02 - KW TR Relation PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 55

Introduction to Improving Energy

Efficiency in Chiller Systems

Riyaz Papar, PE, CEM


Director, Global Energy Services
Hudson Technologies Company
rpapar@hudsontech.com

November 2013

1 © Hudson Technologies
Acknowledgments

 Texas Industries of the Future (TXIOF)


 Texas State Energy Conservation Office (SECO)

 Energy Industries in Ohio

 Joe Longo & Derrick Shoemake, Hudson


Technologies

2 © Hudson Technologies
Webinar Agenda

 The Systems Approach

 Fundamentals of Refrigeration

 Chiller Plant Actual Operating Performance

 Predictive and Preventive Maintenance


BestPractices

 Energy Conservation Measures (ECMs)

 Conclusions

3 © Hudson Technologies
Chiller System Energy Cost?
 1,000 Refrigeration Tons chiller plant load
 Chiller System performance = 0.75 kW/ton
 Bundled power cost = $0.085/kWh
600,000

500,000
Operating Cost ($)

400,000

300,000

200,000

100,000

-
4 months 6-8 months All year round
Operating hours

4 © Hudson Technologies
The Systems Approach

5 © Hudson Technologies
The Systems Approach

 Establish current system conditions,


operating parameters, and system energy use
 Investigate how the total system presently
operates
 Identify potential areas where system
operation can be improved
 Analyze the impacts of potential
improvements to the plant system
 Implement system improvements that meet
plant operational and financial criteria
 Continue to monitor overall system
performance
6 © Hudson Technologies
A Chilled Water Plant Systems Approach

7 © Hudson Technologies
Main Driving Force for Change

 Energy
 Reliability
 Maintenance
 Productivity
 Quality
 Cost avoidance
 Emissions reductions

8 © Hudson Technologies
Fundamentals of
Refrigeration

9 © Hudson Technologies
The Refrigeration Cycle
3 R134a
10
P [psia]

Condensation / SubCooling

105°F
2
10 Expansion

Compression
40°F
Ev aporation (Boiling)

0.2 0.4 0.6 0.8

1
10
0 25 50 75 100 125 150
h [Btu/lbm]
State Point
10 © Hudson Technologies
Single Stage Chiller System
HGBP (Hot Gas ByPass)

Compressor

Condenser Cooling Water

Evaporator Chilled Water

HGBP

11 © Hudson Technologies
A Centrifugal
A Water-Cooled
Chiller Chiller System

Condenser

Compressor

Evaporator (Chiller Barrel)

12 © Hudson Technologies
Two Stage Chiller System
HGBP

Compressor

Condenser Cooling Water

Evaporator Chilled Water

Economizer HGBP
(Hot Gas ByPass)

13 © Hudson Technologies
LiBr-Water Absorption Chillers

14 © Hudson Technologies
The Air, Water and Refrigerant Cycle

The Systems Approach

15 © Hudson Technologies
Chiller Plant - Actual
Operating Performance

16 © Hudson Technologies
Chiller Capacity

 Definition of Refrigeration Ton (RT)


 The amount of thermal energy to be
removed from 1 Ton (2,000 lbs) of
water at 32°F to make it into ice at 32°F
in one day (24 hr) is known as 1 RT

 1 RT = 12,000 Btu/hr = 3.517 kW

 Chiller capacity (size or tonnage) is the


amount of full load cooling capacity
provided by the chiller at certain design
conditions
17 © Hudson Technologies
Chiller Performance Metrics

 Most standard rating in the US - kW/RT


(hp/RT)
 Amount of compressor power (kW or
hp) required to produce 1 RT of cooling
or refrigeration

Compressor Power (kW )


kW / RT 
Cooling Load ( RT )

18 © Hudson Technologies
Chiller Full Load Design Specifications

 Obtained from the Chiller Manufacturer

Chiller ID: Chiller #6 Chiller Manufacturer: ZZZZZZZ

Year Commissioned: 1990 Chiller Type: Constant Speed Centrifugal

Model Number: XXXXXXXXXX Serial Number: AAAAAAAA

Refrigerant Type: R-134a Capacity (Tonnage): 2,000

Efficiency (kW/Ton): 0.625 IPLV / NPLV: .541

Full Load Amps (FLA): 198 Volts: 4160

Evaporator Entering Water Temperature: 54.37°F Evaporator Leaving Water Temperature: 44°F

Condenser Entering Water Temperature: 85°F Condenser Leaving Water Temperature: 94.4°F

Evaporator Delta Temperature: 10.37°F Condenser Delta Temperature: 9.4°F

Evaporator GPM: 4,627 Condenser GPM: 6,000

Evaporator Pressure Drop (psig): 9.9 Condenser Pressure Drop (psig): 8.1

19 © Hudson Technologies
Overall Chiller Plant Performance

 Information required
 Total tonnage
 Total kW
 Compressor Power
 Pumping Power
 Cooling Tower Fan Power
 Other (as defined in the scope)

 kW
Plant Performance  n
 Chiller Tons
m

20 © Hudson Technologies
Overall Chiller Plant Performance

21 © Hudson Technologies
Chiller Plant Efficiency Metrics

 Overall chiller plant performance


 Total tonnage
 Total kW (including chillers and auxiliaries)
 Individual chiller efficiency
 Chiller tonnage
 Compressor kW
 Individual Chiller Lift
 Lift is defined as the difference between the refrigerant
saturated condensing and evaporating temperatures
 Individual compressor isentropic efficiency
 Suction and discharge temperatures
 Suction and discharge pressures
 Individual heat exchanger effectiveness
 Approach temperatures
 T on chilled water and cooling tower water

22 © Hudson Technologies
Predictive & Preventive
Maintenance
BestPractices

23 © Hudson Technologies
First Things First – Fluid Management
 Understanding “Cause” and “Effect” is very
important for Root Cause Analysis
 This enhances system reliability and reduces
unplanned shutdown
 Significant savings in Maintenance costs
 Most Maintenance BestPractices are testing-
based
 Refrigerant, Oil and Water Testing
 Rotating equipment monitoring
 Vibration analysis
 Eddy-current testing
 In chiller systems, contaminants affect
efficiency & capacity
 Chemistry Based Solutions
24 © Hudson Technologies
Blood Chemistry

25 © Hudson Technologies
Chiller Chemistry

26 © Hudson Technologies
Refrigerant Analysis Criteria

 Moisture
 Oil
 Particulate
 Chlorides
 Acid
 Purity
 Non-Condensables
 Other Contaminants

27 © Hudson Technologies
Nonferrous cutting wear Severe sliding wear

Ferrography Copper alloy


Oil Analysis sliding wear

28 © Hudson Technologies
Water Testing and Analysis

 Cooling Tower Water testing and analysis


 Open loop – evaporation of water
 Control of corrosion, scale and biological activity
 Material of construction plays a very important role
 Testing conducted for pH, TDS, Conductivity, Hardness,
Alkalinity, Chlorides, Silica, Bacteria, etc.

 Chilled Water testing and analysis


 Closed loop – generally less issues
 Lower temperatures

 Working with a water chemist / treatment


company
 Periodic testing program

29 © Hudson Technologies
Energy Conservation
Measures (ECMs)

30 © Hudson Technologies
3 Methods of Maximizing Chiller Plant Efficiency

 Preventive
 Identify problems before they become expensive
(cost avoidance)
 Maintain optimum chiller plant efficiency
 Restorative
 Identify heat transfer problems, i.e., off-design
water flow, fouling or scaling, etc.
 Remove non-condensable gases
 Maintain proper refrigerant levels
 Opportunity
 Identify optimal chilled water set points
 Proper chiller sequencing and load balancing
 Proper tower basin water management
 Peak demand management
 Condition-based maintenance versus scheduled
preventive maintenance
31 © Hudson Technologies
List of ECMs

 Implement ECWT management


 Optimize settings for ChWST

No Cost / Low Cost


 Eliminate all refrigerant leaks
Maintain design water flow rates

ECMs

in evaporator / condenser
 Eliminate refrigerant stacking
 Remove non-condensable gases
and moisture
 Reclaim refrigerant
32 © Hudson Technologies
List of ECMs (continued)
 Clean fouled and scaled heat

Medium Cost
exchangers

ECMs
 Sequence multiple chillers to optimize
efficiency
 Maintain compressor isentropic
efficiency
 Improve drive efficiency

Higher Cost
 Investigate application of variable

ECMs
frequency drives
 Undertake peak load management
strategy
 Install water-side economizers
33 © Hudson Technologies
Implement ECWT Management
 ECWT – Entering Cooling Water Temperature

 Approach
 The approach is the difference in temperature between
the cooled-water temperature and the entering-air wet
bulb temperature
 Since the cooling towers are based on the principles of
evaporative cooling, the maximum cooling tower
efficiency depends on the wet bulb temperature of air

 Wet Bulb
 Wet bulb temperature is the lowest temperature that
can be reached by the evaporation of water only
 It is determined by the atmospheric pressure, ambient
temperature and the relative humidity
34 © Hudson Technologies
Concept of Lift

35 © Hudson Technologies
Implement ECWT Management

80°F ECWT drops to 70°F ECWT

kW/ton drops from 0.7 to 0.47 (33% improvement)

36 © Hudson Technologies
Optimize Settings for ChWST
 ChWST – Chilled Water Supply Temperature

 Approach / RAT
 The approach (RAT) is the difference in temperature
between the chilled-water supply temperature and the
refrigerant saturated temperature in the evaporator
 It provides the driving force to transfer the heat from
the water to the refrigerant

 Load control
 Cooling required is controlled by bypassing chilled
water flow
 Alternate methodology – variable pumping
 Primary
 Secondary
37 © Hudson Technologies
Optimize Settings for ChWST

0.475

0.45
Chiller Performance (kW/RT)

0.425

0.4

0.375

0.35

0.325

0.3
41 42 43 44 45 46 47

CWST (°F)

38 © Hudson Technologies
Clean Fouled and Scaled Evaporator

 Fouling in the evaporator / cooler


 Refrigerant-side
 Water-side

 Refrigerant-side fouling – Excess Oil

 Refrigerant-side fouling – Water

 Water-side fouling
 High makeup (leaks) in the closed loop system
 Iron fouling from corrosion, microbiological growth and
scale due to insufficient chemical protection

39 © Hudson Technologies
Fouled/Scaled Evaporator

Iron Oxide Scaled


Condition

After tube brushing

40 © Hudson Technologies
Fouled/Scaled Condenser
March

July

Sept

41 © Hudson Technologies
Reclaim Refrigerant

 Over time and operations, the refrigerant in the


chiller gets contaminated and results in
 Fouling of heat exchangers
 Reductions in heat transfer coefficients
 The process of recovering the refrigerant and
bringing it back to AHRI-700 specification
standard is known as “Reclamation”
 Reclaiming a refrigerant improves overall
operating performance and in most cases
increases chiller tonnage (capacity)
 Periodic sampling and testing of refrigerants in
chiller systems is key to ensuring that the chiller
chemistry is well maintained
 Analogous to maintaining water chemistry in boilers

42 © Hudson Technologies
Reclaim Refrigerant

Moisture in
refrigerant
Presence of Oil
in refrigerant

Particulate in
refrigerant
43 © Hudson Technologies
Impact on Capacity Reclaim Refrigerant
SUMMARY of RESULTS & COST SAVINGS
Total System Design P/L Design F/L Refrigerant
Tons = 1,502 [RT] 1,502 [RT] 2,002 [RT] Design: R134a
com pHP = 1,219 [HP] 1,503 [HP] 2,360 [HP] Currently Used: R134a
HPTon = 0.81 [BHP/RT] 1.001 [HP/Ton] 1.18 [BHP/RT]

Steam Rate = 12.02 [lb/hr-HP] 12.03 [lb/hr-HP]


NC% = 0.0 [% ] Superheat Capacity Penalties
Balance Syste m = 0.0 [% ]
Capacity Loss (RT) %

Com ponent Balances Evaporator 2.8 0.1

Balance Evap = 0.0 [% ]

Balance SubCoole r = ???? [% ]


Potential Savings Opportunities
Pressure Ratio (current): 2.6
Annual Energy Costs
Steam Cost = 14.48 [$/1000lb]
Evaporator Condenser System
Hours = 4,000 [Hr]
New Ratio 2.3 2.6 2.3
LFC = 0.80 [kW/ton]
Savings (% ) 13.1 0.0 13.1
Cost ($) NC Penalty ($)

678,871 0

Impact of Oil, Particulate


& Moisture in refrigerant
on energy efficiency &
44 costs © Hudson Technologies
Eliminate Refrigerant Stacking

 Refrigerant stacking impacts heat transfer efficiency


in both the evaporator and condenser - higher
kW/Ton and energy costs

 Leads to reduced compressor capacity

 Chiller surging or stalling

 Shut down on low refrigerant temperature


(pressure)

45 © Hudson Technologies
Refrigerant Stacking

Raise
ECWT
46 © Hudson Technologies
Sequence Multiple Chillers to Optimize Efficiency

 All chillers will have an optimal operation range


(best efficiency point)

 When multiple chillers are operating, the overall


plant’s composite operating curve maybe very
different from the individual chiller’s curve

 It is important to know how each of the chillers


operate under different load conditions

 Pick the best chiller operating combination for


the current operating conditions – Dynamic
Optimization problem (NOT Easy)
47 © Hudson Technologies
Investigate Application of Variable
Frequency Drives (VFD)
 Replacing old chillers with newer energy efficient systems –
most new packaged chillers will come with a VFD option

 VFDs take advantage of lower ambient temperatures (lower


lift) and correspondingly lower cooling loads (lower
refrigerant flow rates)

 VFD pumps and fans can play a very important role in


reducing total system energy consumption

 VFD efficiency is extremely high (99%) and more


importantly, it offers a benefit on the drive side by providing
 Soft start capability
 Power factor correction

48 © Hudson Technologies
Comparison of Constant Speed & VFD
Chiller Performance

0.75
0.7
Chiller Performance (kW/RT)

Constant Speed
0.65
Variable Frequency
0.6
0.55
0.5
0.45
0.4
0.35
0.3
20 30 40 50 60 70 80 90 100
Cooling Load (% )

49 © Hudson Technologies
Install Water-side Economizers

 This ECM is applicable only in certain


geographical areas but can have a huge
impact on energy savings

 Installing a water-side economizer allows for


“free cooling” during times of the year when
the outdoor ambient conditions allow for
very low wet-bulb temperatures

 The cooling tower water provides all (or


some portion) of the chilled water plant load
and reduces the amount of chillers required

50 © Hudson Technologies
Undertake a Peak Load Management Strategy

 Peak demand charges can become excessive


depending on chiller plant management and
operational strategy

 There are 3 ways to manage peak demand


regarding chillers
 Thermal energy storage
 Optimize chiller efficiency to lower kW usage of running
chillers
 Take a chiller off-line

51 © Hudson Technologies
Conclusions

52 © Hudson Technologies
Next Steps
 Develop a simple schematic of your Chiller Plant /
Refrigeration system and define the boundaries

 Use a systems approach to complete an initial assessment to


understand operations and load profile

 Undertake a simple gap analysis to identify any potential


improvement opportunities

 Evaluate each ECM and prioritize based on quantified savings


opportunities

 Put a program in place to ensure that there is proper


Predictive and Preventive Maintenance BestPractices

 Implement an effective Chiller Plant Performance Monitoring,


Diagnostics and Optimization system
53 © Hudson Technologies
1-Day Training Workshop

Introduction to Energy Efficiency in


Chiller Plant Systems
December 17, 2013
8 am – 4 pm

Houston Business RoundTable


5213 Center Street
Pasadena, TX 77505

Facilitator: Riyaz Papar, PE, CEM


Hudson Technologies Co.

Registration Information:
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu

54 © Hudson Technologies
Contact Information

Technical Information
Riyaz Papar, PE, CEM
Hudson Technologies Co.
rpapar@hudsontech.com
http://www.hudsontech.com

Program Information
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu

55 © Hudson Technologies

You might also like