Moisture and particulate matter can greatly affect pressure function and longevity. Environmental exposure to water ranges from "condensing"
moisture to wash-down with water under pressure to total and permanent submersion.
Defined by two types of enclosure classification rating systems: National Electronic Manufacturers Association (NEMA) ratings and Ingress
Protection (IP) ratings.
These systems define protection from solids and liquids entering an enclosure.
An IP rating considers only protection against ingress of solid foreign objects and ingress of water, while NEMA ratings consider these
and other specifics such as corrosion and construction details.
It is possible to say that a NEMA type is equivalent to an IP rating, but it is not possible to say that an IP rating is equivalent to a NEMA type. The
comparison of NEMA and IP enclosure ratings is only approximate. It is the responsibility of the user to verify the enclosure rating necessary for the
given application.
NEMA Ratings
NEMA 1: General Purpose – Indoors
Intended for general purpose indoor use, primarily to provide a degree of ingress protection against contact with the enclosed
equipment or locations where unusual service conditions do not exist
NEMA 2: Drip Proof – Indoors
Intended for general purpose indoor use, primarily to provide a degree of protection against limited amounts of falling water and dirt
NEMA 3: Dust tight, rain tight, and ice/sleet resistant – indoors/outdoors
Intended for general purpose outdoor use, primarily to provide a degree of protection against windblown dust, rain, and sleet
Will be undamaged by the formation of ice on the enclosure
NEMA 3R: Rain proof and ice/sleet proof – indoors/outdoors
Intended for general purpose outdoor use, primarily to provide a degree of protection against falling rain
Will be undamaged by the formation of ice on the enclosure
NEMA 3S: Dust tight, rain tight, and ice/sleet – outdoors
NEMA 4: Water tight and dust tight – indoors/outdoors
Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental
contact with the enclosed equipment
Provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water
NEMA 4X: Water tight, dust tight, and corrosion resistant – indoors/outdoors
Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental
contact with the enclosed equipment.
Provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water
Protection of corrosion resistance
NEMA 5: General purpose dust tight
Intended for use indoors or outdoors with protection from dust provided by gaskets
NEMA 6: Submersible, water tight, dust tight, and ice/sleet resistant – indoors/outdoors
Intended for general purpose indoor and outdoor use primarily to provide a degree of protection against the entry of water
during temporary submersion at a limited depth
Will be undamaged by the formation of ice on the enclosure
NEMA 7: Underwriters Lab Class 1 – Groups C & D – explosion proof – indoors
Intended for indoor use in locations classified as Class I, Groups A, B, C, or D, as defined in the National Electrical Code
Capable of withstanding the pressures resulting from an internal explosion of specified gases and containing such an
explosion sufficiently that an explosive gas-air mixture existing in the atmosphere surrounding the enclosure will not be
ignited.
Enclosed heat-generating devices shall not cause external surfaces to reach temperatures capable of igniting explosive gas-
air mixtures in the surrounding atmosphere
Enclosures shall meet explosion, hydrostatic, and temperature design tests
NEMA 8: Underwriters Lab Class I – Groups C & D – explosion proof – indoors
Same as NEMA 7, except the unit is oil-immersed
NEMA 9: Underwriters Lab Class II – Groups E, F, G – indoors
Intended for special-purpose indoor use in locations classified as hazardous (Class II, Groups E, F, and G, as defined in the
National Electric Code)
Capable of preventing the entrance of dust
Enclosed heat-generating devices shall not cause external surfaces to reach temperatures capable of igniting or discoloring
dust on the enclosure or igniting dust-air mixtures in the surrounding atmosphere
Enclosures shall meet dust penetration and temperature design tests and aging of gaskets (if used)
NEMA 11: Corrosion resistant and drip proof – oil immersed – indoors
NEMA 12: dust tight and drip tight – indoors
Constructed (without knockouts) to provide a degree of protection to personnel against incidental contact with the enclosed
equipment
Intended for industrial indoor use, primarily to provide a degree of protection against dust, falling dirt, and dripping
noncorrosive liquids
NEMA 13: Oil tight and dust tight – indoors
Intended for industrial indoor use, primarily to provide a degree of protection against dust, spraying of water, oil, and
noncorrosive coolant).
The comparison of NEMA and IP enclosure ratings is only approximate. It is the responsibility of the user to verify the
enclosure rating necessary for the given application
IP ratings
The the Ingress Protection system is more commonly used in Europe but is increasingly used in the U.S. as well. Because the two systems use
different test parameters, they are not directly comparable or easily converted.
The IP rating system provides a means of classifying the degree of protection from solid objects and liquids afforded by electrical equipment and
enclosures. The system is recognized in most European countries and is set out in a number of British and European standards. These include:
Classification of Degrees of Protection Provided by Enclosures, BS (British Standards) 5490:1977; IEC (International Electrotechnical Commission)
529:1976.
The first number defines the level of protection against penetration of solid objects into the housing. The second number defines the level of
protection against penetration of liquids into the housing.