VRV To AHU Connection: Application Guide
VRV To AHU Connection: Application Guide
Top secret
Secret
Internal use only
Public
1
6/8/2016
01. Basics
In this chapter we will learn about:
• How VRV can be useful for AHU air treatment
• What are the benefits of this application
• What possibilities do you have
THE BASICS
View: SECTION
2
6/8/2016
THE BASICS
What do you need to use VRV for cooling and heating the air in the AHU?
communication Thermistors
R410A liquid
R410A gas
THE BASICS
What are the benefits?
1) Immediate Cooling and Heating under any ambient or room conditions → less heat transfer losses,
fast and accurate response to load changes → better comfort and less energy consumption compared
to water cooling/heating coils coupled with chillers.
2) Better management of load for medium size spaces due to VRV technologies.
• Total solution: AHU can work together with other VRV indoor units in same system
• Extended operating range
• Accurate temperature control due to inverter capacity management
• Quick switchover between cooling & heating.
→ better comfort and wider possibilities compared to water systems and ON/OFF CCUs.
3
6/8/2016
THE BASICS
What are the configuration possibilities?
THE BASICS
What are the temperature control possibilities?
Ts (supply air Te (evaporator
Td (discharge air
temperature temperature
temperature
sensor) sensor)
sensor)
DDC controller
(AHU’s own
controller, collecting
data from sensors Return Air Supply Air
and forming capacity
demand signal) Tr (room air
temperature sensor)
X: Control of supply or return air temperature ( uses Td, Ts or Tr- all field supplied sensors)
with external controller (DDC) using an un-proportional 0~10 V algorithm for capacity control
Y: Control of evaporating/condensing temperature, indirect room temperature control (uses Te- Daikin supplied)
with 3rd party thermostat and Daikin controller BRC1D52 or BRC1E52A/B used for field settings and error indication
Z: Control of supply or return air temperature (uses Ts or Tr- Daikin or field supplied sensors)
with Daikin controller BRC1D52 or BRC1E52A/B used for control, field settings and error indication
W: Control of supply or return air temperature (uses Td, Ts or Tr- all field supplied sensors)
with external controller (DDC) using a proportional 0~10 V algorithm for capacity control
8 Title - Internal use only
4
6/8/2016
Allowed
coil
capacity, 5,0-6,2 6,3-7,8 7,9-9,9 10,0-12,3 12,4-15,4 15,5-17,6 17,7-24,6 24,7-30,8 35,4-49,5 49,6-61,6
kW
(cooling)
Allowed
coil
capacity, 5,6-7,0 7,1-8,8 8,9-11,1 11,2-13,8 13,9-17,3 17,4-19,8 19,9-27,7 27,8-34,7 39,8-55,0 55,1-69,3
kW
(heating)
5
6/8/2016
SELECTION PROCESS
Step 1. Calculate the required coil capacity, determine coil parameters and select expansion
valves
AHU selection software
Air flow
No, max. capacity for single circuit is 61,6 No, min. capacity for single circuit is 5
kW. You need to split your coil. kW. You need to go to 1 circuit coil.
SELECTION PROCESS
Step 2. Determine your system configuration and select control box(es) and outdoor units
6
6/8/2016
The EKEQ controller switches between What are the benefits? When to
capacity levels like this: use this type of control? It is
expensive to buy and setup…
If the voltage from DDC If the voltage from DDC
is increasing: is decreasing:
7
6/8/2016
Te/Tc control
3rd Party Thermostat EKEQF control box
ON/OFF signal
Te/Tc control
Voltage
Capacity Te setting Tc setting Approx. %
level
from DDC
(cooling) (heating) of capacity We can (though indirectly) set the
controller
% of system capacity by means of
Level 1 0,8 - - 0 (OFF) 0-10 V signal.
Level 2 2,5 13,50C 310C 40 Most of the AHU controllers
Level 3 5 110C 360C 60 available in the market are suitable
Level 4 7,5 8,50C 410C 80 for this without any additional
Level 5 9,2 60C 460C 100 programming.
8
6/8/2016
EKEQM
Daikin or 3rd Party Thermistor Superheat/subcool information
9
6/8/2016
• To control the temperature of the air leaving or • To control the temperature of the
returning to the AHU, by means of an external returning air to AHU by means of a
DDC device (X and W control) Daikin controller (Z control)
• To control indirectly the room air temperature
by fixing Te or Tc (Y control)
EKEQFCBA EKEQD
EKEXV class
EKEQ* EKEXV
63
Control Box Expansion Valve
80
communication 100
125
140
0-10 V
EXV control 200 Air Handling
250 Unit (AHU)
DDC Controller
Max +/-30 m
Max +/-5
m
Max. 5 m
Min 5 m, max. 50 m
R410A gas
EKEQFCBA
EKEQ* EKEXV
Expansion Valve EKEXV
Control Box class
communication 200
250
400
0-10 V
EXV control 500 Air Handling
Unit (AHU)
DDC Controller
Max +/-30 m
Max +/-5
m
Max. 5 m
Min 5 m, max. 50 m
R410A gas
VRV IV Heat Pump CH/Non-CH
Water cooled VRV
10
6/8/2016
F 1F 2 F 1F 2 F 1F 2
EKEXV class
EKEQFCBA EKEQFCBA EKEQFCBA
63
EXV control EXV control EXV control
80
0-10 V
100
125
DDC Controller
140
200
250 Interlaced coil (max. 3
400 circuits). Max. capacity =
500 50 kW x 3 = 150 kW
Thermistors
Piping length limitations are the same as for single circuit coils:
• OU → (each) EXV kit = 5..50 m
• EXV kit → AHU = 5 m max.
• Level difference between OU and AHU = 30 m max.
21 Title - Internal use only
CH/Non-CH EKEXV 80
Water 100
F1 F2 EKEXV 140
200
Only return air 250
temperature control 400
(Z) is possible. Like EKEQMCBA 500
VRV indoor units. P1P2
22
11
6/8/2016
DX Kit 1 DX
EKEQMCBA EKEXV
DX
EKEQMCBA EKEXV
Coil
(multi-
EKEQMCBA EKEXV circuit)
Outdoor N DX Kit 2
EKEQMCBA EKEXV
DX Kit 2
If for some reason you need to work with You can also connect several outdoor units to
more than 3-circuit coil with one outdoor 1 multi-circuit coil, but only in Z control mode.
unit, it is possible, but only in Z control Thus you can obtain theoretically unlimited
mode. capacity.
24
12
6/8/2016
COIL REQUIREMENTS
How to select DX coil properly?
Is the coil selected by AHU selection software suitable for VRV application?
Thank you
13