Discrepancy layout with single line diagram:-

ITEMS AS PER APPROVED LAYOUT AS PER APPROVED SLD

1. Transformer-3 1000kva 1600kva


2. Transformer-4 1000kva 2000kva
3. Transformer-5 1600kva 1000kva
4. Transformer-spare 2000kva ---

LOCATION:

TRANSFORMER TR-11 Main building Utility building

RATING:

TRANSFORMER –TR-5, rating is less than required capacity i.e. 1000kva

MISSING INFORMATION:

All switchgears bus- bar rating are not mentioned in single line diagram drawing

SHORT CIRCUIT & COORDINATION STUDY:

Short circuit level not mentioned in drawing

Prepared by : Eng Nadim