Professional Documents
Culture Documents
Eeda 512 - Ac/Dc Machinery (Lecture) Lesson 3: Transformers and Regulators
Eeda 512 - Ac/Dc Machinery (Lecture) Lesson 3: Transformers and Regulators
Coils of transformers are wound with copper or aluminum wire or strap. For heavy-current windings, several strands of
conductor are paralleled to reduce eddy-current loss in the conductors.
Two basic types of transformer windings are commonly used. These are the concentric and the pancake types. Concentric
windings are cylindrical in form with one winding placed inside the other with the necessary insulation between them. The low-
voltage winding is normally placed on the inside next to but insulated from the core. Pancake windings are built up with primary
and secondary sections interleaved. In both types, spacers are provided between adjacent coils to permit ventilation or the circulation
of the cooling liquid.
RATINGS:
The output rating or capacity of a transformer is given in kilovoltamperes (kVA) since this is equivalent to specifying the load
current. The rated kilovoltamperes of a transformer is based on the maximum output that the transformer can deliver at rated
secondary voltage and rated frequency without exceeding a given temperature rise. Since power in ac circuit depends upon the power
factor of the load as well as the current flowing, an output rating in kilowatts would have to be at some stated power factor. For this
reason, transformers are rated in kilovoltamperes, which are independent of power factor.
Included on a transformer nameplate in addition to capacity and voltage rating data are the connection diagrams, percent
impedance, polarity data, cooling class, data on winding taps, and basic insulation level. Basic insulation level is an indication of the
ability of the insulation system to withstand transient overvoltages.
Transformers may be classified as distribution or as power transformers. The term distribution transformer, as generally
accepted, is applied to transformers rated 500 kVA and smaller. Transformers rated greater than 500 kVA are referred to as power
transformers.
Although transformers are highly efficient, some losses are present in all transformers. There are two classes of losses, namely,
load losses, which are principally I2R losses in the transformer windings, and no-load losses, which are primarily core losses. Load
losses can be calculated for any given load if the resistances of both windings are known or can be measured. If RH and RX are the
high- and low-voltage winding resistances, then the load loss is:
Load Loss = IH2 RH2 + Ix2 Rx
No-load or core losses are due to the effects of hysteresis and eddy currents in the iron core of the transformer. These effects
are similar to those occurring in generators and motors.
IV. SINGLE-PHASE and THREE-PHASE CONNECTIONS
SINGLE-PHASE CONNECTIONS:
Single phase transformers, like other electrical devices, may
be connected into series or parallel arrangements. For example,
distribution transformers are normally wound with the secondary
or low-voltage windings that can be connected in series or parallel.
The availability of primary voltages and the requirements of the
load dictate how the transformer will be wired. A single-phase
connection diagram is shown in Figure 3.5.
THREE-PHASE CONNECTIONS:
Single-phase transformer can be connected to form three-phase transformer banks for raising or lowering the voltages of three-
phase systems. Four common methods of connecting three transformers for three-phase transformations are the delta-delta, wye-
wye, wye-delta, and delta-wye connections. Connection diagrams for three-phase is shown in Figure 3.6.
The delta-delta connection is often used for moderate voltages. An advantage of this connection is that if one transformer
becomes damaged or is removed from the service the remaining two can be operated in what is known as the open-delta or V-
connection. By being operated in this way, the bank still delivers three-phase currents and voltages in their correct phase
relationships, but the capacity of the bank is reduced to 57.7 percent of what it was with all three transformers in service.
In the wye-wye connection, only 57.5 percent of the line voltage is impressed upon each winding, but full line current flows
in each transformer winding. Power circuits supplied from a wye-wye bank often create serious disturbances in communication
circuits in their immediate vicinity. Because of this and other disadvantages, the wye-wye connections is not as commonly used as
the other connections.
The delta-wye connection is well adapted for stepping up voltages since the voltage is increased by the transformer ratio
multiplied by the factor 1.732. Likewise wye-delta connection is used for stepping down voltages. The high-voltage windings of
most transformers operating at above 100,000 V are wye-connected.