Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2018-07-16, 17:19:44


Test device: CT-Analyzer Device Serial No.: BL268V
File name: C:\Users\Segara Daya Mandiri\Downloads\siemens_1700927_4_s1-s2.xml
Assessments: OK

Used test settings:


I-pn: 2000,0 A Location: Object:
I-sn: 1,0 A Company: PT. INDOKOMAS Manufacturer: TRENCH
Rated burden: 30,0 VA / 0,8 Country: IND Type: iosk 170
Operating burden: 30,0 VA / 0,8 Station: GI MARTAPURA Serial number: 1700927
Applied standard: IEC 60044-1 Feeder/Bay: MUARA DUA 1 Core number: 4
Core type (P/M): P Phase: T Tap: S1 - S2
Class: 5P IEC-ID Optional:
ALF: 15,0 Ts:
f: 50,0 Hz max. Rct: 6,41 Ω

Resistance test: Burden test:


Rmeas (25°C): 5,37486 Ω Burden: cos φ: Z:
Rref (75°C): 6,41048 Ω Vmeas: Imeas:

Excitation test:
V-kn: 487,508 V I-kn: 0,011463 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: 17,95 ALFi: 17,31 ALF: 17,95 ALFi: 17,31
Ls: 0,0077529H Lm: 154,4299 H Ts: 5,078s Ts: 5,078s
Kr: 90,47 %

Ratio test:
Ratio: 2000,0 : 0,99727 ε : -0,2726 % Δφ: 5,19 min Polarity: OK N: 2002,10
εc : 0,3142 %

Residual Magnetism Test:


Residual Flux:
Residual Magnetism:

Excitation curve data Excitation curve data

100

10
Es / V

0,1

0,01
0,00001 0,0001 0,001 0,01 0,1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2

siemens_1700927_4_s1-s2 Page 1 of 4
Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0,8 -0,792 -0,571 -0,460 -0,377 -0,308 -0,273 -0,268 -0,259
15 VA/ 0,8 -0,466 -0,416 -0,349 -0,291 -0,237 -0,212 -0,206 -0,195
7,5 VA/ 0,8 -0,287 -0,308 -0,275 -0,238 -0,198 -0,177 -0,173 -0,164
3,75 VA/ 1 -0,197 -0,237 -0,226 -0,204 -0,175 -0,158 -0,155 -0,147
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0,8 53,178 18,859 12,630 9,082 6,692 5,192 4,846 3,798
15 VA/ 0,8 41,784 15,129 9,720 6,535 4,396 3,530 3,309 2,721
7,5 VA/ 0,8 33,475 12,412 7,944 5,118 3,153 2,397 2,256 1,930
3,75 VA/ 1 27,514 10,510 6,749 4,281 2,488 1,783 1,663 1,395
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 Ratio
10 Error Graph 20 50 100 120 200
1,00 1,00 1,00
-1,00 -1,00 -1,00
0,000
0 50 100 150 200 250
-0,100

-0,200
Current deviation [%]

-0,300
100% Load

-0,400
50% Load

-0,500
25% Load

-0,600

-0,700

-0,800

-0,900

% I-pn

siemens_1700927_4_s1-s2 Page 2 of 4
siemens_1700927_4_s1-s2 Page 3 of 4
siemens_1700927_4_s1-s2 Page 4 of 4

You might also like