TK C19 (RTU K19) Compact Terminal - Installation Manual
TK C19 (RTU K19) Compact Terminal - Installation Manual
INSTALLATION ............................................
............................................ 8
Cable Breakaway Tabs ................................................................................ 8
Connectors and Jumpers ............................................................................. 9
Power .......................................................................................................... 11
NET ............................................................................................................. 12
LONWORKS Data Cables................................................................. 12
INPUTs ....................................................................................................... 14
Digital INPUTs ..................................................................................... 15
Supervised INPUTs ............................................................................. 16
Power OUTs ............................................................................................... 17
Resistive load ...................................................................................... 18
Inductive load ...................................................................................... 18
Inductive load with external Power supply .......................................... 19
External relays ..................................................................................... 20
Assembling the Terminal Closure Guide .................................................... 21
Closing the Terminal (Wall-Mounted Assembly)................................. 22
Closing the Terminal (Turnstile-Mounted Assembly) .......................... 23
ACTIVATION ..............................................
.............................................. 24
Identification via the Service Pin ................................................................ 24
Identification via Bar Code.......................................................................... 25
Mounting Instructions
The cables are attached to an encased box. Make sure that you place the
box at a height of 120cm from the floor (see Figure 1).
120 cm
tube
cables
floor
Figure 1. Space Requirements for Mounting
Avoid metal surface Page 3 of 29
75mm
75mm
72mm
Anchor
Cables
entrance
Anchor
PG9 cable
Anchor
clamp
Multi-pole
cable
(15 poles)
Breakaway tab
for cables exit
from back
Breakaway tab Anchor
for cables exit
from bottom
J2
IN 1+ J1 J4
OUT2 -
IN 1- (GND) OUT2+ (12V)
IN 2+ OUT1-
IN 2- (GND) OUT1+ (12V)
J3
ground
NET-A
NET-B
+12V
Figure 7. Connectors
JP4 Buzzer
ON/OFF
BUZZER
JP3, 5
Outs NC/NO
Tamper
Figure 8: Jumpers
+12V Ground
When the cables run outside of the building, you must use shielded cables.
The cables’ shielding must be connected to the ground connector.
For internal wiring without shielded cables, the cables should run in an
environment where all cables are well separated, even for short runs. This is
especially true for the power cables or any external cables that may be
subjected to interference or lighting.
Power Page 11 of 29
NET
1
LONW ORKS® is a trademark of Echelon Corporation
Page 12 of 29 NET
• Check that the length of the LONW ORKS data cable corresponds to the
norms indicated in Table 1.
• The FTT10A Echelon v1.2 User Guide recommends the cables indicated
in Table 2.
Producer and Model AWG Connection to Connection in free Connection in free
bus – topology – maximum topology – maximum
maximum total node-node length total wire length. [m]
length [m] max. [m]
Belden 85102 16 2700 500 500
Belden 8471 16 2700 400 500
Level IV (twisted-pair, 22 1400 400 500
typically solid and
unshielded)
JY (St) 2x2x0.8 (4-wire 20 900 320 500
helical twist, solid
shielded)
TIA Cat5 / 900 250 450
Table 2. Recommended LONWORKS Cables
NET Page 13 of 29
INPUTs
It is possible to manage digital inputs and supervised inputs.
Usually, the IN1 is dedicated to the Door contact.
Usually, the IN2 is dedicated to the push button (request to exit).
However, the inputs can also be used as general purpose inputs.
Use JP2 to select the mode:
• JP2 Close Supervised inputs (default)
Supervised inputs 4 status: normal, alarm, cut, short
• JP2 Open Digital inputs
Digital inputs status: Open or Close
JP2
Page 14 of 29 INPUTs
Digital INPUTs
The typical connection for digital dry contacts is shown in the next figure.
+12V Ground
INPUTs Page 15 of 29
Supervised INPUTs
The typical connection for supervised dry contacts is shown in the next figure.
Put the resistors close to the dry contact.
Dry contacts
Normally closed
Door
White
input 1+
yellow
input 1-
White input 2+
yellow input 2-
+12V
Ground
Page 16 of 29 INPUTs
Power OUTs
It is possible to manage two digital outputs NC (Normally Close) or NO
(Normally Open).
Usually, the OUT1 is dedicated to the Door Electrolock.
Usually, the OUT2 is dedicated to the Busy lamp.
However, the Outputs can be also used as general purpose outputs.
Use JP3 and JP5 to select the mode:
JP3 1-2 OUT 1 NO (default)
2-3 OUT 1 NC
JP5 1-2 OUT 2 NO (default)
2-3 OUT 2 NC
3
2
JP5 1-2 1
JP3 1-2
Internally, the output lines are provided with Power Mosfet, which can drive to
ground:
1,2A 30V continuous
5A 30V (0,5 sec) peak current for inductive loads
Resistive load
OUT2-
+12V
OUT1- max 1,2A
+12V
max 1,2A
12VDC / GND
Inductive load
load
1N4004
OUT2-
+12V
max 1,2A (5A impulse)
1N4004
OUT1-
+12V
max 1,2A (5A impulse)
12VDC / GND
1N4004
OUT2-
1N4004
OUT1-
Isolated Power Supply
max 1,2A (5A impulse)
10 to 30VDC
DC OUT
GND
AC IN
12VDC / GND
12V relay
1N4004
OUT2
12V relay
1N4004
OUT1
12VDC / GND
screw head
Figure 17. Mounting the Terminal Closure Guide (1)
Make sure that the fitting is correctly positioned, and then insert the flat cable
from the front casing into the connector (see Figure 18).
O-ring
Special
screws
Closure
Guide Flat cable
NUT
Special
star-
shaped
screw
Figure 18. Mounting the Terminal Closure Guide (2)
Magnet
service pin
(reed)
service
LED
Description of location
TKC01 (RTU-K01) ፬
TKC02 (RTU-K02) ፬ NID label
TKC03 (RTU-K03) ፬
TKC12 (RTU-K12) ፬
TKC19 (RTU-K19) X
፬
Compliance with
Industry Canada
Operation is subject to the following two conditions: (1) this device may not
cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the
device.
Optional Parts
TORX screwdriver TX10 code 1500108AA
2
LONW ORKS® is a trademark of Echelon Corporation
Page 28 of 29 TemaKey TK C19 (RTU-K19 code 1500167xx)
Recycling
In accordance with directive 2002/96/EC regarding waste electrical and
electronic apparatus (effective since 13 August 2005), Honeywell commits,
when requested by the customer, to the collection, treatment, recovery, and
disposal of the apparatus produced.
Customers in the European Union are advised to dispose this product, at the
end of its useful life, in accordance with local laws, regulations, and
procedures.
Honeywell
Via Tintoretto 15 – 21012 Cassano Magnago (VA) - Italy
Recycling Page 29 of 29