Known Data: H Z 2 I R S G

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

1.

Known Data
Length of lift wall=2.134m
breadth of lift wall=1.524m
Thickness of lift wall=0.18m
Opening width=0.914m
Live load = 4KN/m2

2. Lump Mass Calculation


Floor dead load live load total
basement 60.201 13.009 73.210
Ground Floor 110.369 13.009 123.378
First Floor 100.335 13.009 113.344
Second Floor 100.335 13.009 113.344
Third Floor 100.335 13.009 113.344
Fourth Floor 100.335 13.009 113.344
Fifth Floor 50.168 13.009 63.177
TOTAL 713.141

3. Calculation of Base Shear


Z I Sa
Ah = 2 ∗ R ∗ g

Z= Zone factor = 0.36 (From IS 1893 table 2 for zone V)


I=Importance factor = 1 (From IS 1893 table 6 for zone V)
Total height of lift, h = 15.24m
R = Response reduction factor = 5 (IS1893 table 7)
Sa/g is spectral acceleration depending upon time period:
T = 0.075h0.75= 0.578 Sec
Sa 1.36
= T (for medium soil) = 2.353 (From IS 1893 Cl 6.4.5 for zone V)
g
So, Ah = 0.09 m2/s
Total seismic weight of shear wall, Ws = 713.141 KN
Base shear, Vb = Ah*Ws = 64.183 KN

4. Lateral Load Calculation and Moment Calculation at Base


Design of Lift Shear Wall
Grade of concrete, fck = 25 N/mm2

Weight Wi h i2 Cum.
Hi Qi = Wi*H2 Qi  VB Moment
Floor W VB=Ah*W n Q
(KN)
(m) (KN)  Wj h 2
j (KN)
(KNm)
j1

Bm 73.210 0 64.183 0.000 0.000 0.000 480.610


GF 123.378 3.658 64.183 1650.556 1.216 1.216 476.163
1F 113.344 3.048 64.183 5096.521 3.754 4.970 461.016
2F 113.344 3.048 64.183 10782.722 7.942 12.912 421.662
3F 113.344 3.048 64.183 18574.924 13.681 26.593 340.606
F4 113.344 3.048 64.183 28473.126 20.972 47.565 195.628
5F 63.177 3.048 64.183 22561.547 16.618 64.183 0
TOTAL 713.141 87139.395 2375.688
Grade of steel, fy = 500 N/mm2

Reference Step Calculation Output


1 Known data:
Length of lift wall (along Y) =2.134 m Ly=2.134 m
Length of lift wall (along X) = 1.524 m Lx=1.524 m
Thickness of shear wall, t = 0.18m
Floor height, H = 3.048 m

2 Check for slenderness ratio


IS 456:2000 Effective height of wall,
Cl.32.2.4a Hwe=2.286 m
Hwe = 0.75H = 2.286 m
Hwe
Slenderness ratio, = 12.7 < 30
t

Eccentricity
IS 456:2000 3
Minimum eccentricity
Cl.32.2.3
emin = 0.05t = 9 mm emin = 9 mm

Additional eccentricity,
IS 456:2000
H2we ea =11.613 mm
Cl.32.2.2 ea = 2500∗t = 11.613 mm

4
IS 456:2000 Ultimate load carrying capacity per unit length
Cl.32.2.5 of wall, Puw=1094.805
Puw = 0.3(t-1.2emin-2ea)*fck = 1094.805 N/mm N/mm
5

Calculation for main vertical reinforcement


Assuming clear cover =25 mm
a Diameter of bar = 16mm
effective cover = 35 mm
When lateral load is acting along Y- direction;
length along Y direction = 2.134 m
Muy = Mu/2 = 2375.688/2 = 1187.844 KNm
Vuy = Vu/2 = 64.183/2 = 32.092 KN
Puy = Pu/2 = 713.141/2 = 356.141 KN
d'/D = 35/2134=0.016
Mu
= 0.058
D2 ∗b∗fck

u P
and, D∗b∗f = 0.037
ck

SP16 Pt
= 0.02
fck
chart 35
IS 456:2000 So, Pt = 0.5 % Pt = 0.5 %
Cl.32.5a Ast req = 0.5%*180*2134=1920.6 mm2 Astrq=1920.6mm2
Min.Ast required = 0.12%*180*2134 =460.94mm2
IS 456:2000 Number of bars of 16 mm bars required = 10 Nos. Astmin=460.94mm2
cl.32.5b
Spacing of bars
,Sv=(2134-35-16)/(10-1)=231.444 mm Sv=200 mm

Check for spacing of bars


𝐿
Maximum spacing of bars = Min of ( 5𝑤 ,3𝑡, 450)

= 426.8 mm
11-φ16@200mm
To take account of the reversal effect, provide
b 16mm bars @ 200 mm c/c on both faces of the
wall
When lateral load is acting along X- direction;
length along X direction = 1.676 m
Muy = Mu/2 = 2375.688/2 = 1187.844 KNm
Vuy = Vu/2 = 64.183/2 = 32.092 KN
Puy = Pu/2 = 713.141/2 = 356.141 KN
d'/D = 35/1524=0.023
Mu
= 0.094
D2 ∗b∗fck

u P
and, D∗b∗f = 0.047
ck
SP16
Pt
chart 35 = 0.033
fck
IS 456:2000 Pt = 0.825 %
So, Pt = 0.825 %
Cl.32.5a
Ast req = 0.825%*180*1676= 2488.6 mm2
Astrq=2488.6 mm2
2
Min. Ast = 0.12%*180*1676=362.02mm
IS 456:2000 Astm=362.02mm2
cl.32.5b Number of bars of 16 mm bars required = 13 Nos.
Spacing of bars ,Sv=(1676-35-16)/(13-1)
=135.417 mm Sv=120 mm
Check for spacing of bars
𝐿
Maximum spacing of bars = Min of ( 5𝑤 ,3𝑡, 450)

= (335.2, 540, 450 )mm


=335.2 mm
To take account of the reversal effect, provide
16mm bars @ 120mm c/c on both faces of the
wall.
6 14-φ16@120mm

Calculation of horizontal reinforcement:


Area of horizontal reinforcement = 0.2% of b*H
= 1097.28mm2
IS 456:2000
Provide ϕ 12 mm bar =113.04 mm2
cl 32.5c No of bars = 10 Nos.
Spacing of bars, Sv = 3048/(13-1)
= 254 mm 16-φ12@200mm
IS 456:2000 To take account of reversal effect, provide 12 mm
cl 32.5c
bars @ 200 mm c/c on the both sides of the wall.
7
a
Check for shear :
When lateral load acting along X- direction
Nominal shear stress,
Vu V u
τv = = t∗0.8∗L = 0.146 N/mm2
td w
IS 456:2000
cl.32.4.2.2 Allowable Shear stress,
τallow = 0.17fck = 4.25 N/mm2
IS 456:2000
i.e. 4.25 > τv. So OK
cl.32.4.2.1
Design shear strength of concrete:
Hw
= 1.819 > 1
Lw

Here,
K1 = 0.2
K2 = 0.045
IS 456:2000 τcw shall be lesser of:-
cl.32.4.3 H
τcw = (3 − L w )*K1*√fck = 1.181 N/mm2
w
H
( w +1)
Lw
τcw =K2*√fck ∗ H = 0.774 N/mm2
( w −1)
Lw

Take τcw =0.774 N/mm2


And τcw should not be less than 0.15*√fck = 0.75
N/mm2
Since, τcw > τv, the design is safe.
b
When lateral load acting along Y- direction
Nominal shear stress,
Vu V u
τv = = t∗0.8∗L = 0.104 N/mm2
td w

IS 456:2000 Allowable Shear stress,


cl 32.4.2 τallow = 0.17fck = 4.25 N/mm2
i.e. 4.25 > τv. So OK
IS 456:2000
Design shear strength of concrete:
cl.32.4.2.1
Hw
= 1.428 > 1
Lw

Here, K1 = 0.2
K2 = 0.045
τcw shall be lesser of:-
H
IS 456:2000 τcw = (3 − L w )*K1*√fck = 1.572N/mm2
w
cl.32.4.3
H
( w +1)
Lw
τcw =K2*√fck ∗ Hw =1.276N/mm2
( −1)
Lw
And τcw should not be less than 0.15*√fck = 0.75
N/mm2
Since, τcw > τv, the design is safe.