Designing A Septic Tank
Designing A Septic Tank
Width = 750mm(min)
Length = 2 to 4 times width
Depth = 1000 to 1300mm. (min below water level) + 300 to 450mm free board
Maximum depth = 1800mm + 450 mm free board
Capacity = 1 cubic meter (10 cubic feet) minimum
ii) Detention period: in the procedure of designing the septic tank, detention period should
have been 24hrs. The rate of flow of waste matter needs to be equal to the rate of flow of
influent.
iii) Inlet and outlet pipes: An elbow or T pipe with 100mm diameter is submerged to a deepness
of 250-600mm below the liquid level. For outlet pipe, an elbow or T kind of 100mm diameter
pipe is submerged to a deepness of 200-500mm below the liquid level. Choose the pipes
which made of stone ware or asbestos.
iv) Baffle walls of Septic Tank: For the tanks small in size, RCC hanging kind scum
baffle walls are set in septic tanks. Baffle walls are arranged adjacent to the inlet. it’s far non-
compulsory close to the outlet.
The inlet baffle wall is set at a gapping of L/5 from the wall, wherein L denotes the length of the
wall. The baffle wall is usually expanded 150mm above to scum level and 400-
700mm underneath it.
Since scum is lighter, it commonly floats on the water level within the tank. The density of the
wall fluctuates from 50mm to 100mm. Inside the lower part of larger tanks, there are holes for
discharging sludge.
v) Roofing Slab of Septic Tank: Primarily based on the size of the tank, RCC slab with density
of 75–100 mm is placed at the top of the septic tank. Round manholes with
500mm clear diameter are organized for inspection and desludging.
For square opening, clear size is maintained as 600X450mm.
vi) Ventilation Pipe: The cast iron or asbestos pipe having 50-100mm diameter is set up as outlet
to discharge polluted gases and for ventilation. The pipes should be expanded 2m (min) over
ground level. On the upper part of the ventilation pipe a mosquito proof wire mess or cowl
should be placed.