1. High Speed Digital DSP Controller station battery. The power supply module is
2. Analog Measuring Module design using very advance PWM controller
3. Power supply Module which allow very wide input supply variation i.e.
4. Digital Input output module. 18V to 250VAC/DC covering 24Vdc, 30Vdc,
110Vdc and 220Vdc station battery
The High speed Digital Signal Controller
requirement.
continuously monitors phase, E/F current along
with different optical isolated status The relay is having total 4 nos of high intensity
connections. The high-speed micro-controller dual LED for easy identification of type of fault
samples these current signals through a A/D for easy user interface. All LEDs and control
converter. The Digital Signal performs output R1 to R4 are fully programmable via
powerful Numerical Algorithms to find out keypad interface
RMS of fundamental & harmonic contents of
Main Functions
the current then this value is used for protection
The ADR141C are having following protection
and metering function. All measurement is
functions.
tuned to fundamental frequency i.e 50Hz, thus
1. Non Directional phase Over current
relay remain stable during distorted waveform
element. (Ip>, and Ip>> )
generated electronics loco-motive. All these
2. Non Directional 3Io (Internally derived EF)
measure values are then used for different
(3Io> and 3Io>>).
protection function such as IDMT/DMT Over
3. Trip Circuit Super vision.
current protection, Instantaneous Over current
4. Breaker Failure Detection.
protection, Earth Fault protection, etc. These
5. Monitoring Functions.
measured values are also displayed on large
Each of these functions are independently
16 x 2 LCD display for metering purpose. The
programmable and can be enable or disable by
DSC also monitors different digital input
user depending upon requirement.
through optical isolator and perform some
monitoring function such trip circuit supervision,
Over Current & EF Element:
and control potential free contact for control CB
The ADR141C is member of Ashida Numerical
and generate ALARM and Tele-signalling
Relay family design for protection general
feeder. The relay has one stage of IDMT/DMT
The power supply module is basically DC – DC
setting and one stage of instantaneous setting.
converted designed using modern PWM based
(Ip>, IP>>, 3Io>, 3Io>>). All major international
Switching mode technique to convert station
IDMT curves are available. Range for first stage
battery supply to the 12V and 24Vdc low
is 10% to 200% and 50% to 3000% for
voltage supply for relay electronics and control
instantaneous stage for phase and 3Io.
circuit. It also provides necessary isolation from
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
B+
Although the curves tend towards infinite when TCCOM
1
6 To Relay CPU
the current approaches Is (general threshold), 2
S4
CB NO
the minimum guaranteed value of the operating
B-
1
current for all the curves with the inverse time 6 To Relay CPU
S3 2
TC
characteristic is 1.1Is (with a tolerance of ± CB NC
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
AM XXX–XX – X – X – XX – X
Auxiliary Supply
PT Secondary 01 = 18 – 52 V dc 04 = 30 V dc
0 = NO PT 02 = 77 – 250 V dc 05 = 48 V dc
03 = 24 V dc 06 = 18 – 250 V dc
CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable
AM XXX XX X
Over Current Earth Fault Relay
For Adity-V2 series start from 201. For V1 series refer respective document
201 01 Obsolete Version CSE – H – 150 3
201 02 Relay with standard Back Connection (not CSF – H – 136 3
Recommended)
201 03 Relay with Ring Type Back Connections CSF – H – 136 3
Ordering information:
A D R 1 4 1 C - A M - X X X - X X - X - X - X X - X
Example
AD R 1 4 1 C – AM - 2 0 1 - 0 2 - 3 - 1 - 0 6 - 0
T yp e : A D R 1 4 1 C
St. Back terminal layout
C a b i n e t T yp e : C S F - 1 5 0 H
Auxiliary Supply: 18-250Vdc
C T s e c : 1 Amp. / 5 Amp selectable
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5Amp. Or 1Amp site selectable
II. Aux. Supply : 18 - 250VDC.
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous carrying capacity : 2 x of rated for CT and 1.5 x of rated for PT
VII. Pick up : Within 1.1 times of set value.
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 4 Trip duty user assignable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO & 1 for CB NC
XII. Thermal With stand for CT : 20 x of rated for 3.0 sec.
General Settings
XIII. General setting : New PassWord 0 – 99 in steps of 1
: Unit Id 0 – 250 in steps of 1
: CT Sec 1A or 5A
: CT Primary 10 - 2000in steps of 10
: Test Block 01: YES, 02: NO
: Trip Ckt. 01: YES, 02: NO
:BF Enable 01: YES, 02: NO
: BF Delay 50-800 mS steps of 50ms
Relay Settings
XIV. Phase Section (Ip) : IP> Settings 10% – 250% in steps of 1%.
: IP> Time Multiplier (TMS) x0.01 – x1.00 in steps of 0.01
: IP> Curve (Operating Time) C1 – C6 ( IDMT curve C1 – C5 or Define
Time C6 )
: IP> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>> Settings 00% – 3000% insteps of 50% 00 means
block
: IP>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
XV. Earth Fault Section (3Io) : 3Io> Settings 10% – 250% insteps of 1%
: 3Io> Time Multiplier (TMS) x0.01 – x1.00 in step of 0.01.
: IE> Curve (Operating Time) C1 – C6 ( IDMT curve C1 – C5 or Define
Time C6 )
: 3IO> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3IO>> Settings 00% – 3000% insteps of 50% 00 means
block
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Environmental tests:
13. Cold test Storage test : IEC 60068-2-1
14. Dry heat test : IEC 60068-2-2
Damp heat test,
15. : IEC 60068-2-3
steady state
16. Damp heat test, cyclic : IEC 60068-2-30
Mechanical tests
: IEC 60255-21-1 class 1
: Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8
17. Vibration
m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
18. Bump Test : IEC 60255-21-2 Class-1
: 1000 bumps of 10gn peak acceleration and 16ms pulse
duration in each of the two opposite direction per axis as per
IEC 60255-21-2 class 1 No. of axes . 3.
19. Shock Withstand : IEC 60255-21-2 Clas-1
: 3 shocks of 15gn peak acceleration and 11ms pulse in each of
two opposite direction . No. of axis : 3
20. Seismic Test : IEC 60255-21-3
: In single axis sine sweep in X-axis
sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn
(whichever is less)
: In single axis sine sweep in Y-axis
- sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn
(whichever is less)
Revision Note
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.