Tank Dimension Calculation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

For OCTC only for 11/22kV for 33kV

L = 3C/C + 60 L = 3C/C + 70
B = C/C + 60/70 {70 for tapchanger's
upto 100kVa (100 breath} B = 3C/C + 80
included ) H = Fp + 2Lp + WH + 80 +
H = Fp + 2Lp + WH + 80 + (A) {For (A){ For tapchanger A = 40
tapchanger A = 40 + tapchanger height} + tapchanger height}
L = 3C/C + 80 L = 3C/C + 80
above 100kVA to B = C/C + 80 B = C/C + 90
315kVA (315 H = Fp + 2Lp + WH + 80 + (A)
included ) H = Fp + 2Lp + WH + 80 + (A) {For { For tapchanger A = 40 +
tapchanger A = 40 + tapchanger height} tapchanger height}
above 315kVA to L = 3C/C + 90 L = 3C/C + 90
630kVA (630 B = C/C + 90 B
H = C/C
Fp +2L 100 W 40 Tc
p H
included ) H = Fp + 2Lp + WH + 40 + Tc + 90 + 90
L = 3C/C + 90 L = 3C/C + 90
above 630kVA to
B = C/C + 100 B = C/C + 110
800kVA (800 H = Fp + 2Lp + WH + 40 + Tc
included )
H = Fp + 2Lp + WH + 40 + Tc + 100 + 100
L = 3C/C + 100 L = 3C/C + 100
above 800kVA to
B = C/C + 130 B = C/C + 130
1600kVA (1600 H = Fp + 2Lp + WH + 40 + Tc
included ) H = Fp + 2L + W + 40 + Tc + 120 + 120
p H
L = 3C/C + 110 L = 3C/C + 110
above 1600kVA to B = C/C + 170 B = C/C + 170
3150kVA H = Fp + 2Lp + WH + 40 + Tc
H = Fp + 2Lp + WH + 40 + Tc + 120 + 120

Tc is the distance between the top yoke


and tapchanger centre line. Take this
value as 70 mm for initial calculation.