Professional Documents
Culture Documents
Substation Event Analysis Using Information From Intelligent Electronic Devices
Substation Event Analysis Using Information From Intelligent Electronic Devices
www.elsevier.com/locate/ijepes
Abstract
The data acquisition capability of processor-based relays and intelligent electronic devices (IEDs) can improve reliability and reduce the global
cost of the power system. Nevertheless, the quantity and complexity of the captured data is beyond the requirements of most utilities, particularly
when ones consider their immediate operational needs. Though the data acquisition process has been highly automated, the process of assimilating
and analysing data still lags behind. Raw data must be transformed into knowledge in order to help users decide how to respond to the event and
implement the necessary actions. A promising technique for substation event analysis using rough set theory is described in this paper. It interprets
the data and outputs meaningful and concise information, which improves the performance of a data analysis system and help with the knowledge
acquisition process. A 132/11 kV substation model was developed to generate various fault scenarios for our case studies to evaluate the
performance of the rough set algorithm. The results show that it works well and efficiently with the overwhelming data.
q 2006 Elsevier Ltd. All rights reserved.
Keywords: Intelligent electronic devices (IEDs); Data overwhelm; Knowledge extraction; Rough set theory; Discernibility functions; Fault events
1. Introduction of plant and its substation, but also, at the system operational
level [3]. The paper focuses on ‘system’ instead of ‘device’
Processor based IEDs can improve the reliability of the data analysis and formulates a technique that converts available
power network and reduce lifetime operating costs. Never- data to knowledge for decision-support.
theless, the quantities of data acquired, particularly during a Fig. 1 shows the impact of information overload that leads
major incident, can overwhelm an operator and lead to an to the decrease in our decision quality and accuracy. The
incorrect response [1]. Operators have to analyse the available burden of heavy information load can confuse the individual,
data and apply the most appropriate remedial action. Emotional affect his ability to set priorities, or makes prior information
and psychological stress may result in an inadequate response harder to recall [4].
that could damage equipment, risk human life or even initiate a
catastrophic emergency [2]. What we require is useful
information that summarises the problem and helps with the 2. Information flow
solution. The data acquired in a substation come from a
multitude of sources but often carry the same information. This The terms data and information are often used synonymously,
but they are not the same. Data describes what was collected
creates superfluous and/or redundant information, which
through observation and inference. Information describes what
makes the analytical task harder to achieve. To improve the
was produced when data is analysed and organised.
speed of data handling, the data must be grouped and unified.
Fig. 2 shows the steps required to convert raw data into
The data overwhelm issue not only has an impact on each piece
useful information before it can actually be used as knowledge.
Fig. 3 presents a future digital control system (DCS) integrated
* Corresponding author. with an information management unit (IMU) that is used to
E-mail address: c.hor@lboro.ac.uk (C.L. Hor). deliver useful information to appropriate manpower groups in a
0142-0615/$ - see front matter q 2006 Elsevier Ltd. All rights reserved. utility. Each group uses the monitored data for a different purpose
doi:10.1016/j.ijepes.2005.12.010 and consequently has varied information requirements.
C.L. Hor, P.A. Crossley / Electrical Power and Energy Systems 28 (2006) 374–386 375
Fig. 1. Decision accuracy versus information overload. It is impossible to test all scenarios because real data from
the control centre and IEDs are difficult to obtain. To partially
solve this problem, a typical 132/11 kV substation given in
Fig. 4 and its associated feeders has been simulated using
PSCAD/EMTDC [6].
The model includes the primary plant and the secondary
protection [7] and control systems. Bus-coupler BC is assumed
closed during normal operating conditions. To prevent both
transformers tripping when a fault occurs on the 11 kV
terminals of a transformer, the directional overcurrent and
earth fault relays (DOC/DEF), i.e. {IED5 and IED6} are set to
look into their respective transformers (IEEE nomenclature
67). These relays also include non-directional time graded
earth fault elements (50, 51N) for the protection of the 11 kV
busbar and backup of the overcurrent and earth fault relays
(OC/EF), i.e. {IED1, IED2, IED3 and IED4} on the outgoing
feeders [8]. Both 132 kV feeders are protected by overcurrent
Fig. 2. Information flow diagram.
(OC) and earth fault relays (EF) which may also include
Balanced Earth Fault (not shown in Fig. 4). The 132/11 kV
transformers are protected by restricted earth fault (REF) and
biased differential unit protection (BDF) [9]. A selection of
fault scenarios was applied to the simulator. For each scenario,
Table 1
Data availability by device types
A B C D E F G H I J K L M N O P
SER ! ! ! ! ! # # # # ! # * ! ! ! !
DFR # # # # # # # # # ! # # # # # #
SCADA # # # # # ! * * # * * ! ! ! ! !
RELAYS # # # # # * * # ! # * # # # # #
#: data available, !: data not available,: partial data may not available in some form. SER, sequence events recorder; DFR, digital fault recorder; SCADA,
supervisory control and data acquisition system.
the operating response of the relays, circuit breakers and verified. Real-time data in power system always contains
voltage and current sensors are recorded and stored in an event mixed types of data, such as analogue values and digital data.
database. All these data contain useful information that could provide us
There are many types of IEDs, which could provide data for with a good picture about the supervised network in a safe and
solving different problems. The operational data required unsafe condition. For qualitative reasoning, the voltages and
analysing the performance of the relay systems and circuit currents parameters need to be discretised into three categories:
breakers during a fault on the electrical system are [3]: ‘normal (N)’, ‘high (H)’ and ‘low (L)’. The discretisation
determines how coarsely we want to view the raw data. It is
A. Bus phase voltages formulated as P : R/ C assigning a class c 2C to each value
B. Bus residual voltage r 2R in the domain of the attribute being discretised [12]. The
C. Line phase voltages normal operating range for voltage is typically 90–110% of the
D. Line phase currents nominal voltage. To categorise the disturbances, a threshold is
E. Line residual current set for the voltage and current signals [13]:
F. Pilot channel data
G. Breaker, station tripping and blocking status † The voltage thresholds:
H. Control contact performance (i) Low (L)!90% of the nominal voltage
I. Alarm contacts (ii) 90%!Normal (N)!110%
J. Relay target data (iii) High (H)O110%.
K. Time coded information † The current thresholds:
L. Fault duration (i) Low (L)!50% of nominal current
M. Clearing time (all phases) (ii) 50%!Normal (N)!150%
N. Magnitude of the fault current (iii) High (H)O150%.
O. Type of fault
P. Phases involved in the fault Sometimes the real-time data received may oscillate a lot.
If this happens close to the threshold, it will lead to a flood
Table 1 compares different devices types for the availability of events. The problem can be reduced by defining hysteresis
of the given set of data. values, i.e. 1% hysteresis for voltage threshold and 10% for the
Relays provide most of the information and the main current threshold.
exception is the alarm contacts. Since our interest lies on lower
level data analysis rather than higher-level alarm processing, 5. Information system
the absence of the alarm contacts is not important. Further-
more, relays have become the preferred recording system over Information system or knowledge representation system can
the years. The cost of adding other types of recording systems be perceived as a two-dimensional data table with sets of data
may not be justified if the use of relays as the source of data can represented by rows. Each row corresponds to a case or event
meet the goals [10]. Thus, protection IED is seen as the main and each column represents an attribute, which could be a
data source for us. There are two types of data in an IED relay, variable, an observation or a property. The table is filled with
i.e. operational and non-operational [11]. What we are attributes values. A set of attributes, i.e. voltage, current logged
interested is the operational data that could help us in fault in 1 ms time tag represents a set of operational situations in the
analysis. substation. Each of the attributes has a value set as normal (N),
high (H) or low (L).
4. Discretisation Table 2 describes a simplified dataset, which is composed of
a set of discrete voltages and currents over a time period of
The power system state changes over time as the event 0.139–2.012 s. It can be considered as a pair of finite and non-
evolves. It is important to determine the condition of the empty set (U, A) as an information table. U is the universe of
system based on the real-time data collected from IEDs. This objects and A is the set of attributes {IED1, IED2, IED5,
normally requires manipulating and processing a large volume IED7} assuming that the bus-coupler is open and only a partial
of data and information before the status of the system can be single busbar system of Fig. 4 is considered. Each attribute
C.L. Hor, P.A. Crossley / Electrical Power and Energy Systems 28 (2006) 374–386 377
Table 2 Table 3
Information system Protection status of IED1
6. Protection status
For a circuit breaker, the value set is either open (1) or close
(0). To capture more information about the breaker status, we
utilise its auxiliary contacts (52A, 52B): ‘00 (breaker failed)’,
‘01 (closed)’, ‘10 (opened)’ and ‘11 (unknown)’. Table 3
presents the protection trip data, which merge with Table 2 to
describe the entire events, occurred. Relay IED1 has operated
whilst the other relays remain unchanged. The auto-recloser
(AR) has been disabled to simplify the example. Relay IED1 Fig. 5. Schematic diagram of the upper and lower approximation of set X.
378 C.L. Hor, P.A. Crossley / Electrical Power and Energy Systems 28 (2006) 374–386
7.1. Indiscernibility
Table 7 Table 9
Reducts Change of states
Index IED1 IED2 IED5 IED7 Index IED1 IED2 IED5 IED7
No. I1 V2 I2 V5 I5 V7 I7 No. I1 V2 I2 V5 I5 V7 I7
1 N N N N N N N 1 N N N N N N N
2 N L N L N N N 2 † L † L † † †
3 H L N L N N N 3 H † † † † † †
4 H L N L H N H 4 † † † † H † H
5 H L L L H N H 5 † † L † † † †
6 L L N L N N N 6 L † N † N † N
7 L N N L N N N 7 † N † † † † †
8 L N N N N N N 8 † † † N † † †
9 H L N L H N N 9 † † N † † † N
Index Time, t (s)
1 0.139 8. Case studies
2 1.002
3 1.003, 1.004, 1.128, 1.985, 2.108, 3.367, 3.492, 5.172, 5.048 The following case studies discuss how rough set theory can be
1.005, 1.007, 1.008, 1.009, 1.125, 1.127, 1.987, 1.988, used to interpret substation data using unsupervised classification.
4 1.989, 1.990, 1.992, 2.105, 2.107, 3.368, 3.369, 3.372,
The approach requires no predefined classes or priori knowledge
3.373, 3.488, 5.049, 5.051, 5.053, 5.054, 5.168
to discover new relations between the data. It is able to perform
1.012, 1.014, 1.022, 1.117, 1.118, 1.122, 1.123, 1.124,
5 1.994, 1.995, 2.003, 2.097, 2.098, 2.102, 2.103, 2.104,
data clustering automatically. The events collected from the
3.377, 3.374, 3.385, 3.481, 3.482, 3.484, 3.487, 5.058, 132/11 kV substation are time-tagged in every 1 ms and thus,
5.066, 5.161, 5.162, 5.164, 5.167 only the results are presented. In these case studies, the currents
6 1.130, 1.132, 2.110, 2.112, 3.365, 3.494, 5.046, and voltages are regarded as separate entities.
5.047, 5.174
7 1.137, 1.984, 2.117, 3.366, 3.502, 5.181
8 1.156, 2.136, 3.520, 5.200
9. Permanent fault on the load feeder L1
9 3.491, 5.171
This section considers a three phase fault (F2) at 1.0 s on the
feeder L1. The reducts computed is given in Table 7. For
checking purpose, let us take a look at the time index. The
Table 8
Protection status
rest, i.e. IED2, IED5 and IED7 are normal. Referring to the
voltage V5 at time 1.156, 2.136, 3.520, and 5.200 s (see Index 8),
it indicates a recovery after the opening of BRK1. However, it
dropped to low after BRK1 was reclosed on the faulty feeder.
Based on the logic data in Table 8, we can conclude that the
fault was permanent. Table 7 was thus condensed to Table 9 as
a summary of the events represented as follows:
Station report
Date of event 13/08/04 Event number 11:20:12 am
Time of event 001 Sample rate 1 ms
Event description
Feeder L1: current (H) at 1.003 s.
Feeder L2: current (L) at 1.012 s, voltage (L) at 1.002 s.
Feeder L5: current (H) at 1.005 s, voltage (L) at 1.002 s.
Feeder L7: current (H) at 1.005 s.
IED1: tripped multiple times.
Breaker: BRK1 opened multiple times.
Loss of supply: feeder L1.
Protection system operation analysis
Relay IED1 Types 79, 50/51, 50/51N
First pickup (s) 1.003, 1.985, 3.367, 5.048
Primary (s) 1.022, 2.003, 3.384, 5.065
Backup N/A
Status Healthy Breaker state Healthy
Recloser Yes Number 3
Reclose time 1.902s, 3.283s, 4.964s, N/A
Status Healthy No. breakers 1 (BRK1)
Breaker (s) 1.102, 2.083, 3.464, 5.145
Breaker time 0.08 s Breaker status 52A(1), 52B(0)
Estimated fault data
Fault inception 1.0 s Fault types A–B–C, permanent
Faulted section L1 Avg. duration z0.098s
Maximum fault 32.21 kA
Breaker contact wear 406.68!106 As
Line currents, voltages (faulted section)
RMS value Pre-fault Max. fault Post-fault Unit
In 0.000 0.000 0.000 (kA)
Ia 0.513 31.89 0.000 (kA)
Ib 0.513 31.98 0.000 (kA)
Ic 0.513 32.21 0.000 (kA)
Va 6.170 0.000 0.000 (kV)
Vb 6.140 0.000 0.000 (kV)
Vc 6.300 0.000 0.000 (kV)
Vab 10.86 0.000 0.000 (kV)
Vbc 10.58 0.000 0.000 (kV)
Vca 10.80 0.000 0.000 (kV)
382 C.L. Hor, P.A. Crossley / Electrical Power and Energy Systems 28 (2006) 374–386
Table 11 Table 12
Protection status Reducts
Fig. 12. Voltages of IED1, IED2, IED5 and IED7 against time.
Table 14
Station report
Station report
Date of event 01/10/04 Event number 23:12:06 pm
Time of event 002 Sample rate 1 ms
Event description
Feeder L1: current (H)Z1.004 s, voltage (L)Z1.004 s.
Feeder L2: current (L)Z1.012 s, voltage (L)Z1.004 s.
Feeder L5: current (H)Z1.007 s, voltage (L)Z1.004 s.
Feeder L7: current (H)Z1.007 s.
IED1: tripped at 1.011 s; resets at 1.115 s.
Breaker: BRK1 opened at 1.091 s.
Loss of supply: none. System restored after 5.045 s.
Protection system operation analysis
Relay IED1 Types 79, 50/51, 50/51N
First pickup (s) 1.004, 1.974, 3.344
Primary (s) 1.011, 1.981, 3.351
Backup N/A
Status Healthy Breaker state Healthy
Recloser Yes Number 3
Reclose time 1.891s, 3.261s, 4.931s
Status Healthy No. breakers 1 (BRK1)
Breaker (s) 1.091, 2.061, 3.431
Breaker time 0.08s Breaker status 52A(0), 52B(1)
Estimated fault data
Fault inception 1.0 s Fault types A–G, Transient
Faulted section L1 Avg. duration z0.087s
Maximum fault 32.99 kA
Breaker contact wear 284.1!106 As
Line currents, voltages (faulted section)
RMS value Pre-fault Max. fault Post-fault Unit
In 0.000 32.51 0.000 (kA)
Ia 0.513 32.99 0.513 (kA)
Ib 0.513 0.511 0.513 (kA)
Ic 0.513 0.490 0.513 (kA)
Va 6.170 4.770 6.120 (kV)
Vb 6.140 6.170 6.200 (kV)
Vc 6.300 6.020 6.290 (kV)
Vab 10.86 9.110 10.59 (kV)
Vbc 10.58 10.610 10.89 (kV)
Vca 10.80 9.080 10.76 (kV)
Time IED1 IED5 IED6 IED7 IED8 The challenge for the modern power system operation
t (s) V1 I1 V5 I5 V6 I6 V7 I7 V8 I8 and control is the ability to interpret the data correctly
0.139 N N N N N N N N N N from IEDs and ensure the right decision is reached.
1.002 L N N N N N N N N N Without good information, action is either impossible or
1.003 L N L N L N N N N N foolhardy.
1.005 L N L H L N N H N H
1.007 L N L H L H N H N H
This paper presented a fairly simple technique that
1.015 L L L H L H N H N H automatically processes large volumes of raw data, identifies
1.134 L N L H L H N H N H the most significant and meaningful data patterns and
1.139 L N L H L L N H L N presents this information in an appropriate and condensed
1.140 L N L N L L N N L L
form. This helps the operators grasp a good picture of the
1.153 N N L N L L N N L L
1.172 N N N N L L N N L L events during the emergency. Several different fault scenarios
were analysed using the event datasets from the simulated
network. The case studies were conducted to evaluate the
Table 17 algorithm and improve our understanding about substation
Change of states
data. Like most data analysis algorithm, the defective/
Time IED1 IED5 IED6 IED7 IED8 incorrect data might affect the quality of extracted knowledge
t/s V1 I1 V5 I5 V6 I6 V7 I7 V8 I8 particularly for those datasets that contain a high degree of
0.139 N N N N N N N N N N noises. Advanced filtering or other pre-processing techniques
1.002 L † † † † † † † † † are thus required.
1.003 † † L † L † † † † † Substation event processing and analysis using rough set
1.005 † † † H † † † H † H approach is a new research area that would certainly benefit
1.007 † † † † † H † † † †
1.015 † L † † † † † † † † power utilities. It offers us the insightful analysis about the
1.134 † N † † † † † † † † power system data by examining how the pattern changes.
1.139 † † † † † L † † L N
1.140 † † † N † † † N † L
1.153 N † † † † † † † † †
1.172 † † N † † † † † † † References
[12] Risvik. K. Discretization of numerical attributes tech. rep. 45073, [15] Pawlak Z. Rough set approach to knowledge-based decision support 14th
department of computer science and information science, Norwegian European journal of operational research, Jerusalem, Israel, July; 1995. p.
University of Science and Technology (NTNU), Trondheim, Norway; 48–57.
1997. Computer Science Project. [16] Skowron A, Rauszer C. Intelligent decision support—Handbook of
[13] Hor C, Crossley P. Substation data analysis with rough sets The eighth applications and advances of the rough sets theory The discernibility
international conference on developments in power system protection, matrices and functions in information systems. Dordrecht, New Haven:
Amsterdam, The Netherlands, April 5–8; 2004. Kluwer; 1992 p. 331–62.
[14] Komorowski J, Pawlak Z, Polkowski L, Skowron A. Rough fuzzy [17] Hor C, Crossley P. Analysis of substation data for knowledge extraction
hybridization—A new trend in decision making. In: Pal SK, Skowron A, IEEE power engineering society general meeting, San Francisco, USA,
editors. Rough sets: A tutorial. New York, USA: Springer; 1999. 12th–16th June; 2005.