Professional Documents
Culture Documents
02 - KW TR Relation PDF
02 - KW TR Relation PDF
02 - KW TR Relation PDF
November 2013
1 © Hudson Technologies
Acknowledgments
2 © Hudson Technologies
Webinar Agenda
Fundamentals of Refrigeration
Conclusions
3 © Hudson Technologies
Chiller System Energy Cost?
1,000 Refrigeration Tons chiller plant load
Chiller System performance = 0.75 kW/ton
Bundled power cost = $0.085/kWh
600,000
500,000
Operating Cost ($)
400,000
300,000
200,000
100,000
-
4 months 6-8 months All year round
Operating hours
4 © Hudson Technologies
The Systems Approach
5 © Hudson Technologies
The Systems Approach
7 © Hudson Technologies
Main Driving Force for Change
Energy
Reliability
Maintenance
Productivity
Quality
Cost avoidance
Emissions reductions
8 © Hudson Technologies
Fundamentals of
Refrigeration
9 © Hudson Technologies
The Refrigeration Cycle
3 R134a
10
P [psia]
Condensation / SubCooling
105°F
2
10 Expansion
Compression
40°F
Ev aporation (Boiling)
1
10
0 25 50 75 100 125 150
h [Btu/lbm]
State Point
10 © Hudson Technologies
Single Stage Chiller System
HGBP (Hot Gas ByPass)
Compressor
HGBP
11 © Hudson Technologies
A Centrifugal
A Water-Cooled
Chiller Chiller System
Condenser
Compressor
12 © Hudson Technologies
Two Stage Chiller System
HGBP
Compressor
Economizer HGBP
(Hot Gas ByPass)
13 © Hudson Technologies
LiBr-Water Absorption Chillers
14 © Hudson Technologies
The Air, Water and Refrigerant Cycle
15 © Hudson Technologies
Chiller Plant - Actual
Operating Performance
16 © Hudson Technologies
Chiller Capacity
18 © Hudson Technologies
Chiller Full Load Design Specifications
Evaporator Entering Water Temperature: 54.37°F Evaporator Leaving Water Temperature: 44°F
Condenser Entering Water Temperature: 85°F Condenser Leaving Water Temperature: 94.4°F
Evaporator Pressure Drop (psig): 9.9 Condenser Pressure Drop (psig): 8.1
19 © Hudson Technologies
Overall Chiller Plant Performance
Information required
Total tonnage
Total kW
Compressor Power
Pumping Power
Cooling Tower Fan Power
Other (as defined in the scope)
kW
Plant Performance n
Chiller Tons
m
20 © Hudson Technologies
Overall Chiller Plant Performance
21 © Hudson Technologies
Chiller Plant Efficiency Metrics
22 © Hudson Technologies
Predictive & Preventive
Maintenance
BestPractices
23 © Hudson Technologies
First Things First – Fluid Management
Understanding “Cause” and “Effect” is very
important for Root Cause Analysis
This enhances system reliability and reduces
unplanned shutdown
Significant savings in Maintenance costs
Most Maintenance BestPractices are testing-
based
Refrigerant, Oil and Water Testing
Rotating equipment monitoring
Vibration analysis
Eddy-current testing
In chiller systems, contaminants affect
efficiency & capacity
Chemistry Based Solutions
24 © Hudson Technologies
Blood Chemistry
25 © Hudson Technologies
Chiller Chemistry
26 © Hudson Technologies
Refrigerant Analysis Criteria
Moisture
Oil
Particulate
Chlorides
Acid
Purity
Non-Condensables
Other Contaminants
27 © Hudson Technologies
Nonferrous cutting wear Severe sliding wear
28 © Hudson Technologies
Water Testing and Analysis
29 © Hudson Technologies
Energy Conservation
Measures (ECMs)
30 © Hudson Technologies
3 Methods of Maximizing Chiller Plant Efficiency
Preventive
Identify problems before they become expensive
(cost avoidance)
Maintain optimum chiller plant efficiency
Restorative
Identify heat transfer problems, i.e., off-design
water flow, fouling or scaling, etc.
Remove non-condensable gases
Maintain proper refrigerant levels
Opportunity
Identify optimal chilled water set points
Proper chiller sequencing and load balancing
Proper tower basin water management
Peak demand management
Condition-based maintenance versus scheduled
preventive maintenance
31 © Hudson Technologies
List of ECMs
ECMs
in evaporator / condenser
Eliminate refrigerant stacking
Remove non-condensable gases
and moisture
Reclaim refrigerant
32 © Hudson Technologies
List of ECMs (continued)
Clean fouled and scaled heat
Medium Cost
exchangers
ECMs
Sequence multiple chillers to optimize
efficiency
Maintain compressor isentropic
efficiency
Improve drive efficiency
Higher Cost
Investigate application of variable
ECMs
frequency drives
Undertake peak load management
strategy
Install water-side economizers
33 © Hudson Technologies
Implement ECWT Management
ECWT – Entering Cooling Water Temperature
Approach
The approach is the difference in temperature between
the cooled-water temperature and the entering-air wet
bulb temperature
Since the cooling towers are based on the principles of
evaporative cooling, the maximum cooling tower
efficiency depends on the wet bulb temperature of air
Wet Bulb
Wet bulb temperature is the lowest temperature that
can be reached by the evaporation of water only
It is determined by the atmospheric pressure, ambient
temperature and the relative humidity
34 © Hudson Technologies
Concept of Lift
35 © Hudson Technologies
Implement ECWT Management
36 © Hudson Technologies
Optimize Settings for ChWST
ChWST – Chilled Water Supply Temperature
Approach / RAT
The approach (RAT) is the difference in temperature
between the chilled-water supply temperature and the
refrigerant saturated temperature in the evaporator
It provides the driving force to transfer the heat from
the water to the refrigerant
Load control
Cooling required is controlled by bypassing chilled
water flow
Alternate methodology – variable pumping
Primary
Secondary
37 © Hudson Technologies
Optimize Settings for ChWST
0.475
0.45
Chiller Performance (kW/RT)
0.425
0.4
0.375
0.35
0.325
0.3
41 42 43 44 45 46 47
CWST (°F)
38 © Hudson Technologies
Clean Fouled and Scaled Evaporator
Water-side fouling
High makeup (leaks) in the closed loop system
Iron fouling from corrosion, microbiological growth and
scale due to insufficient chemical protection
39 © Hudson Technologies
Fouled/Scaled Evaporator
40 © Hudson Technologies
Fouled/Scaled Condenser
March
July
Sept
41 © Hudson Technologies
Reclaim Refrigerant
42 © Hudson Technologies
Reclaim Refrigerant
Moisture in
refrigerant
Presence of Oil
in refrigerant
Particulate in
refrigerant
43 © Hudson Technologies
Impact on Capacity Reclaim Refrigerant
SUMMARY of RESULTS & COST SAVINGS
Total System Design P/L Design F/L Refrigerant
Tons = 1,502 [RT] 1,502 [RT] 2,002 [RT] Design: R134a
com pHP = 1,219 [HP] 1,503 [HP] 2,360 [HP] Currently Used: R134a
HPTon = 0.81 [BHP/RT] 1.001 [HP/Ton] 1.18 [BHP/RT]
678,871 0
45 © Hudson Technologies
Refrigerant Stacking
Raise
ECWT
46 © Hudson Technologies
Sequence Multiple Chillers to Optimize Efficiency
48 © Hudson Technologies
Comparison of Constant Speed & VFD
Chiller Performance
0.75
0.7
Chiller Performance (kW/RT)
Constant Speed
0.65
Variable Frequency
0.6
0.55
0.5
0.45
0.4
0.35
0.3
20 30 40 50 60 70 80 90 100
Cooling Load (% )
49 © Hudson Technologies
Install Water-side Economizers
50 © Hudson Technologies
Undertake a Peak Load Management Strategy
51 © Hudson Technologies
Conclusions
52 © Hudson Technologies
Next Steps
Develop a simple schematic of your Chiller Plant /
Refrigeration system and define the boundaries
Registration Information:
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu
54 © Hudson Technologies
Contact Information
Technical Information
Riyaz Papar, PE, CEM
Hudson Technologies Co.
rpapar@hudsontech.com
http://www.hudsontech.com
Program Information
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu
55 © Hudson Technologies