Professional Documents
Culture Documents
Main Components of Central Air Conditioning
Main Components of Central Air Conditioning
enters the evaporator in the form of a cool, low-pressure mixture of liquid and vapor (A).
Heat is transferred from the relatively warm air or water tobe cooled to the refrigerant,
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
causing the liquid refrigerant to boil and in some cases superheat (B). The resulting vapor
(B) is then pumped from the evaporator by the compressor, which increases the pressure and
temperature of the refrigerant vapor. Notice that during the compression process (B to C),
the heat content (enthalpy) of the vapor is increased. The mechanical energy used by the
compressor to increase the pressure of the refrigerant vapor is converted to heat energy,
called the heat of compression. This causes the temperature of the refrigerant to also rise as
the pressure is increased. The resulting hot, high-pressure refrigerant vapor (C) enters the
condenser where heat is transferred to ambient air or water at a lower temperature.
Inside the condenser, the refrigerant desuperheats (C to D), condenses into a liquid (D to E),
and, in some cases, subcools (E to F). The refrigerant pressure inside the ondenser is
determined by the temperature of the air or water that is availableas the condensing media.
This liquid refrigerant (F) then flows from the condenser to the expansion device. The
expansion device creates a pressure drop that reduces the pressure of the refrigerant to that of
the evaporator.
At this low pressure, a small portion of the refrigerant boils (or flashes), cooling the
remaining liquid refrigerant to the desired evaporator temperature (A). The cool mixture of
liquid and vapor refrigerant travels to the evaporator to repeat the cycle.
3.2 Compressor
automobile engine. Refrigerant is drawn into the cylinders on the downstroke of the piston
and compressed on the upstroke. Scroll and helical-rotary (or screw) compressors have
become more common, replacing the reciprocating compressor in most applications due to
their improved reliability and efficiency. These three types of compressors (reciprocating,
scroll, and helical-rotary) all work on the principle of trapping the refrigerant vapor and
compressing it bygradually shrinking the volume of the refrigerant. Thus, they are called
positive-displacement compressors. In contrast, centrifugal compressors use the principle
of dynamic compression, which involves converting energy from one form to another in
order to increase the pressure and temperature of the refrigerant.
Since the pressure within the cylinder is less than the pressure of the refrigerant at the
suction side of the compressor, the suction valve is forced open and the refrigerant vapor is
drawn into the cylinder.
along with a fine layer of oil, prevent the compressed refrigerant vapor from escaping
through the mating surfaces. The upper scroll, called the stationary scroll, contains a
discharge port. The lower scroll, called the driven scroll, is connected to a motor by a shaft
and bearing assembly.. In this example scroll compressor, refrigerant vapor enters through
the suction opening. The refrigerant then passes through a gap in the motor, cooling the
motor, before entering the compressor housing. The refrigerant vapor is drawn into the scroll
assembly where it is compressed, discharged into the dome, and finally discharged out of the
compressor through the discharge opening.
helical-rotary compressor, refrigerant vapor is drawn into the compressor through the
suction opening and passes through the motor, cooling it. The refrigerant vapor is drawn into
the compressor rotors where it is compressed and discharged out of the compressor. In the
air-conditioning industry, helical-rotary compressors are most commonly used in water
chillers ranging from 70 to 450 tons [200 to 1,500 kW].
of the impeller is fitted with blades that draw refrigerant vapor into radial passages that are
internal to the impeller body. The rotation of the impeller causes the refrigerant vapor to
accelerate within these passages, increasing
its velocity and kinetic energy. The
accelerated refrigerant vapor leaves the
impeller and enters the diffuser passages.
These passages start out small and become
larger as the refrigerant travels through them.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
As the size of the diffuser passage increases, the velocity, and therefore the kinetic energy,
of the refrigerant decreases. Fig 3-9 Centrifugal Compressor
The first law of thermodynamics states that energy is not destroyed—only converted from
one form to another. Thus, the refrigerant’s kinetic energy (velocity) is converted to static
energy (or static pressure).
In this example centrifugal compressor, refrigerant vapor is drawn into the compressor and
enters the center of impeller. This particular centrifugal
the shaft protrudes through the compressor housing, a seal is used to prevent refrigerant
from leaking out of the compressor housing. This motor is cooled by air that is drawn in
from the surrounding space..
A hermetic compressor, on the other hand, seals the motor within thcompressor housing.
This motor is cooled by the refrigerant, either by refrigerant vapor that is being drawn into
the compressor from the suction line or by liquid refrigerant that is being drawn from the
liquid line. The heat from the motor is then Fig 3-12 Hermetic Compressor
rejected by thcondenser. Hermetic compressors eliminate the need for the shaft couplings
and external shaft seals that are associated with open motors. The coupling needs
precisealignment, and these seals are a prime source of oil and refrigerant leaks.
3.3Condenser
The first major component to be discussed is the condenser. The condenser is a heat
exchanger that rejects heat from the refrigerant to air, water, or some other fluid. The three
common types of condensers are air-cooled, water-cooled, and evaporative .
A typical air-cooled condenser uses propeller-type fans to draw outdoor air over a finned-
tube heat transfer surface. The temperature difference between the hot refrigerant vapor that
is flowing through the tubes and the cooler outdoor air induces heat transfer. The resulting
reduction in the heat content of Fig 3-14 Air cooled condenser
the refrigerant vapor causes it to condense into liquid. Within the final few lengths of
condenser tubing (the subcooler), the liquid refrigerant is further cooled below the
temperature at which it was condensed. The air-cooled condenser is very popular in both
residential and commercial applications because of its convenience.
(the line from A’ to B). The system without subcooling must evaporate substantially more
refrigerant within a larger coil to produce the same capacity as the system with subcooling.
Instead of subcooling in the condenser, some packaged refrigeration equipment, such as
water chillers, may use an economizer or liquid/vapor separator to increase this refrigeration
effect.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
An alternative air-cooled condenser uses a centrifugal fan to draw or blow air over the
condensing coil. The principal advantage of this design is that the centrifugal fan is capable
Fig 3-16 Fan air cooled condenser
of overcoming the higher static-pressure losses associated with ductwork. Therefore, if the
condenser is to be located indoors and uses a duct system to deliver air to and from the
condenser coil, the centrifugal fan air-cooled condenser is probably best suited for this
application.
The remaining water then falls to the sump to be recirculated and used again. Subcooling of
the refrigerant can be accomplished by piping the condensed liquid back through another
few rows of coil tubing, located either in the condenser airstream or in the water sump,
where additional heat transfer reduces the temperature of the liquid refrigerant.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
brings in 85°F [29°C] water and warms it up to 95°F [35°C]. Before this water can be used
again, it must be cooled back down to 85°F [29°C].
cooled water then falls to the tower sump to be returned to the condenser.
Fig 3-19 Cooling tower
The final temperature of the water leaving the tower is determined, in part, by the humidity
of the outdoor air. If the outdoor air is dry, the final water temperature can be considerably
lower than the ambient dry-bulb temperature. If the outdoor air is humid, however, the final
temperature will be near the ambient dry-bulb temperature. While a cooling tower can
reclaim much of the condensing water, it cannot reclaim it all. The evaporation process uses
up water to dissipate heat contributed by the cooling load plus the heat of compression.
3.4 Evaporators
The second major component to be discussed is the evaporator. The evaporator is a heat
exchanger that transfers heat from air, water, or some other fluid to the cool liquid
refrigerant. Two common types of evaporators are the finned-tube and the shell-and-tube.
(the line from B to C) shifts it away from the liquid/vapor region and ensures that the
refrigerant vapor is completely free of liquid prior to traveling to the compressor.
cooling load. These heat exchangers could be coils used to cool air or they could be some
other load that requires chilled water Baffles within the shell direct the water in a rising and
falling flow path over Fig 3-24 Shell-and-Tube Evaporators
A capillary tube is a refrigerant control; its common types of air conditioner expansion valve. The
capillary is simply a length of tubing with a small inside diameter which acts as a constant throttle
on the refrigerant entering the evaporator. A fine filter or filter drier installed at the inlet of the
capillary prevents
dirt from blocking
the tube.
Fig 3-27 2
Capillary tube
A recent
development in the design of capillary tubes for air conditioning system uses capillary tubes
with a larger insider diameter and a longer tube length. A larger diameter tubes are less
likely to become plugged with dirt and other impurities than a smaller diameter tube. The
long length provides the necessary resistance to create the desired pressure difference across
the metering device. The capillary tube equalizes the pressure in the system when the unit
stops. This pressure equalizing characteristic of the capillary allows a low starting torque
motor to be used with the compressor. Typically, a capillary does not operate as efficiently
over a wide range of conditions as does the thermostatic expansion valve. However, because
of its counterbalance factors in most applications, its performance is generally very good.
Refrigeration systems using a capillary tube doesn’t require the use of a liquid receiver since
all the liquid is stored in the evaporator during the off cycle. However, a suction accumulator
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
is often found in the suction line to prevent any non vaporized refrigerant from reaching the
compressor. This will prevents damage to the compressor when excessive liquid refrigerant
enters the evaporator on a low evaporator load condition.
3.6 Accessories
This can present a problem if some of the refrigerant drains into the suction line and slugs
the compressor when it starts up again. To prevent this from occurring, many systems pump
the refrigerant out of the evaporator and suction line before shutting the compressor off.
cause problems in any refrigeration system. When water is mixed with refrigerant and oil,
and heat is added by the compressor, acids are formed that can damage the valves or
compressor.
replaceable core type allows the core to be easily replaced. The sealed type is completely
closed, reducing the Fig 3-31 Liquid-Line Filter Drier
chances of refrigerant leaks. Ball-type shutoff valves are typically installed just upstream and
downstream to allow the filter drier to be isolated and the core (or unit) replaced.
are required to determine proper charge and subcooling. With the sight glass installed
directly ahead of the expansion valve, it can also be used to detect the presence of bubbles in
the liquid line. This would indicate that some of the liquid refrigerant has flashed into vapor
upstream of the expansion valve. Since the expansion valve is designed to control the flow
of liquid refrigerant only, the presence of refrigerant vapor results in a reduction in the
quantity of liquid refrigerant being fed to the evaporator. There are many potential causes of
liquid refrigerant flashing. The sight glass can alert the operator to the conditio
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
Similar to the liquid-line filter drier, the two common types of suction line filtersare
replaceable core and sealed. The replaceable core type allows the core to beeasily replaced.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
The sealed type is completely closed, reducing the chances ofrefrigerant leaks.Replaceable
core suction filters are commonly installed after a compressorfailure has occurred. The core
is replaced after the foreign matter or acid hasbeen
reciprocating pistons. The muffler contains a perforated tube inside a shell. The pressure
peaks cause some of the refrigerant vapor to pass from the perforated tube into the muffler
shell. This shell is divided into chambers that allow it to absorb these peaks. In essence, the
muffler shaves off the peaks of these pulsations and fills in the valleys,
Additionally, they can be used to trap the refrigerant charge in one component of the system,
the condenser for example, to permit service or repair to another part of the system.
Common uses of shutoff valves include: Isolating the liquid-line filter drier and suction filter
to allow easier core (or unit) Fig 3-36 Shutoff Valve
replacement Isolating the compressor from the rest of the system to allow for repair or
replacement Isolating the charge within the condenser or a receiver to allow access to the
rest of the system
used to measure subcooling. The suction line typically includes two access ports. One is
installed near the compressor and is used to measure suction pressure. The other is located
near the external equalizer-line connection for the expansion valve, and is used to measure
superheat when checking or adjusting the expansion valve setting.
corrosion inhibitors; other fluids such as thin oils can be chilled as well.Chilled water is used
to cool and dehumidify air in mid- to large-size commercial, industrial, and institutional
Most chillers are designed for indoor operation, but a few are weather-resistant. Chillers are
precision machines that are very expensive to purchase and operate,
Where available, cold water readily available Fig 3-40 Water-cooled chillers
in nearby water bodies might be used directly for cooling, or to replace or supplement
cooling towers It dispensed with the need for cooling towers, with a significant cut in
[[carbon emissions]] and energy consumption. It uses cold lake water to cool the chillers,
which in turn are used to cool city buildings
via a [[district heating district cooling]]
system.
3.8.1 Introduction
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
Air handling unit and often abbreviated to AHU, is a device used as part of a heating,
ventilating, and air-conditioning (HVAC) system. Usually, an air handler is a large metal
box containing a blower, heating and cooling elements filter racks or chambers, sound
attenuators, and dampers. Air handlers usually connect to ductwork that distributes the
conditioned air through the building, and returns it to the AHU.
box simulated in the model. A variant of this design has a separate outside air damper
that is adjusted to provide the minimum outside air flow required during occupancy.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
3.8.2.2 Dampers
3.8.2.3 Filters
and other filters. Selection of filters depends on the indoor air quality requirements.
3.8.2.4 Coils
coils are available to suit the client needs. Coils are manufacturing from seamless copper
tubes expanded in aluminum Fig 3-48 coils
fins and they are provided with manual air vent accessible from out side casing for quick
venting. Coils are available from 1-12 rows for both chilled water and DX-systems and
from 1-4 rows for heating coils. Finally coils are Anti-corrosion coating.
3.8.2.5 Fans
Supply & return /exhaust fans are centrifugal fans and all fans are selected for optimum
outlet velocities and low sound level. Fans are supplied with flexible connection between
fan discharge outlet and the unit casing. The fan shaft is made of steel machined and the
bearing is ball bearing.
3.9.1 Introduction
A basic air-distribution system includes supply air and return air. An air-distribution
system should be zoned to deliver an adequate amount of supply air to the cooling air
intake vents of the server equipment cabinets. Supply air temperature should be
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
maintained within the following parameters: The following three types of air distribution
systems are listed in order of recommendation
2) Ceiling plenum air distribution system—Supply air is ducted into the ceiling plenum
from up flow air-conditioning equipment located in the computer room or from an air
handling unit (remote).
1) Air distribution system comprising various inlets for recalculated air and outlets for
supply air.
Frictional effects may sometimes be important, but usually they are neglected. However, the
external work transfer is always assumed to be zero. It is also assumed that changes in
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
thermal energy are significantly greater than changes in potential energy and therefore the
latter can usually be neglected for the purpose of analysis.
Square
ceiling
The amount of air delivered by outlet should be proportional to the load of the
part of space for which it installed.
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
The selection of the type of outlet is governed by the ceiling high, nature of
room, occupancy, etc.
The location of the outlet should be governed by the condition of uniform air
distribution and rapid temperature equalization.
The selection of size of the outlet can be made from the manufacture's catalog
data according to the air delivery.
There should not be any short-circuiting of air between the supply outlet and
return inlet.
The return air which is either too cool in winter or too warm in summer or
contains dirt, gasses or odors should be removed without causing any drafts in
conditioned space by making the undesirable product to move in its natural
direction.
The velocity of air decreases rapidly as one move away from the inlet.
The consideration of noise is a little more in the case of return inlets as they are
normally located near the ear-level. In this case the velocity in the return inlets
should not exceed 75 % of the velocity in the supply air outlets.
Make sure any other specification are met (noise, total pressure. Etc,).
3.10 Ducts
used in heating, ventilation, and air conditioning (HVAC) to deliver and remove air. These
needed airflows include, for example,
supply air, return air, and exhaust air.[1]
Ducts also deliver, most commonly as
part of the supply air, ventilation air. As
such, air ducts are one method of
ensuring acceptable indoor air quality as
well as thermal comfort. A duct system
is often called ductwork. Planning
('laying out'), sizing, optimizing,
detailing, and finding the pressure losses
through a duct system is called duct
design
Fig 3-51 Duct
3.10.1 Materials
Traditionally, air ductwork is made of sheet metal which is installed first and then lagged
with insulation as a secondary operation. Ductwork manufactured from rigid insulation
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
panels does not need any further insulation and is installed in a single fix. Light weight and
installation speed are among the features of preinsulated aluminium ductwork, also custom
or special shapes of ducts can be eas ily fabricated in the shop or on site.
Among the various types of rigid polyurethane foam panels available, a new water
formulated panel stands out. In this particular panel, the foaming process is obtained through
the use of water instead of the CFC, HCFC, HFC and HC gasses. And most manufacturers of
rigid polyurethane foam panels use normal pentane as foaming agent instead of the CFC,
HCFC, HFC and HC gasses, so dose manufacturers of rigid phenolic foam panels.
automatically trims out a "valley" with 45° sides; the valley does not quite penetrate the
entire depth of the duct board, providing a thin Fig 3-53 Fiberglass
section that acts as a hinge. The duct board can then be folded along the valleys to produce
90° folds, making the rectangular duct shape in the fabricator's desired size. The duct is then
closed with staples and special aluminum or similar 'metal-backed' tape. Commonly
available duct tape should not be used on air ducts, metal, fiberglass, or otherwise, that are
intended for long-term use; the adhesive on so called 'duct tape' dries and releases with time.
and is usually composed of polyethylene or metalised PET. Flexible duct is very convenient
for attaching supply air outlets to the rigid ductwork. However, the pressure loss through
flex is higher than for most other types of ducts. As such, designers and installers attempt to
keep their installed lengths (runs) short, e.g., less than 15 feet or so, and to minimize turns.
Kinks in flex must be avoided. Some flexible duct markets prefer to avoid using flexible
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
duct on the return air portions of HVAC systems, however flexible duct can tolerate
moderate negative pressures - the UL181 test requires a negative pressure of 200 Pa.
3.10.1.3 Fabric
extile ducts are not usually concealed within false ceilings, because of this, they are
manufactured in various colours to coordinate with the interior. Fabric ducts fitted above a
ceiling will need to be pvc coated so that no maintenance is required to maintain
performance.
A duct system often begins at an air handler. The blowers in the air handlers can create
substantial vibration and the large area of the duct system would transmit this noise and
vibration to the inhabitants of the building. To avoid this, Fig 3-57 Vibration
isolators
vibration isolators (flexible sections) are normally inserted into the duct immediately before
and after the air handler. The rubberized canvas-like material of these sections allow the air
handler to vibrate without transmitting much vibration to the attached ducts.
3.10.2.2 Take-offs
Take-offs may be fitted into round or rectangular openings cut into the wall of the main duct.
The take-off commonly has many small metal tabs that are then bent to retain the take-off on
the main duct; round versions are called spin-in fittings. Other take-off designs use a snap-in
Chapter 3 [MAIN COMPONENTS OF CENTRAL AIR CONDITIONING]
attachment method, sometimes coupled with an adhesive foam gasket to provide improved
sealing.
registers or diffusers that spread air into individual rooms, dampers can be fitted within the
ducts themselves. These dampers may be manual or automatic.
Fig 3-60 Volume Control Dampers
AHU (Air Handling Unit) or elsewhere within the run. Once smoke is detected within the
duct, the Actuator triggers the motor release and the smoke damper will automatically close
until manually re-opened. You will also find Fire dampers in the same places as smoke
dampers, depending on the application of the area after the firewall.
3.10.2.6 Plenums
handler. The supply plenum directs air from the central unit to the rooms which the system is
designed to heat or cool.