP. GLASS OF THESE PLANS FOR ANY
TEMP. GLASS
3'-5"
PURPOSE IS STRICTLY PROHIBITED
COATS
R/S
SHUT OFF VALVE
FOR HOSE BIB NOTE:
NON-FREEZE TYPE
4'-1"
ALL FIREPLACE LISTING
BACKFLOW PREVENTER
INFORMATION SHALL BE
ENTRY PROVIDED @ TIME OF
12'-0"
11"
STAIRS
RAILING
105
(- RISERS)
103
*
61 2" UP 61 2"
16'-111 2"
3'-4" 17'-7"
7'-1"
DW
*
8'-4"
02 102 02
TEMP. GLASS
TEMP. GLASS
104
* 104
Project:
A4.0 PWDR KITCHEN A4.0
53'-0"
53'-0"
104 102 WATER SUPPLY LINE
FOR ICE MAKER
STUB FOR GAS
COOK TOP CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
REF PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
102 THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
14'-6"
MECH ROOM
BACKFLOW PREVENTER
103 WALLS W/ R-13)
6'-7"
ALL MECHANICAL
INSTALLATIONS SHALL COMPLY F.D.
WITH THE 2015 IRC & IFGC.
INSULATE HEATING & BRANCH
SUPPLY DUCTS IN UNFINISHED
AREAS, CRAWL SPACES, ATTICS,
TEL 801.372.2950
UNHEATED GARAGES, ETC. PER
61 2"
IRC N1103.
17'-51 2" 3'-51 2" 61 2"
GARAGE
27'-5"
103
7'-0"
Client:
16'-11"
AUTOMATIC GARAGE DOOR OPENERS IF PROVIDED
SHALL BE TESTED IN ACCORDANCE WITH UL325. (R309.6)
Project Info: Custom Plan
105
*
GENERAL NOTES
6'-5"
PRELIMINARY 1. 2X WALLS
2. STONE VENEER
DRAWINGS
101
3. ALERT DG DRAFTING & DESIGN AND
ENGINEER TO ANY UNFORESEEN ISSUES
DURING CONSTRUCTION.
RADIANT HEAT WITH FORCED AIR FOR THE A/C COOLING.) 7. CARBON MONOXIDE DETECTORS AND 1 - -
A4.0 SMOKE DETECTORS ARE TO BE HARD WIRED 2 - -
IN SERIES W/ BATTERY BACKUP.
3 - -
NOTE!
4 - -
FIRE BLOCK STUD SPACES AT SOFFITS, FLOOR AND 8. OMISSIONS IN AND/OR CONFLICTS
CEILING JOIST LINES, AT 10 FT. HORIZONTALLY AND
VERTICALLY AT FLOOR AND CEILING LINES, AND AT BETWEEN THE VARIOUS ELEMENTS OF THE 5 - -
OPENINGS BETWEEN ATTIC SPACES AND CHIMNEY CONTRACT DOCUMENTS SHALL BE BROUGHT
SPACES FOR FACTORY-BUILT CHIMNEYS, AND AT ANY Sheet Title:
OTHER LOCATIONS NOT SPECIFICALLY MENTIONED
TO THE IMMEDIATE ATTENTION OF THE
WHICH COULD AFFORD PASSAGE FOR FLAMES.
IRC R30211
DESIGNER AND SHALL BE RESOLVED
BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
A2.1
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
SECOND LEVEL FLOOR PLAN 1166 SQ. FEET
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
22'-0"
* NOTE:
WINDOWS/DOORS ON LEFT OR RIGHT ELEVATIONS OF UNIT SHALL BE INSTALLED ON STREET FACING
UNITS ONLY. NO WINDOWS/DOORS ON END UNITS TO BE INSTALLED IF WITHIN 5'-0" FROM ANOTHER UNIT
OR WITHIN 5'-0" OF PROPERTY LINE. FIELD VERIFY CONDITIONS.
11'-0" 11'-0"
2'-11" 19'-1"
205
61 2"
4'-71 2"
7'-01 2"
201
204
*
13'-11"
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
16'-2"
MASTER
15'-11"
BEDROOM
18'-1"
203
6'-101 2"
25'-111 2"
203 SHWR
TEMP. GLASS
1/2 WALL
*
3'-6"
206 205
TEMP. GLASS
BATH 2.5 GPM
6'-71 2"
SHOWER
204 HEAD
8'-11 2"
2'-111 2"
STAIRS
HALL 204
7'-6"
105
17'-115 8"
201
TEMP. GLASS
SHWR
DRY
TEMP. GLASS
202
*
PAN & DRAIN
Project:
207
SHOWER HEAD
5'-8"
53'-0"
53'-0"
53'-0"
53'-0"
2.5 GPM
WASH
211
ABOVE
CONTRACTOR & ALL SUB
206 CONTRACTORS WORKING ON THIS
VEST
11'-10"
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
7'-35 8"
TEMP. GLASS
207
43
207
6'-51 2" 6'-101 2" 3'-71 2"
3'-
210
6'-2"
2'-67 8"
2'-67 8"
1'-101 2"
LINEN
208
9'-0"
3'-51 2"
TEL 801.372.2950
3'-0"
209
* 209
5'-11" 4'-43 4" 4'-41 4" 6'-3"
201
*
61 2"
61 2"
7'-0"
7'-0"
BEDROOM BEDROOM
18'-61 2"
18'-61 2"
Client:
210 209
14'-61 2"
14'-61 2"
* 210 200
* GENERAL NOTES
6'-5"
6'-5"
PRELIMINARY 1. 2X WALLS
2. STONE VENEER
61 2"
61 2"
10'-33 4"
211 212
10'-71 4 "
DRAWINGS 3. ALERT DG DRAFTING & DESIGN AND
ENGINEER TO ANY UNFORESEEN ISSUES
DURING CONSTRUCTION.
RADIANT HEAT WITH FORCED AIR FOR THE A/C COOLING.) 7. CARBON MONOXIDE DETECTORS AND 1 - -
A4.0 SMOKE DETECTORS ARE TO BE HARD WIRED 2 - -
IN SERIES W/ BATTERY BACKUP.
3 - -
NOTE!
4 - -
FIRE BLOCK STUD SPACES AT SOFFITS, FLOOR AND 8. OMISSIONS IN AND/OR CONFLICTS
CEILING JOIST LINES, AT 10 FT. HORIZONTALLY AND
VERTICALLY AT FLOOR AND CEILING LINES, AND AT BETWEEN THE VARIOUS ELEMENTS OF THE 5 - -
OPENINGS BETWEEN ATTIC SPACES AND CHIMNEY CONTRACT DOCUMENTS SHALL BE BROUGHT
SPACES FOR FACTORY-BUILT CHIMNEYS, AND AT ANY Sheet Title:
OTHER LOCATIONS NOT SPECIFICALLY MENTIONED
TO THE IMMEDIATE ATTENTION OF THE
WHICH COULD AFFORD PASSAGE FOR FLAMES.
IRC R30211
DESIGNER AND SHALL BE RESOLVED
BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
A2.2
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
ROOF PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0 NOTE: NOTE:
ROOF DRAWING IS SCHEMATIC ONLY TRUSS ALL ROOF STACKS, AND PENETRATIONS SHALL
MANUFACTURER SHALL SUPPLY ALL PROJECT ABOVE THE ROOF BY THE MINIMUM
CALCULATIONS AND DETAILS PER CITY REQUIRED BY CODE AND BE LOCATED IN AREAS
REQUIREMENTS. NOT VISIBLE FROM THE STREET.
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
02 02
Project:
A4.0 A4.0
RIDGE
CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
Client:
ROOF NOTES Project Info: Custom Plan
DRAWINGS
24" BOTH SIDES OF VALLEYS, RIDGES,
TRANSITIONS AND EXTENDING 18"
INTERIOR OF WALL AT EAVES.
Stamp:
Drawing Information:
3. COLOR OF ALL EXPOSED VENTS AND ROOF Project Number: 1101-001-17
STACKS TO MATCH ADJACENT ROOF Project Manager: DLG
Revision:
A2.3
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
(OPTIONAL)
FIREPLACE EXHAUST VENT W/ SPARK
ARRESTER PER MANUFACTURER
(FIELD VERIFY EXACT LOCATION)
12 12
9 9
205
SMOOTH FINISH PLASTER SMOOTH FINISH PLASTER
(COLOR / STYLE TO BE (COLOR / STYLE TO BE
DETERMINED BY OWNER) DETERMINED BY OWNER)
8'-0"
8'-0"
TOP OF FLOOR TOP OF FLOOR © COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
EL = 110.229' EL = 110.229' OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
TOP OF PLATE TOP OF PLATE
EL = 109.00' EL = 109.00'
9'-0"
9'-0"
(FIELD VERIFY EXACT
LOCATION) FINISHED GRADE
(6" MIN. SLOPE IN FIRST
FRONT ELEVATION
02
Project:
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
PRELIMINARY CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
DRAWINGS
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
TEL 801.372.2950
TOP OF PLATE TOP OF PLATE
EL = 118.229' EL = 118.229'
211 212
8'-0"
Client:
Project Info: Custom Plan
101
9'-0"
9'-0"
FINISHED GRADE FINISHED GRADE
(6" MIN. SLOPE IN FIRST (6" MIN. SLOPE IN FIRST
10'-0" AWAY FROM 10'-0" AWAY FROM
STRUCTURE TO ALLOW FOR STRUCTURE TO ALLOW FOR
STORM WATER DRAINAGE) STORM WATER DRAINAGE)
Stamp:
TOP OF FLOOR TOP OF FLOOR
EL = 100.00' EL = 100.00' Drawing Information:
Project Number: 1101-001-17
Project Manager: DLG
Project Engineer
Date: 05-22-2018
1 - -
2 - -
3 - -
4 - -
5 - -
REAR ELEVATION
01 SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
*
NOTE:
WINDOWS/DOORS ON LEFT OR RIGHT ELEVATIONS OF UNIT
SHALL BE INSTALLED ON STREET FACING UNITS ONLY. NO
WINDOWS/DOORS ON END UNITS TO BE INSTALLED IF
WITHIN 5'-0" FROM ANOTHER UNIT OR WITHIN 5'-0" OF
Sheet Title:
A3.1
PROPERTY LINE. FIELD VERIFY CONDITIONS.
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
(OPTIONAL)
FIREPLACE EXHAUST VENT W/ SPARK
9:12 9:12 ARRESTER PER MANUFACTURER
(FIELD VERIFY EXACT LOCATION)
METAL SIDING
(COLOR / STYLE TO BE
DETERMINED BY OWNER)
200
* 201
* 202
* 204
* METAL SIDING
(COLOR / STYLE TO BE
DETERMINED BY OWNER)
8'-0"
8'-0"
TOP OF FLOOR TOP OF FLOOR © COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
EL = 110.229' EL = 110.229' OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
TOP OF PLATE TOP OF PLATE
EL = 109.00' EL = 109.00'
* * *
HOSE BIB
9'-0"
FINISHED GRADE FINISHED GRADE
(6" MIN. SLOPE IN FIRST (6" MIN. SLOPE IN FIRST
RIGHT ELEVATION
02
Project:
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
PRELIMINARY CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
DRAWINGS
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
TEL 801.372.2950
GRAY (NON-REFLECTIVE) GRAY (NON-REFLECTIVE)
METAL SIDING
(COLOR / STYLE TO BE
DETERMINED BY OWNER)
206
* 207
* 209
* 210
* METAL SIDING
8'-0"
8'-0"
Client:
(COLOR / STYLE TO BE
DETERMINED BY OWNER)
104
*
9'-0"
9'-0"
FINISHED GRADE FINISHED GRADE
(6" MIN. SLOPE IN FIRST (6" MIN. SLOPE IN FIRST
10'-0" AWAY FROM 10'-0" AWAY FROM
STRUCTURE TO ALLOW FOR STRUCTURE TO ALLOW FOR
STORM WATER DRAINAGE) STORM WATER DRAINAGE)
Stamp:
TOP OF FLOOR TOP OF FLOOR
EL = 100.00' EL = 100.00' Drawing Information:
Project Number: 1101-001-17
Project Manager: DLG
Project Engineer
Date: 05-22-2018
1 - -
2 - -
3 - -
4 - -
5 - -
LEFT ELEVATION
01 SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
*
NOTE:
WINDOWS/DOORS ON LEFT OR RIGHT ELEVATIONS OF UNIT
SHALL BE INSTALLED ON STREET FACING UNITS ONLY. NO
WINDOWS/DOORS ON END UNITS TO BE INSTALLED IF
WITHIN 5'-0" FROM ANOTHER UNIT OR WITHIN 5'-0" OF
Sheet Title:
A3.2
PROPERTY LINE. FIELD VERIFY CONDITIONS.
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
NOTE:
NOTE:
INSPECTION REQUIRED ON EXTERIOR
ALL FLASHING SHALL MEET SECTION R703.8
WEATHER BARRIERS AND FLASHING
OF THE 2015 IRC AND SHALL MEET SECTION
PRIOR TO INSTALLATION OF EXTERIOR
1403.2 AND 1405.3 OF THE 2015 IBC
CLADDING
PRELIMINARY
R-49 MIN. (FILL CAVITY)
-SEE RES CHECK
DRAWINGS
WEATHER BARRIER REQ'D. UNDER
TOP OF PLATE SIDING, ETC. TOP OF PLATE
EL = 118.229' (GRACE ULTRA, HENRY BLUE SKIN EL = 118.229'
160 OR EQUAL) 1 1
INSULATION
2"SHEETROCK WITH 2" SHEETROCK WITH AT EXTERIOR WALLS
EXTERIOR CLADDING PAINTED FINISH PAINTED FINISH - SEE RES CHECK
(SEE PLANS FOR MATERIAL) 2X4 WOOD FRAMED WALL. W/ (2) 2X4
WINDOW TOP PLATE & 2X4 P.T. BOTTOM PLATE
8'-0"
8'-0"
8'-0"
BLOWN-IN INSULATION WEATHER BARRIER REQ'D. UNDER
6'-8"
AT EXTERIOR WALLS VEST LAUNDRY BATH SIDING, ETC.
R-21 - SEE RES CHECK (GRACE ULTRA, HENRY BLUE SKIN
200 202 207
2X WOOD FRAMED WALL. W/ (2) 2X 160 OR EQUAL)
TOP PLATE & 2X BOTTOM PLATE EXTERIOR CLADDING
- SEE STRUCTURAL DRAWINGS (SEE PLANS FOR MATERIAL)
STRUCTURAL SHEATHING STRUCTURAL SHEATHING
TOP OF FLOOR -PER STRUCTURAL DRAWINGS -PER STRUCTURAL DRAWINGS TOP OF FLOOR © COPYRIGHT 2017:
EL = 110.229' EL = 110.229' REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
TOP OF PLATE TOP OF PLATE PURPOSE IS STRICTLY PROHIBITED
EL = 109.00' WEATHER BARRIER REQ'D. UNDER 1 WEATHER BARRIER REQ'D. UNDER EL = 109.00'
SIDING, ETC. 2" SHEETROCK WITH SIDING, ETC.
1
2"SHEETROCK WITH PAINTED FINISH
(GRACE ULTRA, HENRY BLUE SKIN (GRACE ULTRA, HENRY BLUE SKIN
PAINTED FINISH
160 OR EQUAL) 160 OR EQUAL)
EXTERIOR CLADDING EXTERIOR CLADDING
9'-0"
9'-0"
-PER PLAN
9'-0"
Project:
POLYMER-MODIFIED ASPHALT POLYMER-MODIFIED ASPHALT
TEL 801.372.2950
INSPECTION REQUIRED ON EXTERIOR
ALL FLASHING SHALL MEET SECTION R703.8
WEATHER BARRIERS AND FLASHING
OF THE 2015 IRC AND SHALL MEET SECTION
PRIOR TO INSTALLATION OF EXTERIOR
1403.2 AND 1405.3 OF THE 2015 IBC
CLADDING
8'-0"
8'-0"
Client:
BEDROOM 200 CLOSET CLOSET
WEATHER BARRIER REQ'D. UNDER - WEATHER BARRIER REQ'D. UNDER
SIDING, ETC. 210 - - SIDING, ETC.
(GRACE ULTRA, HENRY BLUE SKIN 1 (GRACE ULTRA, HENRY BLUE SKIN
160 OR EQUAL) 2"SHEETROCK WITH 160 OR EQUAL) Project Info: Custom Plan
PAINTED FINISH
EXTERIOR CLADDING STAIRS EXTERIOR CLADDING
(SEE PLANS FOR MATERIAL) (SEE PLANS FOR MATERIAL)
105
STRUCTURAL SHEATHING STRUCTURAL SHEATHING
TOP OF FLOOR -PER STRUCTURAL DRAWINGS -PER STRUCTURAL DRAWINGS TOP OF FLOOR
EL = 110.229' EL = 110.229'
TOP OF PLATE TOP OF PLATE
EL = 109.00' WEATHER BARRIER REQ'D. UNDER 1 WEATHER BARRIER REQ'D. UNDER EL = 109.00'
SIDING, ETC. 2" SHEETROCK WITH SIDING, ETC.
1
2"SHEETROCK WITH PAINTED FINISH
(GRACE ULTRA, HENRY BLUE SKIN (GRACE ULTRA, HENRY BLUE SKIN
PAINTED FINISH
160 OR EQUAL) 160 OR EQUAL)
EXTERIOR CLADDING EXTERIOR CLADDING
6'-8"
(SEE PLANS FOR MATERIAL) (SEE PLANS FOR MATERIAL)
9'-0"
9'-0"
GARAGE PWDR
BLOWN-IN INSULATION INSULATION
103 104 AT EXTERIOR WALLS
AT EXTERIOR WALLS
R-21 - SEE RES CHECK - SEE RES CHECK
2X WOOD FRAMED WALL. W/ (2) 2X 2X4 WOOD FRAMED WALL. W/ (2) 2X4
4" THK CONCRETE SLAB TOP PLATE & 2X4 P.T. BOTTOM PLATE
TOP PLATE & 2X BOTTOM PLATE
W/R-15 RIGID INSULATION 6 MIL. - SEE STRUCTURAL DRAWINGS
- SEE STRUCTURAL DRAWINGS
VAPOR BARRIER & 4" GRAVEL MIN.
2x PRESSURE TREATED SILL PLATE SET ON 2x PRESSURE TREATED SILL PLATE SET ON
TOP OF FLOOR SILL SEALER AND ATTACHED TO SILL SEALER AND ATTACHED TO TOP OF FLOOR Stamp:
EL = 100.00' FOUNDATION BY 10" ANCHOR BOLTS PER FOUNDATION BY 10" ANCHOR BOLTS PER EL = 100.00' Drawing Information:
ENGINEER W/SPACING OF 32" (TYP) O.C. w/ ENGINEER W/SPACING OF 32" (TYP) O.C. w/ Project Number: 1101-001-17
NUTS AND WASHERS, MIN 2 PER PIECE. NUTS AND WASHERS, MIN 2 PER PIECE. Project Manager: DLG
START ANCHOR BOLTS 1'-0" FROM EACH START ANCHOR BOLTS 1'-0" FROM EACH Project Engineer
CORNER 7" MIN EMBEDMENT. CORNER 7" MIN EMBEDMENT. Date: 05-22-2018
TOP OF FOOTING TOP OF FOOTING
FINISHED GRADE - 6" MIN. FINISHED GRADE - 6" MIN. Revision:
SLOPE IN FIRST 10'-0" AWAY SLOPE IN FIRST 10'-0" AWAY MRK DESCRIPTION DATE
FROM STRUCTURE TO ALLOW FROM STRUCTURE TO ALLOW 1 - -
FOR STORM WATER DRAINAGE FOR STORM WATER DRAINAGE
2 - -
REINFORCED CONCRETE REINFORCED CONCRETE
FOUNDATION WALL FOUNDATION WALL 3 - -
5
-
-
-
SEE PLAN SEE PLAN SEE PLAN FOR SEE PLAN FOR SEE PLAN SEE PLAN
SHOWER DOOR AND
FOR SWING FOR SWING SLIDE SLIDE FOR SWING FOR SWING
SURROUND, SEE PLANS
DIRECTION DIRECTION
FOR LAYOUT AND SIZE
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
TYPE A TYPE B TYPE C OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
FOLD LINE
FOLD LINE
SLIDE SLIDE
TYPE HH TYPE JJ
03 DOOR SCHEDULE
ROOM NAME & No.
DOOR
TYPE WIDTH HEIGHT THICK HEAD HT
(A.F.F.)
OPERATION GLAZING SCRN MATRL FINISH
FRAME
TYPE MATRL FINISH
DETAILS
HEAD SILL JAMB
FIRE RATING HRDWR TYPE NOTES 02 GLAZING SCHEDULE
GLAZING
THICKNESS INSULATED TEMPERED LAMINATED DESCRIPTION
SURFACE TREATMENT
ONE TWO THREE FOUR
INSULATED
01 WINDOW SCHEDULE
ROOM NAME & No.
WINDOW
TYPE WIDTH HEIGHT HEAD HT
(A.F.F.)
OPERATION GLAZING SCRN MATRL INT
FINISH
EXT
FINISH
DETAILS
HEAD SILL JAMB
NOTES
A 1/4" - - - - - - - - GLAZING
Project:
B 1/4" - YES - - - - - -
**
100 100 ENTRY FF 3'-0" 6'-8" 1 34" 6'-8" SWING E GLASS PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY 101 103 GARAGE B 3'-0" 3'-0" 6'-8" AWNING F - VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
**
1 34" CONTRACTOR & ALL SUB
102 103 GARAGE CC 3'-0" 6'-8" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - 20 MIN. - SEE ELEVATION -FIELD VERIFY 103 101 LIVING B 3'-0" 3'-0" 6'-8" AWNING F - VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
CONTRACTORS WORKING ON THIS
E
SURFACE THREE
3/4" YES YES - LOW E - LOW E - -
SURFACE FOUR
3 PROJECT TAKE FULL LIABILITY OF
SURFACE TWO
E
SURFACE ONE
103 103 GARAGE CC 5'-0" 6'-8" 1 4" 6'-8" FRENCH - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY 104 104 PWDR B 3'-0" 3'-0" 6'-8" AWNING - VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
THESE PLANS AND SHALL
F 3/4" YES - - LOW E - LOW E - -
THOROUGHLY REVIEW AND VERIFY
104 104 PDWR EE 2'-6" 6'-8" 1 34" 6'-8" POCKET - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY
ALL DIMENSIONS, LOCATIONS,
G 3/4" YES YES - LOW E, TRANSLUCENT - LOW E - - NOTES, ETC. PRIOR TO STARTING
*
EXT INT
105 103 GARAGE GG 3'-0" 6'-8" 1 34" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY ANY STAGE OF CONSTRUCTION.
3 THREE PANEL
106 100 ENTRY JJ 9'-0" 6'-8" 1 4" 6'-8" SLIDING E GLASS PAINT - WOOD PAINT - - - - - SEE ELEVATION -FIELD VERIFY
**
3
203 204 BATH DD 2'-8" 6'-8" 1 4" 6'-8" BARN SLIDING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY
3. PROVIDE SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION AND INSTALLATION.
C. GLAZING IN FIXED PANELS ADJACENT TO SLIDING OR SWING DOORS.
D. GLAZING IN SHOWER DOORS AND ENCLOSURES.
200 209 BEDROOM B 3'-0" 3'-0" 6'-8" AWNING F VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
** E
NOT USED IS LESS THAN 60" ABOVE ADJACENT FLOOR OR WALKING SURFACE. 202 207 BATH SEE ELEVATION -FIELD VERIFY
TEL 801.372.2950
- - - - - - - - - - - - - - - - - - - 5. SASH SIZE SHALL BE 138" U.N.O. B 3'-0" 3'-0" 6'-8" AWNING VINYL - VINYL - - -
G. GLAZING IN FIXED PANELS HAVING AN AREA IN EXCESS OF 9 SQ. FT.
AND THE LOWER EDGE LESS THAN 18" ABOVE A WALKING SURFACE
3 6. ALL EXTERIOR FRENCH DOOR TO HAVE CASEMENT INTER-SASH GLAZING AND SCREENS.
206 202 LAUNDRY AA 3'-0" 6'-8" 1 4" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY WITHIN 36" 203 NOT USED - - - - - - - - - - - -
H. GLAZING IN RAILINGS REGUARDLESS OF HEIGHT ABOVE WALKING
*
SURFACE WITH SECTION 2406.4 (8) EXCEPTIONS. 203 MASTER
207 207 BATH AA 2'-6" 6'-8" 1 34" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY J. GLAZING IN WALLS AND FENCES USED AS A BARRIER FOR INDOOR 204 B 3'-0" 3'-0" 6'-8" AWNING F VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
BEDROOM
AND OUTDOOR SWIMMING POOLS AND SPAS.
203 MASTER DOUBLE
208 209 BEDROOM AA 3'-0" 6'-8" 1 34" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY K. GLAZING IN WALLS ENCLOSING STAIRWAY LANDINGS OR 60" OF THE 205 A 6'-0" 6'-0" 8'-0" F VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
BOTTOM AND TOP STAIRWAY WHERE THE BOTTOM EDGE OF THE BEDROOM CASEMENT
GLASS IS LESS THAN 60" ABOVE THE WALKING SURFACE.
**
3
209 210 BEDROOM AA 3'-0" 6'-8" 1 4" 6'-8" SWING - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY 206 105 STAIRS B 3'-0" 3'-0" 6'-8" AWNING E VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
210 201 HALL CC 4'-0" 6'-8" 1 34" 6'-8" FRENCH - WOOD PAINT - WOOD PAINT - - - NR - SEE ELEVATION -FIELD VERIFY 207 200 VEST B 3'-0" 3'-0" 6'-8" AWNING E VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
-
211 208 SHWR BB 2'-0"± 7'-0"± 7'-0"± SWING D GLASS - - NONE - - - - NR - SEE ELEVATION -FIELD VERIFY 208 NOT USED - - - - - - - - - - - - - -
** 209 F
210 BEDROOM B 3'-0" 3'-0" 6'-8" AWNING VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
* NOTE:
WINDOWS/DOORS ON LEFT OR RIGHT ELEVATIONS OF UNIT SHALL BE INSTALLED ON STREET FACING
UNITS ONLY. NO WINDOWS/DOORS ON END UNITS TO BE INSTALLED IF WITHIN 5'-0" FROM ANOTHER UNIT
OR WITHIN 5'-0" OF PROPERTY LINE. FIELD VERIFY CONDITIONS.
210
211
210 BEDROOM
210 BEDROOM
B
C
3'-0"
3'-0"
3'-0"
6'-0"
6'-8"
8'-0"
AWNING
CASEMENT
F
F
VINYL
VINYL
-
-
VINYL
VINYL
-
-
-
-
-
-
SEE ELEVATION -FIELD VERIFY
212 209 BEDROOM C 3'-0" 6'-0" 8'-0" CASEMENT F VINYL - VINYL - - - SEE ELEVATION -FIELD VERIFY
Client:
Project Info: Custom Plan
Stamp:
Drawing Information:
Project Number: 1101-001-17
Project Manager: DLG
Project Engineer
Date: 05-22-2018
Revision:
PRELIMINARY
MRK DESCRIPTION DATE
1 - -
2 - -
3 - -
4 - -
DRAWINGS
5 - -
Sheet Title:
A5.0
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
2x PRESSURE TREATED SILL PLATE SET
WEATHER RESISTANT BARRIER
(4) 12" LVL STRINGERS ON SILL SEALER
(FOR SPANS UP TO 8 FT.)
(1) 2 X 12 AT EACH SIDE, AND ICE AND WATER SHIELD FLASHING
GYPBOARD
A DOUBLE 2 X 12 AT CENTER 4" CONCRETE SLAB W/ FIBERMESH TO EXTEND BEHIND CONC. CAP
HEADROOM HEIGHT
REINFORCING ON 6 MIL. VAPOR
FLEXABLE WATER CONN
BARRIER AND 6" MIN. COMPACTED
6'-8" MIN.
2X STUDS GRANULAR FILL. PROVIDE 2" R-10
1 1/4" MIN. RIGID INSULATION JOINT AROUND
2 5/8" MAX. PER PLAN
1 1/2" ENTIRE SLAB PERIMETER Z METAL FLASHING
HARDWOOD
HANDRAIL- SILICONE CAULK
RETURN TO
STAIR NOSING
EACH END 4" CONC SLAB.
SEE PLAN
(9" MIN.)
PROVIDE 2X TANK TO BE A
BLOCKING AT MINIMUM OF 6"
SEE PLAN
(8" MAX.)
EACH BRACKET AWAY FROM WALLS
WATER
3
4" WOOD TREADS HEATER
& RISERS SIMPSON STRONG TIE OR
METAL BRACKET EQUAL STRAPPING REQUIRED
@ 6'-0" O.C. CONT. 2 X 4 P.T. FOR WATER HEATER SEISMIC
MAX. W/ 2 1/4" X 2" 5 TIE DOWNS
8" TYPE "X"
SCREWS TO BLOCKING
GYPBOARD AT
USABLE SPACE
UNDER STAIRS
STAIRWAY LANDINGS SHALL
HAVE A MINIMUM DIMENSION FLEXABLE GAS CONNECTION
MEASURED IN THE DIRECTION OF REINFORCED CONCRETE FOUNDATION
TRAVEL OF 36" (IRC R311.4.3) WALL © COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
-SEE STRUCTURAL DRAWINGS OF THESE PLANS FOR ANY
ANCHOR WATER PURPOSE IS STRICTLY PROHIBITED
HEATER TO FLOOR
MIN.
18"
6'-8" MIN.
CODES AND OUTSIDE OF THE BUILDING) R-49 MIN. -SEE RES CHECK
MANUFACTURER'S -PROVIDE CODE APPROVED METAL DRIP EDGE
FLOOR FRAMING SMART VAPOR BARRIER
-PER STRUCT. DWGS INSTRUCTIONS CONDENSATE DRAIN
1
2" SHEETROCK WITH PAINTED FINISH
PRESSURE SPECIFY INDOOR OR O/ 4 MIL VAPOR BARRIER (WARM SIDE)
RELIEF TANKLESS OUTDOOR UNIT BLOWN-IN INSULATION DRYWALL BACKING
VALVE AS REQUIRED
WATER AT EXTERIOR WALLS
SEE PLAN HEATER POWER 120 VOLTS R-21 - SEE RES CHECK
(9" MIN.)
(REFER TO MANUFACTURER 2X WOOD FRAMED WALL. W/ (2) 2X TOP
HOT SPECIFICATIONS) PLATE & (2) 2X P.T.BOTTOM PLATE
Project:
SEE PLAN
(8" MAX.)
TEL 801.372.2950
EXTERIOR CLADDING
Client:
B-VENT PIPE CORNER 7" MIN EMBEDMENT.
AROUND ENTIRE SLAB PERIMETER
HEADROOM HEIGHT
DOUBLE JOIST WALL APPLICATION. HORIZONTAL NAILING STRIPS OR MRK DESCRIPTION DATE
1. ALL WALLS AND CEILINGS ARE TO RECEIVE GYPSUM BOARD FINISH. CENTER. NAILS SHALL PENETRATE
LATERAL 1-1/2 INCHES INTO STUDS, STUDS
2 - -
2. BASE DETAIL IS TO BE A 41" REVEAL ACHIEVED USING A "ZIP STRIP".
STAIRWAY LANDINGS SHALL 3. ALL WINDOW JAMBS HEAD AND SILL ARE TO BE WRAPPED IN GYPSUM BOARD. AND WOOD SHEATHING COMBINED 3 - -
HAVE A MINIMUM DIMENSION 4. ALL WALLS AND CEILING ARE TO RECEIVE A GYPSUM BOARD PRIMER PRIOR OR BLOCKING 4 - -
MEASURED IN THE DIRECTION OF TO PAINTING. -IRC R703.4
TRAVEL OF 36" (IRC R311.4.3) 5 - -
Sheet Title:
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
INSPECTION REQUIRED ON EXTERIOR ALL FLASHING SHALL MEET SECTION
WEATHER BARRIERS AND FLASHING R703.8 OF THE 2015 IRC AND SHALL
WEATHER RESISTIVE BARRIER PRIOR TO INSTALLATION OF MEET SECTION 1403.2 AND 1405.3 OF
(CHECK LOCAL BUILDING CODE FOR EXTERIOR CLADDING THE 2015 IBC
REQUIREMENTS)
GRACE UNDERLAYMENT
(OR EQUAL)
VARIES
LIGHT FIXTURE
(PER PLAN) EXPOSED WALL COVERING CORNER PATCH AS REQUIRED
12" FDN WALL BELOW -PER PLAN
GARAGE DOOR - PER PLAN
- PER PLAN
12" MIN. DISTANCE FROM BITUTHENE FLASHING
LIGHT FIXTURE
GYP. BOARD
16"± SHELF - PER PLAN
(REF)
INSULATION METAL STEP FLASHING
1"± HANGING ROD DOOR STOP AS REQ'D
(REF) - PER PLAN SILL PLATE
2X TRIM BOARD
STANDING SEAM WALL SHEATHING
CLOTHES HANGER W/ METAL WRAP
METAL ROOF COVERING -PER STRUCTURAL
(REF)
6'-0"±
-PER PLAN
WALL SHEATHING
SHEATHING
2X FRAMING - PER STRUCTURAL
-PER STRUCTURAL WEATHER RESISTIVE BARRIER
WEATHER RESISTIVE BARRIER (CHECK LOCAL BUILDING CODE FOR
(CHECK LOCAL BUILDING CODE FOR SIDING REQUIREMENTS)
REQUIREMENTS) -PER PLAN
(2) LAYERS GRACE UNDERLAYMENT
EXTERIOR CLADDING (OR EQUAL) W/ CORROSION
- PER PLAN RESISTANT FASTENERS © COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
BENT METAL TRIM PURPOSE IS STRICTLY PROHIBITED
(TYP AROUND EACH SIDE OF WINDOW) NOTE:
NOTE:
STRUCTURAL ROOF DECK ALL FLASHING SHALL MEET SECTION
INSPECTION REQUIRED ON EXTERIOR
-PER STRUCTURAL R703.8 OF THE 2015 IRC AND SHALL
WEATHER BARRIERS AND FLASHING
MEET SECTION 1403.2 AND 1405.3 OF
PRIOR TO INSTALLATION OF
THE 2015 IBC
EXTERIOR CLADDING
2"±
WINDOW
GYP. BOARD METAL
SHEATHING - PER PLAN
- PER PLAN FLASHING
- PER STRUCTURAL
ROOF
EXTERIOR CLADDING DECK
- PER PLAN BENT METAL TRIM WEATHER RESISTIVE BARRIER 2
(TYP AROUND EACH SIDE OF WINDOW) (CHECK LOCAL BUILDING CODE FOR
BASE BOARD REQUIREMENTS) 4
-PER FINISH SPEC. 1
2X FRAMING
2X FRAMING GYP. BOARD CORNER PATCH AS REQUIRED
- PER STRUCTURAL
- PER STRUCTURAL PROVIDE BLOCKING - PER PLAN
AS REQUIRED BITUTHENE
BITUTHENE FLASHING
Project:
INSULATION FLASHING
AS REQ'D WOODEN
- PER PLAN 3 TAPERED FURRING STRIP
WOOD CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
PROJECT TAKE FULL LIABILITY OF
SILL PLATE SILL PLATE THESE PLANS AND SHALL
-PER PLAN
GRACE UNDERLAYMENT STANDING SEAM
(OR EQUAL) METAL ROOF COVERING WALL SHEATHING WALL SHEATHING
TEL 801.372.2950
- PER PLAN RESISTANT FASTENERS
- PER STRUCTURAL NOTE:
BENT METAL TRIM
EXTERIOR CLADDING ALL FLASHING SHALL MEET SECTION NOTE:
(TYP AROUND EACH SIDE OF WINDOW)
-PER PLAN R703.8 OF THE 2015 IRC AND SHALL INSPECTION REQUIRED ON EXTERIOR
WEATHER RESISTIVE BARRIER NOTE:
MEET SECTION 1403.2 AND 1405.3 OF WEATHER BARRIERS AND FLASHING
(CHECK LOCAL BUILDING CODE FOR NOTE: INSPECTION REQUIRED ON EXTERIOR
THE 2015 IBC PRIOR TO INSTALLATION OF
REQUIREMENTS) CORTEN / PLATE METAL MUST WEATHER BARRIERS AND FLASHING
EXTERIOR CLADDING
BE IN ADVANCED STAGE OF PRIOR TO INSTALLATION OF
FLUSH BASE BOARD BENT METAL WINDOW TRIM PATINA PRIOR TO INSTALLATION
FLASHING @ VERTICAL SIDE WALL WINDOW SILL PAN FLASHING
EXTERIOR CLADDING
Client:
WEATHER BARRIERS AND FLASHING R703.8 OF THE 2015 IRC AND SHALL (CHECK LOCAL BUILDING CODE FOR R703.8 OF THE 2015 IRC AND SHALL
PRIOR TO INSTALLATION OF MEET SECTION 1403.2 AND 1405.3 OF REQUIREMENTS)
MEET SECTION 1403.2 AND 1405.3 OF
EXTERIOR CLADDING THE 2015 IBC THE 2015 IBC
Project Info: Custom Plan
WEATHER EXTERIOR
RESISTIVE 3 SHEATHING
STANDING SEAM SILL SEAL SILL PLATE BARRIER
METAL SIDING 5
2 TAPE SILL PLATE
1
CORNER PATCH AS
BITUTHENE FLASHING REQ'D.
2
(ASSEMBLED WINDOW ) 1
4 2
INSULATION ANCHOR BOLTS 2
-PER STRUCTURAL FOUNDATION WALL
AS REQ'D Stamp:
4 - -
5 - -
NOTE:
INSPECTION REQUIRED ON EXTERIOR
Sheet Title:
WEATHER BARRIERS AND FLASHING
PRIOR TO INSTALLATION OF
10 DETAIL
SCALE = N.T.S. 07 FOUNDATION SILL PLATE FLASHING
SCALE = N.T.S. 04 DOOR FLASHING
SCALE = N.T.S. 01 WINDOW FLASHING
SCALE = N.T.S.
EXTERIOR CLADDING
A6.1
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
INTERIOR SIDE:
ONE LAYER 5/8" TYPE "X" GYPSUM WALLBOARD, WATER
RESISTANT GYPSUM BACKING BOARD, OR GYPSUM
VENEER BASE APPLIED PARALLEL OR AT RIGHT
ANGLES TO STUDS W/ 6d COATED NAILS, 1-7/8" LONG,
0.0915" SHANK, 1/4" HEADS, 7" O.C.
EXTERIOR SIDE:
ONE LAYER 5/8" TYPE "X" GYPSUM SHEATHING APPLIED
STND. GYPSUM BOARD PARALLEL TO 2 X 6 WOOD STUDS @ 16" O.C. WITH 6d
COATED NAILS, 1-3/4" GALVANIZED ROOFING NAILS 4"
O.C. AT VERTICAL JOINTS AND 7" O.C. IN INTERMEDIATE
STUDS AND TOP AND BOTTOM PLATES. OVER
STRUCTURAL SHEATHING (SEE STRUCT. PLANS)
JOINT OF GYPSUM SHEATHING MAY BE LEFT
2X WOOD STUDS
UNTREATED. EXTERIOR CLADDING TO BE ATTACHED
THROUGH GYPSUM SHEATHING TO STUDS AS
REQUIRED.
INT. EXT.
INT. INT.
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
Project:
ATTIC ACCESS TO
+1" OF INSULATION LEVEL
STND. GYPSUM BOARD
CONTRACTOR & ALL SUB
1" RIGID INSULATION CONTRACTORS WORKING ON THIS
2X WOOD STUDS PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
SOUND BATT INSULATION ANY STAGE OF CONSTRUCTION.
-TYP. WHERE INDICATED
ACCESS PANEL
DRAW ACCESS PANEL SNUG
TEL 801.372.2950
INTERIOR STUD WALL @ TILE ATTIC ACCESS DETAIL
05 SCALE = N.T.S. 02 SCALE = N.T.S.
Client:
2X WOOD FRAMED WALL. W/ (2) 2X TOP
PLATE & (2) 2X P.T.BOTTOM PLATE - SEE
STRUCTURAL DRAWINGS Project Info: Custom Plan
INSULATION Stamp:
6" MAX.
PANEL OR WOOD SIDING) SHALL
2" MIN.
MRK DESCRIPTION DATE
TERMINATE @ BENT METAL
1 - -
FLASHING 6" MAX. ABOVE GRADE.
3" X 4" KEY FOR SLAB AT TOP OF
2 - -
FOUNDATION WALL (TYP ALL
AROUND) 3 - -
PORCH
-
A 9'-0"±
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
ENTRY
A 9'-0"
STAIRS A 9'-0"
105
02 02
Project:
A4.0 PWDR KITCHEN A4.0
104 102
TEL 801.372.2950
GARAGE
103
A 9'-0"
Client:
Project Info: Custom Plan
Stamp:
Drawing Information:
Project Number: 1101-001-17
Project Manager: DLG
Project Engineer
CEILING TAG Date: 05-22-2018
PRELIMINARY
X x'-x" Revision:
1 - -
A4.0 FINISH TYPE
2 - -
4 - -
Sheet Title:
-
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
MASTER
BEDROOM
A VAULT
BATH
204
STAIRS
HALL A VAULT
105
201
A VAULT
SHWR
02 LAUNDRY 208 02
Project:
A4.0 202 A4.0
A VAULT
CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
VEST PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
200 ALL DIMENSIONS, LOCATIONS,
BATH NOTES, ETC. PRIOR TO STARTING
A VAULT ANY STAGE OF CONSTRUCTION.
207
A VAULT
BEDROOM BEDROOM
210 209
A VAULT A VAULT
Stamp:
Drawing Information:
Project Number: 1101-001-17
Project Manager: DLG
Project Engineer
CEILING TAG Date: 05-22-2018
X x'-x" Revision:
PRELIMINARY
1 - -
A4.0 FINISH TYPE
2 - -
4 - -
A8.1
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
FIRST LEVEL FLOOR FINISH PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
PORCH
-
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
ENTRY
STAIRS
105
02 02
Project:
A4.0 PWDR KITCHEN A4.0
104 102
TEL 801.372.2950
GARAGE
103
Client:
Project Info: Custom Plan
Drawing Information:
1 - -
A4.0
2 - -
3. CARPET
3 - -
4 - -
Sheet Title:
-
A9.0
4. POLISHED CONCRETE
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
SECOND LEVEL FLOOR FINISH PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
MASTER
BEDROOM
203
BATH
204
STAIRS
105 HALL
201
SHWR
02 LAUNDRY 208 02
Project:
A4.0 202 A4.0
200 207
Client:
210 209
Drawing Information:
2. HARDWOOD Revision:
PRELIMINARY
1 - -
A4.0
2 - -
3. CARPET
3 - -
4 - -
A9.1
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
FIRST LEVEL ELECTRICAL PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
PORCH
-
GFI/WP
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
SS SS PURPOSE IS STRICTLY PROHIBITED
3
S ENTRY
BRACE FOR
FUTURE FAN
DATA
STAIRS
105
C SMOKE/Co2
S
ALARM
PROVIDE UNDER
CABINET OUTLET FOR
DISPOSAL- SWITCH PER PROVIDE UNDER
OWNER CABINET OUTLET FOR
DISHWASHER
GFI
GFI
SS
GFI
02 02
PROVIDE MAKEUP AIR AS REQ'D
Project:
A4.0 PWDR IF RANGE HOOD EXHAUSTS IN KITCHEN A4.0
EXCESS OF 400 CFM
104 ( VERIFY WITH HOOD SPECS) 102
SS GFI GFI
F.D.
TEL 801.372.2950
GARAGE
103
GFI
GFI GFI
Client:
AUTOMATIC GARAGE DOOR OPENERS IF PROVIDED
SHALL BE TESTED IN ACCORDANCE WITH UL325. (R309.6)
GFI/WP
ELECTRICAL NOTES
S
PRELIMINARY
Revision:
Sheet Title:
-
DATA
PURPOSE IS STRICTLY PROHIBITED
203 BRACE FOR
FUTURE FAN
SS
3
90 CFM
S
SHWR
GFI
SSS
C SMOKE/Co2
S
ALARM 205
BATH
STAIRS 204
105 HALL
GFI
201
SS
3
02 LAUNDRY 208 02
Project:
A4.0 202 A4.0
SS
VEST THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
200 BATH NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
207
TEL 801.372.2950
S
ALARM ALARM
S SMOKE S SMOKE
BEDROOM BEDROOM
Client:
DATA
DATA
210 209
BRACE FOR
FUTURE FAN
BRACE FOR
FUTURE FAN ELECTRICAL NOTES
Project Info: Custom Plan
BEDROOM ELECTRICAL CIRCUIT BEDROOM ELECTRICAL CIRCUIT 1. ARC-FAULT CIRCUIT INTERRUPTERS ARE REQUIRED
TO BE ARC FAULT PROTECTED TO BE ARC FAULT PROTECTED ON ALL BRANCH CIRCUITS THAT SUPPLY 125-VOLT,
SINGLE PHASE, 15- AND 20-AMP RECEPTACLE
OUTLETS, LIGHTS, SWITCHES, AND SMOKE
DETECTORS IN DWELLING UNIT BEDROOMS (IRC
SECTION E3082.11).
PRELIMINARY
1 - -
A4.0 MANUFACTURER'S REQUIRMENTS. 2 - -
7. ALL EXTERIOR LIGHTING TO BE RECESSED CANS IN
3 - -
EAVES/SOFFITS.
4 - -
E1.1
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
FOOTING / FOUNDATION PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01
A4.0
22'-0"
6'-0"
6'-0"
FDN STEP UNEXCAVATED FDN STEP
EL = 99.50' EL = 99.50'
© COPYRIGHT 2017:
2'-1"
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
DOOR LOCATION
3'-0"
OPT. F.P.
KEY
24'-0"
(TYP ALL AROUND)
TOP OF FLOOR
18'-11"
EL = 100.00'
ROUGH-IN
02 FOR SINK 02
ROUGH-IN
Project:
FOR BATH
A4.0 A4.0
53'-0"
53'-0"
CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
ANY STAGE OF CONSTRUCTION.
TEL 801.372.2950
16'-7"
23'-0"
23'-0"
UNEXCAVATED
Client:
DOOR LOCATION
6'-5"
DOOR LOCATION
GENERAL NOTES
1. ICF (FOX BLOCK) FOUNDATION WALLS
Drawing Information:
3. ALERT DG DRAFTING & DESIGN AND Project Number: 1101-001-17
PRELIMINARY
01 MRK DESCRIPTION DATE
1 - -
A4.0 5. SEE COVER SHEET FOR DRAWING INDEX
2 - -
THE IDEAS, CONCEPTS , DETAILS, FLOOR PLANS & 6. OMISSIONS IN AND/OR CONFLICTS 3 - -
ELEVATIONS ARE COPYRIGHTED AND ARE THE
EXCLUSIVE PROPERTY OF BETWEEN THE VARIOUS ELEMENTS OF THE 4 - -
DRAWINGS
5 - -
S1.1
BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
801.557.6711 | www.dgdraftinganddesign.com
Stock Plans | Custom Design | Drafting Services
DG Drafting & Design
SECOND FLOOR FRAMING PLAN
SCALE 1/8" = 1'-0" (11 X 17 PAPER) OR
1/4" = 1'-0" (22 X 34 PAPER)
01 FRAMING PLAN NOTES
A4.0
ALL JOISTS ARE 16" FLOOR TRUSSES OR
EQUIVALENT UNLESS SPECIFIED
OTHERWISE.
CONTRACTOR IS RESPONSIBLE TO
CHECK FRAMING LAYOUT FOR CONFLICT
WITH MECHANICALS, PLUMBING, ETC.
PRIOR TO ASSEMBLY.
02 02
Project:
A4.0 A4.0
TEL 801.372.2950
Client:
PRELIMINARY GENERAL NOTES
Project Info: Custom Plan
1. 2X WALLS
DRAWINGS
START LAYOUT
2. 2X BEARING WALLS
@ 16" O.C.
4 - -
9. OMISSIONS IN AND/OR CONFLICTS
BETWEEN THE VARIOUS ELEMENTS OF THE 5 - -
© COPYRIGHT 2017:
REPRODUCTION OF ANY PORTION
OF THESE PLANS FOR ANY
PURPOSE IS STRICTLY PROHIBITED
CIS
Project:
A4.0 A4.0
SO
RT
CONTRACTOR & ALL SUB
CONTRACTORS WORKING ON THIS
RU
PROJECT TAKE FULL LIABILITY OF
THESE PLANS AND SHALL
SSE
THOROUGHLY REVIEW AND VERIFY
ALL DIMENSIONS, LOCATIONS,
NOTES, ETC. PRIOR TO STARTING
S@
ANY STAGE OF CONSTRUCTION.
RIDGE
24"
TEL 801.372.2950
Client:
Project Info: Custom Plan
GENERAL NOTES
PRELIMINARY 1. 2X WALLS
2. 2X BEARING WALLS
TRUSS DESIGN PACKAGE TO ENGINEER 6. SEE COVER SHEET FOR DRAWING INDEX Drawing Information:
4 - -
9. OMISSIONS IN AND/OR CONFLICTS
BETWEEN THE VARIOUS ELEMENTS OF THE 5 - -