OMICRON TEST PROCEDURE

Normal distance: you can test point by point manual change


Advanced distance you can adjust ramp of testing points

1 / 14
U can make right click and test the point this menu will appear
Or u can write the value here and test

2 / 14
Here u can adjust the setting for your test
Prefault Max. fault current

3 / 14
Advanced distance
Shot if u want to make one point test
Check : for zone reach , timing test

Press parameter – hardware configuration

4 / 14
Press general - detail to check the connection

Press test opject

5 / 14
Enter your system data ( VIP)

You can select the direction for your test

6 / 14
Select zone setting
To add new zone click new then edit

Select the type of your char. Then enter the setting

7 / 14
Click default setting and adjust the current = 2A then click OK

8 / 14
Press sequence and enter your required ramps start , stop & step

9 / 14
RELAY MIN. PICKUP CURRENT
OPEN ADV.DISTANCE SCREEN
Select setting and change the fault current & Go to shot screen

Select impedance & click single test

10 / 14
High set
.State seq

.Make the first state ----- healthy 63.5 for 3 ph , 0A for 3 ph time 2 sec
The sec. state VR = 10V and other phases healthy time 2 sec
The third state change the value for IR around HS value=2In then test
Must adjust measurement view start at state 3 , stop at trip

11 / 14
2nd method Mcb trip Q7 & IF SOTF enable must AC SOTF pick delay=1
sec. INJECT one state 0 voltage for all phases , 10A IR & IS=IT=0

12 / 14
SOTF
ADV. DISTANCE & make DISTANCE fun. Enable
AC SOTF
Go to setting screen and adjust pre fault time case A=150msec case B
.=250 msec

And after this test impedance from shot screen and sheck SOTF LED
Case A : SOTF OPERATE
CASE B : SOTF NOT OPERATE

13 / 14
DC SOTF
Go to SEQUENCER screen
State 1: 63.5 V , 0 A for all phases
State 2 : fault state: VR=10V,VS=63.5, VT=63.5 , IR=5A, IS=0 , IT=0
and change the time for state 1
case A=350msec case B =450 msec and apply +ve to A26 CB CLOSE
through BO from Omicron
click here and select BO:1 for state 1 , state 2

14 / 14
Test the two cases

and check SOTF LED


Case A : SOTF OPERATE
CASE B : SOTF NOT OPERATE

VTS (voltage transformer supervision)


Setting Vres.=20 v , Ires. = 1.5 A
by using quick cmc
inject this values VR=VS=VT=63.5 V AND BALANCED
current = 0 for all phases &
Decrease the value of Vr to 43.5 V the led for VTS will be appeared
Increase IR UP TO 1.5 A the led will be disappeared
for phase S,T repeat the above state &

15 / 14
Blocking function
:Inject 3 states like this
healthy state vr=vs=vt =63.5 v , balanced & Ir=Is=It =0 , time =2 sec -1
drop the voltage of ph. R to 10V and remain the others phases like -2
state 1 time = 2 sec
increase the value of current Ir to 6A -3
The relay not trip

16 / 14