Professional Documents
Culture Documents
DCM-Physical Station Service
DCM-Physical Station Service
Physical Design
Contents
AC Station Service Systems – Physical Design ............................................................................................. 1
Overview .................................................................................................................................................... 2
Design Procedure........................................................................................................................................ 2
AC Equipment Selection Criteria ............................................................................................................... 3
Primary Fused Disconnect .......................................................................................................................... 3
Safety Switch .............................................................................................................................................. 4
AC Distribution Cabinet ............................................................................................................................. 5
Station Service Transformers ..................................................................................................................... 6
Standard Transformer KVA-Single Phase .................................................................................................. 6
Standard Transformer KVA-Three Phase ................................................................................................... 6
Voltage Ratings-Standard ........................................................................................................................... 6
Transformer Connections – Single Phase ..................................................................................................10
Transformer Connections – Three Phase ...................................................................................................11
Transformer Loading .................................................................................................................................14
Design Considerations ...............................................................................................................................15
Dual Station Service Schemes ...................................................................................................................15
Cable Sizing ...............................................................................................................................................16
Record of Revision ....................................................................................................................................22
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 1
Overview
The AC station service system supplies all the substation AC power
requirements for the following loads found in a typical substation:
• Power transformer equipment; cooling fans, oil pumps, load
tap changers, cabinet heaters, and receptacles
• Circuit breaker charging motors and heaters
• Switch motor operator heaters
• Outdoor lighting and receptacles
• Control house equipment
Lighting and receptacles
Heating, ventilating, and air conditioning
Battery charger
Design Procedure
The basic design procedure for determining the component
requirements for an AC station service is as follows:
1. A preliminary load study is to be performed to determine the
number of circuits required, the size and rating of the circuit
breakers/fuses needed, the kVA and secondary voltage rating of
the station service transformer(s). If load requirements are
unknown, historical data should be used. Plans for future
expansion of the substation should also be considered in
determining these requirements.
• Current rating
• Voltage rating
• Interrupting rating
• Coordination
Current Rating
The current rating of the station service fuse will be provided by the
protective equipment applications group.
Voltage Rating
The station service fuse must be selected on the basis of actual service
voltage. If over insulation is required, then insulators should be
specified to provide the higher rating.
Interrupting Rating
The interrupting-rating of power fuses should equal or exceed the
maximum short circuit at the point in the system where the fuses are to
be installed.
Coordination
For a standard distribution substation with differential relaying, the
station service fuse must coordinate with the relaying such that a station
service fault will be cleared by the station service fuse before the
differential relay operates. A current limiting fuse is required for this
coordination. See the topic on station service fuse recommendations in
the P&C section of the DCM.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 3
For a standard distribution substation without differential relaying, the
less expensive power fuse may be used. This station service fuse must
coordinate with the high side protective device, e.g. circuit switcher or
fuses.
Safety Switch
A station service safety switch is required at all substations. This
switch is inserted between the secondary of the station service
transformer and the distribution cabinet. In most cases it is mounted
directly below the station service transformer, on the same structure
leg. The secondary leads from the station service transformer shall be
600V insulated copper cable, sized to the output of the station service
transformer (see formulas below), and will be connected to a safety
switch through a weather head and adequately sized conduit. The
Example 3.
3φ safety switch for (3-100kVA) transformer
= 1000 (300kVA) / (240V x 1.732)
= 722A = use an 800A3φ-safety switch
AC Distribution Cabinet
An AC distribution cabinet is required at all substations where AC
power is needed. The distribution cabinet may be indoor or outdoor. It
should be sized to accommodate the maximum number of branch
circuits anticipated while leaving room for additional growth. The
branch circuit protective devices, breakers or fuses, should be sized to
protect the conductors of the branch circuit from overcurrent
conditions. The protective devices should also have the short circuit
current rating to interrupt the available fault current at the device. In
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 5
most cases, particularly on smaller station service transformers, the
available secondary fault current will be well below standard breaker
interrupting ratings.
A typical distribution substation will have a 3 wire, 225A main bus
cabinet, main lugs only (no main breaker), such as the Square D type
NQOD42L225CU with type QO circuit breakers. Future substation
expansion may dictate the need to initially install a larger cabinet, e.g.-
54 pole rather than 42 pole capacity.
Voltage Ratings-Standard
When writing descriptions or the purchase of a distribution transformer
or when applying a distribution transformer based on the description, it
is important to understand the industry standard description format.
E = Winding Voltage
Es = System Voltage (system phase to phase voltage)
Es Y = System Voltage on Wye System
Es Grd Y = System Voltage on a Grounded Wye System
Delta Voltage
E Example: 12470
Indicates winding voltage (E) = system voltage (Es) - suitable for use
on a ∆−system with a φ−φ voltage of 12470V (E=Es)
Delta or Wye
E / Es Y Example: 7560 / 13090 Y
Indicates a winding voltage of 7560V (E) - suitable for installation on a
Y−system (EsY) with a φ−φ voltage of 13090V or a ∆−system with a
φ−φ voltage of 7560V.
Wye Grd
Es GrdY / E Example: 13090 Grd Y / 7560
Indicates a winding voltage of 7560V (E) - suitable for installation on a
Grounded Y−system (Es GrdY) with a φ−φ voltage of 13090V with the
neutral bushing of the transformer effectively grounded (The winding
has reduced insulation on the neutral end. Typical of a one bushing
transformer). Not suitable for use on a ∆−system.
Series-Parallel or 3-Wire
E / 2E Example: 120 / 240
Indicates that the transformer has two separate windings of equal rating
(E & kVA) that can be connected in parallel or series, and can be used
for a 3−Wire Service.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 7
H1 H2
A D
X3 C B X1
X2
3-Wire
2E / E Example: 240 / 120
Indicates that the transformer has only one winding (2E) that has been
center tapped at the mid-point to provide 3−Wire Service.
H1 H2
X3 X1
X2
Series-Parallel Only
E x 2E Example: 240 x 480
Indicates that the transformer has two separate windings of equal rating
(E & kVA) that can be connected in parallel or series to provide 240
(E) or 480 ( 2E) volt service. Not suitable for 3−Wire Service
H1 H2
X4 X1
X2 X3
AC Station Service Systems – Physical Design Southern Company Substation Design
Criteria Manual • 8
Voltage Ratings-Typical
High Voltages H V Winding BIL Low Voltages
600/480 120 / 240
2400 / 4160Y 120 / 240
2400 / 4160Y x 7200 /
125kV 120 / 240
12470Y
2520 / 4360Y 120 / 240
7200 / 12470Y 95kV, 125kV 120 / 240
7560 / 13090Y 95kV, 125kV 120 / 240
7620 / 13200Y 95kV, 125kV 120 / 240
7960 / 13800Y 95kV, 125kV 120 / 240
12470 95kV, 125kV 120 / 240
12000 / 20800Y 125kV 120 / 240
13200 / 22860Y 125kV 120 / 240
13800 / 23800Y 150kV 120 / 240
14400 / 25000Y 150kV 120 / 240
19920 / 34500Y 200kV 120 / 240
27720 / 48000Y 250kV 120 / 240
Transformer Polarity
Transformer polarity is used to indicate the voltage and current
relationship between windings. When the voltage on a winding with a
polarity mark has reached a positive peak, any associated winding
marked with polarity will reach a positive voltage peak simultaneously.
When current flows into a winding with a polarity mark, current will
flow out of any associated winding marked with polarity.
Transformer polarity can be either additive polarity or subtractive
polarity. Industry standards require that any single phase distribution
transformer 200kVA and smaller with a high voltage of 8660V or less
is always additive polarity. All single phase transformers larger than
200kVA or with a high voltage winding greater than 8660V are
subtractive polarity.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 9
Transformer Polarity Test Connections
APPLY
240V
H1 H2
10:1 240V
RATIO READ
24V VM 264V
X2 X1
Additive Polarity
APPLY
240V
H1 H2
10:1 240V
RATIO READ
24V VM 216V
X1 X2
Subtractive Polarity
Great care should be taken to insure that the test voltage is always
applied to the highest voltage winding.
A
B
C
H1 H2 H1 H2
A D D
X3 X1 X3 A
C B C B X1
X2
a
n
b
c
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 11
addition to the single phase load and may be larger than the other
transformers in the bank, however, it is more common to size all of the
transformers the same to allow for greater flexibility during
emergencies.
A
B
C
H1 H2 H1 H2 H1 H2
A D D D
X3 X1 X 3 A X1 X 3 A X1
C B C B C B
X2
a
n
b
c
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 13
Transformer Loading
Single Phase Amperes @ 120/240 Volts
A A A
A A A A A A
B A B B
A B
15 62.5 108
25 104 180
37.5 156 270
50 208 360
75 312.5 542
100 417 723
A A
A A A
Single Phase Amperes
Transformer @120/208 Volts
KVA A
10 83.3
15 125
25 208
37.5 313
50 417
75 625
100 833
Design Considerations
Dual Station Service Schemes
Overview
As substations increase in size, the need to maintain station service
becomes more critical. Dual station service schemes will need to be
considered taking into account economics and customer service. If a
dual feed is required, the two independent sources must be located so
that the loss of one will not affect the other. Various schemes and
sources are discussed in the following sections.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 15
Two Bank Standard Distribution Substation
When a second bank is added to a substation a duplicate station service
system is to be provided. A primary fuse, station service transformer,
and safety switch should be provided on the new bank as duplicate
equipment. A single phase, station service transfer switch is to be
added between the two station services systems with the output of the
transfer switch connected to the AC distribution cabinet. The ampere
rating of the transfer switch should match the rating of the safety
switch.
An automatic transfer switch is designed to transfer the station service
load when the normal supply voltage drops below 70% and to re-
transfer when normal voltage supply is 90% or higher. See section
“Installation – Two Bank Distribution Substation” for typical station
service transformer installation practices.
Cable Sizing
Ampacity
The ampacity of a conductor is the maximum amount of current that it
can carry without raising its temperature above the conductor’s rated
maximum operating temperature. Raising a conductor’s temperature
above its temperature rating will shorten the life of the insulation, or
damage the insulation and eventually cause the cable to fail
prematurely.
The temperature of the conductor is not only a function of cable
construction and loading, it is also a function of the environment in
which the cable is installed. The below table, Table 310.16, from the
National Electrical Code (NEC) gives the ampacity of conductors in
raceway, cable or directly buried.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 17
Factors That Affect the Ampacity of Cable
Overloads - The NEC requires cables that supply power to
compressors motors, fans, pumps, air conditions, etc. be sized with an
overload factor. The NEC requires that the cables that feed these
devices be sized for 125% of the equipment’s Full Load Rating (not
locked rotor current).
Conductor Temperature Rating - Southern Company control and
power cable is rated 90°C (194°F).
Ambient Temperature - If using NEC Table 310.16 for ambient
temperatures other than 30°C, the correction factors at the bottom of
the table must be applied.
Installation conditions - More than three cables in conduit, ambient
temperature, installation in air, cable, raceway, etc. These conditions
may dictate the use of another ampacity table or the application of a
correction factor.
Voltage Drop
The selection of the minimum size conductor is often limited by
voltage drop considerations. A cable may meet the ampacity
requirements but the voltage drop at the equipment due to cable length
may exceed limits. The voltage drop for power and control circuits
should be limited to 5%.
For substation control and power cables the following formula can be
used to calculate voltage drop:
𝐸𝐸 = 2 ∗ 𝐿𝐿 ∗ 𝐼𝐼 ∗ 𝑍𝑍⁄1000
L= one-way circuit length (ft.)
I= load current (amps)
Z= conductor impedance (Ω/1000ft.)
(See NEC Table 8, Uncoated, Direct Current
Resistance. Note for the purpose of performing our
voltage drop calculations, reactance can be
neglected.)
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 19
Example- Single-Phase AC Circuit
Determine the % voltage drop at startup on a three-wire, single phase,
240VAC circuit supplying a circuit breaker with a 3A heater load and a
spring charge motor in which locked rotor current (starting) equals 33A
and running current is 8A. The circuit consists of a three conductor #6
copper cable 300 ft. long.
Solution:
From Table 8, the resistance of #6 cu. conductor is 0.491Ω/1000ft.
𝐸𝐸 = 2 ∗ 𝐿𝐿 ∗ 𝐼𝐼 ∗ 𝑍𝑍⁄1000
= 2 ∗ 300 ∗ (36) ∗ 0.491⁄1000
= 10.6𝑉𝑉 𝑜𝑜𝑜𝑜 4.4% 𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑
From NEC Table 310-16, 2/0 will carry 195A. The cable ampacity is
good.
Southern Company Substation Design Criteria Manual AC Station Service Systems – Physical
Design • 21
Record of Revision