BMS - Point List
BMS - Point List
4
3
2
1
FAN
PAU
FCU
AHU
QUẠT
PUMPS
PUMPS
PUMPS
KHÔNG
SYSTEM
LẠNH SƠ
FCU/AHU
KHÍ/MVAC
QUẠT/FAN
LED WATER
KHÔNG KHÍ
DÀN LẠNH /
BƠM NƯỚC
BƠM NƯỚC
BƠM NƯỚC
HOÀ KHÔNG
TÊN THIẾT BỊ/
PAU BỘ XỬ LÍ
CẤP/PRIMARY
PRIMARY HOT
THIẾT BỊ XỬ LÍ
/ COLD WATER
THẢI/EXHAUST
WATER PUMPS
LẠNH/CHILLER
NÓNG SƠ CẤP /
HỆ THỐNG LÀM
EQUIPMENT NAME
HANDLING UNIT
HỆ THỐNG ĐIỀU
BƠM NƯỚCLẠNH
KHÍ/PRIMARY AIR
SECONDARYCHIL
SỐ LƯỢNG THIẾT BỊ/
X
X
X
X
X
X
X
X
Vị trí/Location: HOI AN CITY
NO.OF EQUIMENT
THIẾT BỊ CHẠY/DỪNG /
X
X
X
Thực hiện/Prepared by: NGUYEN
2X
START/STOP EQUIPMENT
Công trình/Project: MARRIOTT HOI AN
X
VALVE CONTROL
SIGNAL
X
2X
COMMAND
SỐ NGÕ
LINH
X
2X
MODULATING VALE CONTROL
2X
VALVE CONTROL (PID)
ĐIỂU KHIỂN TỐC ĐỘ VSD/VSD SPEED
BẢNG ĐIỂM HỆ THỐNG BMS/BMS SYSTEM POINT SCHEDULE
X
X
2X
CONTROL
X
R/A TEMPERATURE
X
POST COOLING COIL AIR TEMPERATURE
S/A TEMPERATURE
X
S/A & R/A RELATIVE HUMIDITY
2X
TÍN HIỆU ÁP SUẤT / S/A PRESSURE
X
Page 1
PRESSURE AT 2/3 DOWN LONGEST
X
TEMPERATURE
CẢM BIẾN MỨC DẦU / OIL LEVEL SENSOR
TRẠNG THÁI VAN / MODULATING VALE STATUS
X
2X
TÍN HIỆU TƯƠNG TỰ NGÕ VÀO / ANALOGUE INPUT (AI)
Rev.:A
X
X
X
X
X
X
X
2X
STATUS
STATUS
OVER HEAT ALAMRM STATUS
II
5
THẢI /
HOẠT /
PUMPS
CHILLER
SERVICE
SANITARY
DOMESTIC
NHIỆT ĐỘ /
PUMPING &
DRAINAGE /
BƠM NƯỚC
BƠM NƯỚC
BƠM NƯỚC
WATER TANK
3-WAY VALVE
TUẦN HOÀN /
MONITORING
TÊN THIẾT BỊ/
WATER PUMP
CIRCULATION
BƠM TĂNG ÁP
NÓNG / STORE
WATER WASTE
BYPASS VALVE
WATER PUMPS
BỂ NƯỚC SINH
TEMPERATURE
THỊ / SENSOR &
EQUIPMENT NAME
ĐỘ ẨM / HUMIDII
BỂ CHỨA NƯỚC
MÁY LÀM LẠNH /
COOLING TOWER
BOOSTER PUMP /
CẢM BIẾN & HIỂN
SECONDARY HOT
X
X
X
X
X
X
X
X
X
X
X
X
Vị trí/Location: HOI AN CITY
NO.OF EQUIMENT
THIẾT BỊ CHẠY/DỪNG /
X
X
X
X
Thực hiện/Prepared by: NGUYEN
START/STOP EQUIPMENT
Công trình/Project: MARRIOTT HOI AN
VALVE CONTROL
SIGNAL
COMMAND
SỐ NGÕ
LINH
X
CONTROL
R/A TEMPERATURE
POST COOLING COIL AIR TEMPERATURE
S/A TEMPERATURE
S/A & R/A RELATIVE HUMIDITY
TÍN HIỆU ÁP SUẤT / S/A PRESSURE
X
X MULTIMEDIA & MONITORING METER/
Page 2
PRESSURE AT 2/3 DOWN LONGEST
R/A DUCT RUN
SIGNAL
X
X
X
X
X
X
X
X
2X
STATUS
X
X
X
X
X
STATUS
OVER HEAT ALAMRM STATUS
V
L
BƠM
BƠM
ACB)
TANK
PUMP
PUMP
CHIẾU
L PUMP
BƠM BÙ
SERVICE
LIGHTING
CONTROL
HỆ THỐNG
CHÁY/FIRE
III CHÁY/FIRE
ÁP/JOCKEY
MÁY PHÁT /
ĐiỀU KHIỂN
WATER TANK
TÊN THIẾT BỊ/
DIESEL/DIESEL
TRANSFORMER
LVMSB (MCCB &
EQUIPMENT NAME
SÁNG/LIGHTING
BỒN DẦU / FULE
BỂ NƯỚC CHỮA
STOREGE ,DAILY
ĐIỆN/ELECTRICA
TRANSFER PUMP
SỐ LƯỢNG THIẾT BỊ/
X
X
X
X
X
X
X
X
X
X
X
Vị trí/Location: HOI AN CITY
NO.OF EQUIMENT
THIẾT BỊ CHẠY/DỪNG /
X
Thực hiện/Prepared by: NGUYEN
START/STOP EQUIPMENT
Công trình/Project: MARRIOTT HOI AN
VALVE CONTROL
SIGNAL
COMMAND
SỐ NGÕ
LINH
X
X
X
CONTROL
R/A TEMPERATURE
POST COOLING COIL AIR TEMPERATURE
S/A TEMPERATURE
S/A & R/A RELATIVE HUMIDITY
TÍN HIỆU ÁP SUẤT / S/A PRESSURE
X
X
MULTIMEDIA & MONITORING METER/
Page 3
PRESSURE AT 2/3 DOWN LONGEST
R/A DUCT RUN
SIGNAL
X
X
NHIỆT ĐỘ PHÒNG / ROOM TEMPERATURE
NHIỆT ĐỘ ĐIỂM NGƯNG / DEW POINT
TEMPERATURE
X
X
CẢM BIẾN MỨC DẦU / OIL LEVEL SENSOR
TRẠNG THÁI VAN / MODULATING VALE STATUS
TÍN HIỆU TƯƠNG TỰ NGÕ VÀO / ANALOGUE INPUT (AI)
Rev.:A
X
X
X
STATUS
X
STATUS
X
METER
ELECTRIC
GAS METER
HỒ HIỂN THỊ
MONITORING
TÊN THIẾT BỊ/
WATER METER
METER / ĐỒNG
EQUIPMENT NAME
SỐ LƯỢNG THIẾT BỊ/
NO.OF EQUIMENT
THIẾT BỊ CHẠY/DỪNG /
Thực hiện/Prepared by: NGUYEN
START/STOP EQUIPMENT
Công trình/Project: MARRIOTT HOI AN
VALVE CONTROL
SIGNAL
COMMAND
0
0
0
0
0
KIỂM SOÁT VAN TRUYỀN ĐỘNG/MODULATING
VALVE CONTROL (PID)
ĐIỂU KHIỂN TỐC ĐỘ VSD/VSD SPEED
BẢNG ĐIỂM HỆ THỐNG BMS/BMS SYSTEM POINT SCHEDULE
CONTROL
R/A TEMPERATURE
POST COOLING COIL AIR TEMPERATURE
S/A TEMPERATURE
S/A & R/A RELATIVE HUMIDITY
TÍN HIỆU ÁP SUẤT / S/A PRESSURE
Page 4
PRESSURE AT 2/3 DOWN LONGEST
R/A DUCT RUN
SIGNAL
STATUS
STATUS
OVER HEAT ALAMRM STATUS
BẢNG ĐIỂM HỆ THỐNG BMS/BMS SYSTEM POINT SCHEDULE
Công trình/Project: MARRIOTT HOI AN Ngày/Date: 14/07/2016
Vị trí/Location: HOI AN CITY Rev.:A
Thực hiện/Prepared by: NGUYEN THI HUYNH LINH TÍN HIỆU SỐ NGÕ Kiểm tra/Checked by: BUI T
RA / DIGITAL TÍN HIỆU SỐ
TÍN HIỆU TƯƠNG TỰ TÍN HIỆU TƯƠNG TỰ NGÕ VÀO / ANALOGUE INPUT (AI) SIGNAL
OUTPUT (DO) TRẠNG THÁI
SIGNAL NGÕ RA / ANALOGUE
DEFFERENTIAL PRESSURE
MONITORING METER/
SỐ LƯỢNG THIẾT BỊ/
R/A TEMPERATURE
S/A TEMPERATURE
NO.OF EQUIMENT
TEMPERATURE
TEMPERATURE
R/A DUCT RUN
I HỆ THỐNG ĐIỀU HOÀ KHÔNG KHÍ/MVAC x x x x x x x x x x x x x x x
1 QUẠT/FAN
QUẠT THẢI/EXHAUST FAN X X X X
2 DÀN LẠNH / THIẾT BỊ XỬ LÍ KHÔNG KHÍ FCU/AHU
FCU X X X X X X
AHU X 2X 2X 2X 2X 2X X X X 2X X X 2X 2X 5X
3 PAU BỘ XỬ LÍ KHÔNG KHÍ/PRIMARY AIR HANDLING UNIT
PAU X X X X X X X X X X
4 HỆ THỐNG LÀM LẠNH/CHILLER SYSTEM
BƠM NƯỚC LẠNH SƠ CẤP/PRIMARY CHILLED WATER PUMPS X X X X X 2X
BƠM NƯỚC LẠNH THỨ CẤP / SECONDARYCHILLED WATER PUMPS X X X X X
BƠM NƯỚCLẠNH / COLD WATER PUMPS X X X X
BƠM NƯỚC NÓNG SƠ CẤP / PRIMARY HOT WATER PUMPS X X X X
BƠM NƯỚC NÓNG THỨ CẤP / SECONDARY HOT WATER PUMPS X X X X
3-WAY VALVE X X X
BYPASS VALVE X X X X
MÁY LÀM LẠNH / CHILLER X X 2X X X X X X X X X 2X
THÁP GIẢI NHIỆT / COOLING TOWER X X 2X 2X X X
5 CẢM BIẾN & HIỂN THỊ / SENSOR & MONITORING
NHIỆT ĐỘ / TEMPERATURE X X
ĐỘ ẨM / HUMIDII X X
II BƠM & VỆ SINH / PUMPING & SANITARY SERVICE
BƠM NƯỚC THẢI / DRAINAGE / WATER WASTE PUMPS X X X
BỂ NƯỚC SINH HOẠT / DOMESTIC WATER TANK X X
BOOSTER PUMP / BƠM TĂNG ÁP X X X X
BỂ CHỨA NƯỚC NÓNG / STORE HOT WATER TANK X
BƠM NƯỚC TUẦN HOÀN / CIRCULATION WATER PUMP X X X
III HỆ THỐNG CHỮA CHÁY/FIRE SERVICE
FIRE FIGHTING CONTROL PANEL X X
BỂ NƯỚC CHỮA CHÁY/FIRE WATER TANK X
BƠM ĐIỆN/ELECTRICAL PUMP X X X
BƠM BÙ ÁP/JOCKEY PUMP X X X
BƠM DIESEL/DIESEL PUMP X X X
Page 5
LIGHTING
IV HỆ THỐNG ĐIỆN/ELECTRICAL
X
X
X
X
X
NO.OF EQUIMENT
THIẾT BỊ CHẠY/DỪNG /
X
START/STOP EQUIPMENT
Page 6
0
0
0
0
0
R/A TEMPERATURE
POST COOLING COIL AIR TEMPERATURE
S/A TEMPERATURE
S/A & R/A RELATIVE HUMIDITY
TÍN HIỆU ÁP SUẤT / S/A PRESSURE
MONITORING METER/
TRẠNG THÁI
TÍN HIỆU SỐ
Kiểm tra/Checked by: BUI T
Rev.:A
Ngày/Date: 14/07/2016
x
TRẠNG THÁI CB / CIRCUIT BREAKER STATUS
TRẠNG THÁI NORMAL / FAULT /
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X NORMAL / FAULT STATUS
2X
x
X
TRẠNG THÁI LỌC BỤI / DIRTY FILTER STATUS
3X
Kiểm tra/Checked by: BUI THI KIM OANH
X
SWITCH
X
CÔNG TẮC DÒNG CHẢY CHILLED / CHILLED WATER FLOW SWITCH
Page 7
ĐẦU DÒ KHÓI TRONG ỐNG GIÓ / SMOKE ALARM IN R/A, S/A DUCT
X2
x
X
X
X
BÁO ĐỘNG MỨC CAO / HIGH LEVEL ALARM
x
X
X
X
BÁO ĐỘNG MỨC THẤP / LOW LEVEL ALARM
TÍN HIỆU SỐ NGÕ VÀO / DIGITAL INPUT (DI) SIGNAL
TRẠNG THÁI THIẾT BỊ / EQUIPTMENT STATUS & ALARM
X
TRẠNG THÁI CB / CIRCUIT BREAKER STATUS
TRẠNG THÁI NORMAL / FAULT /
NORMAL / FAULT STATUS
Page 8
ĐẦU DÒ KHÓI TRONG ỐNG GIÓ / SMOKE ALARM IN R/A, S/A DUCT
X