Doc No.

: STPL/SAM/ABL/1
STPL DAILY DAIRY Rev No.:
Date of rev.:
0
11-10-12

Project : Sambalpur -Bargarh Orissa/Chattisgarh Border of NH 6


Client : Ashoka Sambalpur-Bargarh Tollway Pvt. Ltd.
Engineer : Sugam Technocrates Pvt. Ltd.

Section 1: Weather Report


a. Weather Clear Cloudy Foggy Rainy

b. Temperature (0C) Min. 28.6 Max. 31.2

c. Rainfall (mm) Nil

Section 2: Details of Activities Checked at Site


Sl. Checked
R.F.I no. Chainage Activities Remarks
No. by
1. STR/12/1095 31+300 VUP wall lift -2 M-35 Asst. B.E
Sr. B.E. & Workability of concrete is more
2. STR/12/1096/A 7+200 Girder-74 Concreting
Asst. B.E. instructed to control W/C ratio.
A-2 side P-8 pile concrete
3. STR/12/1093 7+200 Asst. B.E
Mahanadi
Shuttering is not in line
A-2 RE wall Final lift M-
4. STR/12/1094 9+895 Asst. B.E instructed to rectify before
25
concreting.
Railing beam casting
5. STR/12/1096 4+993 Asst. B.E Checked & found OK.
minor bridge
77+610
T.L. & Rate of spreading checked &
6. RWS/12/1812 to Tack Coat
Sr. M.E. found OK.
77+950
77+610
DBM laying and level T.L. &
7. RWS/12/1813 to
checking Sr. M.E.
77+950

Section 3: Details of Test Conducted in Laboratory


Sl. R.F.I no. Location Test Conducted Witnessed Remarks
No. by
1. Cast 9 no. DBM Mould for Sr. M.E./
Km. 14 Lab
JMF Verification. Lab Tech.
2 Crushed aggregate Sr. M.E./
FI+EI (40mm --- 16%, 10mm---35%
gradation, FI & EI (Nawa) Lab Tech

3 Crushed aggregate
Sr. M.E./ FI+EI (40mm --- 24%, 20mm---
gradation, FI & EI
Lab Tech 18%, 10mm---33%
(Pozzolana.)
Section 4: Observations & Recommendations:
It is observed that for Borrow Area Material used for Embankment & Sub-Grade Test for soluble
1. sulphate & total sulphate has not been conducted. It is recommended that the same should be
conducted on top priority. (Please refer Clause 305.2.1.3 of MORTH Specification.
M 45 Grade concrete for Precast Girder was being batched at Uttamcon Plant at Km. 7 Mahanadi
without moisture correction for sand, as a result concrete mix was produced at a slump of 160 mm.
2.
It was advised to the Material Engg. of Uttamcon to regularly make correction for moisture content.
So that design slumped should be maintained.

Team Leader,
Sugam Technocrates Pvt. Ltd.