VPs =09asgiven
SP =0 (since the end of the duct is at atmospheric
pressure)
SP) =SP,—R(VPs)
0-(0.52)(0.70¥0.90°)
5-033 "wg
FSP. = SPoutet~ SPrict— VPinst
=~0.33- (-7.27) -0.9=6.04"wg
5.16 EXHAUST STACK OUTLETS
‘The final component of the ventilation system is the ex-
hhaust stack, an extension of the exhaust duct above the roof.
There are two reasons for the placement of an exhaust stack
on a ventilation system. First, the air exhausted by a local
exhaust system should escape the building envelope. Second,
nce it has escaped the building envelope, the stack should
provide sufficient dispersion so that the plume does not cause
an unacceptable situation when it reaches the ground. This
brief description of stack design will address only the first
When placing an exhaust stack on the roof of a b
the designer must consider several factors. The most impor-
tant is the pattern of the air as it passes the building. Even in
the case of a simple building design with a perpendicular
‘wind, the ar flow pattems over the building can be complex
to analyze. Figure 5-28a shows the complex interaction be-
tween the building and the wind at height H. A stagnation
zone is formed on the upwind wall. Air flows away from the
stagnation zone resulting in a down draft near the ground.
Vortices are formed by the wind action resulting in a recireu-
lation zone along the front of the roof or roof obstructions,
«down flow along the downwind side, and forward flow along,
the upwind side of the building.
Figure 5-28 shows a schematic of the critical zones
formed within the building cavity. A recirculation zone is,
formed at the leading edge of the building. A recirculation
zone is an arca where a relatively fixed amount of air moves
in a circular fashion with little air movement through the
boundary. A stack discharging into the recirculation zone can
contaminate the zone. Consequently, all stacks should pene-
trate the recirculation zone boundary.
‘The high turbulence region is one through which the air
passes; however, the flow is highly erratic with significant
downward flow, A stack that discharges into this region will,
‘contaminate anything downwind of the stack. Consequently,
all stacks should extend high enough thatthe resulting plume
ddoes not enter the high turbulence region upwind of an air
intake.
Because ofthe complex flow pattems around simple build
ings, it is almost impossible to locate a stack that is not
influenced by vortices formed by the wind. Tall stacks are
often used to reduce the influence of the turbulent flow, to
Exhaust System Design Procedure $33,
release the exhaust air above the influence of the building and,
to prevent contamination of the air intakes. Selection of the
proper location is made more difficult when the facility has
‘several supply and exhaust systems and when adjacent build-
ings or terrain cause turbulence around the facility itself.
When locating the stack and outdoor air inlets forthe air
handling systems, itis often desirable to locate the intakes
upwind of the source. However, often there is no true upwind
position. The wind in all locations is variable. Even when
there isa natural prevailing wind, the direction and speed are
‘constantly changing. If stack design and location rely on the
direction ofthe wind, the system will clearly fil
‘The effect of wind on stack height varies with speed:
+ Atvery low wind speeds, the exhaust jet from a vertical
stack will rise above the roof level resulting, in
significant dilution at the ir intakes.
+ Increasing wind speed will decrease plume rise and
‘consequently decrease dilution,
‘+ Increasing wind speed will increase turbulence and
consequently increase ditution,
‘The prediction of the location and form of the recirculation
cavity, high turbulence region and roof wake is difficult
However, for wind perpendicular to a rectangular building,
the height (H) and the width (W) of the upwind building face
determine the airflow patterns. The critical dimensions are
shown in Figure 5-28, According to Wilson,°® the eritical
dimensions depend on ascaling coefficient (R) which is given
by:
R= Bi xBi* (59)
‘where B, isthe smaller and By isthe larger of the dimensions
Hand W. When By s argerthan 8B, use B,=8 B, to calculate
the scaling coefficient. Fora building witha flat roof, Wil-
son” estimated the maximum height (H), center (X.), and
lengths (L, of the recirculation region as follows,
(5.10)
ea)
(5.13)
In addition, Wilson estimated the length of the building,
wake recirculation region by:
L=10R [13]
‘The exhaust air from a stack often has not only an upward
‘momentum due to the exit velocity of the exhaust air but,
‘buoyancy due to its density as well. For the evaluation of the
stack height, the effective height is used (see Figure 5-29a).
‘The effective height isthe sum ofthe actual stack height (Hi),
the rise due tothe vertical momentum of the air, and any wake
downwash effect that may exist. A wake downwash occurs,
‘when air passinga stack forms a downwind vortex, The vortexS34 Industrial Ventilation
‘will draw the plume down, reducing the effective stack height,
(see Figure 5-29b). This vortex effect is eliminated when the
exit velocity is greater than 1.5 times the wind velocity. Ifthe
exit velocity exceeds 3000 fpm, the momentum of the exhaust
air reduces the potential downwash effect
The ideal design extends the stack high enough that the
expanding plume does not meet the wake region boundary.
‘More realistically, the stack isextended so thatthe expanding
pplume does not intersect the high turbulence region or any
recirculation cavity. According to Wilson, °° the high turbu-
ence region boundary (Z) follows a 1:10 downward slope
from the top of the recirculation cavity
‘To avoid entrainment of exhaust gas ino the wake, stacks
must terminate above the recirculation cavity. The effective
stack height to avoid excessive reentry can be caleulated by
assuming that the exhaust plume spreads from the effective
stack height with a slope of 1:5 (see Figure 5-280). The first
step isto raise the effective stack height until the lower edge
of the I:S sloping plume avoids cantact with all recirculation
Zone boundaries. The zones can be generated by rooftop
obstacles such as ir handling units, penthouses or architec-
tural sereens. The heights ofthe cavities are determined by
Equations §.10, 5.11 and 5.12 using the scaling coefficient for
the obstacle. Equation 5.13 can be used to determine the
length ofthe wake recirculation zone downwind ofthe obsta-
cle
If the air intakes, including windows and other openings,
are located on the downwind wall, the lower edge of the plume
with a downward slope of 1:5 should not intersect with the
recirculation cavity downwind of the building. The length of
the recireulation cavity (L,) is given by Equation 5.13. Ifthe
air intakes are on the roof, the downward plume should not
intersect the high turbulence region above the air intakes
When the intake is above the high turbulence boundary,
extend a Tine from the top of the intake to the stack with a
slope of 1:5. When the intake is below the high turbulence
region boundary, extend a vertical line to the boundary, then
extend back to the stack with a slope of 1:5. This allows the
caleulation ofthe necessary stack height. The minimum stack
height can be determined for each air intake. The maximum
of these heights would be the required stack height.
In large buildings with many air intakes, the above proce-
dure will result in very tall stacks. An alternate approach isto
estimate the amount of dilution that is afforded by stack
height, distance between the stack and the air intake and
intemal ditution that occurs within the system itself, This
approach is presented in the "Airflow Around Buildings"
chapter in the Fundamentals volume of the 1993 ASHRAE
Handbook?
5.16.1 Stack Considerations:
1. Discharge velocity and gas temperature influence the
effective stack height.
2. Wind can cause a downwash into the wake of the stack
reducing the effective stack height. Stack velocity
should beat least 1.5 times the wind velocity to prevent
downwash,
A good stack velocity is 3000 Spm because it
+ Prevents downwash for winds up to 2000 fpm (22
mph). Higher wind speeds have significant dilution
effects,
+ Increases effective stack height.
+ Allows selection of a smaller centrifugal exhaust
fan to provide a more stable operation point on the
fan curve (see Chapter 6).
*+ Provides conveying velocity if there is dust in the
exhaust or there is a failure of the air cleaning
device
4, High exit velocity isa poor substitute for stack height.
For example, a flush stack requires a velocity over
'8000 fp to penetrate the recirculation cavity bound-
ary.
5. The terminal velocity of rain is about 2000 fpm. A.
stack velocity above 2600 fpm will prevent rain from
centering the stack when the fan is operating,
6. Locate stacks on the highest roof ofthe building when
possible. If not possible, a much higher stack is re
4uited to extend beyond the wake of the high bay,
penthouse, or other obstacle.
7. The use of an architectural screen should be avoided
‘The sereen becomes an obstacle and the stack must be
raised to avoid the wake effect of the screen,
8. The best stack shape is a straight cylinder. Ifa drain is
required, a vertical stack head is preferred (see Figure
5-30). In addition, the fan should be provided with a
drain hole and the duct should be slightly sloped
toward the fan,
9. Rain caps should not be used. The rain cap directs the
air toward the roof, increases the possiblity of reentry,
and eauses exposures to maintenance personnel on the
roof. Moreover, rain caps are not effective. A field
study” with a properly installed standard rain cap
showed poor performance, A 12-inch diameter stack
assed 16% of all rain and as high as 45% during
ndividual storms.
10. Separating the exhaust points from the ai intakes can
reduce the effect of reentry by increasing dilution.
11, In some circumstances, several small exhaust systems
can be manifolded to a single exhaust duct to provide
intemal dilution thereby reducing reentry
12. A combined approach of vertical discharge, stack
height, remote air intakes, proper air cleaning device,
and intemal dilution can be effective in reducing the‘consequences of reentry.
13. A tall stack is not an adequate substitute for good
‘emission control, The reduction achieved by properly
designed air cleaning devices can have a significant
impact on the potential for reentry.
5.7 AIR BLEEDNS
Bleec-ins are used at the ends of branch ducts to provide
additional air flow rates to transport heavy material loads as,
in woodworking at saws and jointers or atthe ends of @ main
‘duct to maintain minimum transport velocity when the system
hhas been oversized deliberately to provide for future expan-
sion. Some designers use bleed-ins also to introduce addi
tional air to an exhaust system to reduce air temperature and,
to assist in balancing the system.
EXAMPLE
End cap bleed-in (see sketch). Consider it to be an orifice
or slot, From Figure 5-13, h,= 1.78 VP.
1. Calculate SP for branch duct to junction (X)
2, Determine flow rate in main duct according to design
or future capacity or determine Q bleed-in directly
from temperature or moisture considerations.
- Q bleedin = (Q main duct) (Q branch)
4, SP bleed-in= SP branch as calculated » (h, + VP) =
(178 + 1.0) ve
sP__ SP
5. VP, bledsin = —-S®— . $
Meike (178+10) 278
6. Velocity, bleed-in from VP and Table 5-7a,
bleedin
V bleedin
7. Area bleod-in =
5.18 OPTIMUM ECONOMIC VELOCITY
In systems which are intended to carry dust, a minimum
conveying velocity is necessary to ensure that the dust will
not settle in the duct. Also, when a system is installed in a
quiet area, it may be necessary to keep velocities below some
‘maximum to avoid excessive ductnoise, When axial flow fans,
are used, duct velocities of 1000 to 1500 fpm are preferred.
In a gas or vapor exhaust system installed in atypical factory
Exhaust System Design Procedure 5.35
environment where none of these restrictions apply, the ve~
locity may be selected to yield the lowest annual operating
cost.
To determine the optimum economic velocity, the system
must first be designed at any assumed velocity and the total
initial costs of duct material, fabrication, and installation
estimated "9
‘This optimum economic velocity may range from under
2000 fpm to over 4000 fpm. Lengthy expected service periods
and system operating times tend to lower the optimum while
high interest rates and duct costs tend to raise the optimum,
In general, a velocity of 2500 to 3000 fm will not result in
equivalent total annual costs much in excess of the true
optimum,
5.19 CONSTRUCTION GUIDELINES FOR LOCAL
EXHAUST SYSTEMS.
Ducts are specified most often for use in the low static
pressure range (-10 "wg to +10 "wg), but higher static pres-
sures are occasionally encountered. The duct conveys air or
gas which is sometimes at high temperatures and often con-
taminated with abrasive particulate or corrosive aerosols.
‘Whether conditions are mild or severe, correct design and
‘competent installation of duets and hoods are necessary for
proper functioning of any ventilation system. The following,
‘minimum specifications are recommended.
Exhaust systems should be constructed with materials suit-
able for the conditions of service and installed ina permanent
‘and workman-like manner. To minimize frietion loss and
turbulence, the interior of all ducts should be smooth and free
from obstructions — especially at joints.
5.19.1 Materials: Ducts are constructed of black iron,
‘which has been welded, flanged, and gasketed; or of welded
galvanized sheet steel unless the presence of corrosive gases,
vapors, and mists or other conditions make such material
impractical. Are welding of black iron lighter than 18 gauge
isnot recommended. Galvanized construction is not recom
mended for temperatures exceeding 400 F. The presence of
corrosive gases, vapor, and mist may require the selection of
corrosive resistant metals, plasties, or coatings. It is recom
‘mended that a specialist be consulted for the selection of
materials best suited for applications when corrosive atmos-
pheres are anticipated. Table 5-4 provides a guide for selec-
tion of materials for corrosive conditions.
5.19.2 Construction:
1. There are four classifications for exhaust systems on
noncorrosive applications:
Class 1 — Light Duty: Includes nonabrasive applica-
tions (eg., replacement air, general ventilation, gase-
‘ous emissions control).
Class 2— Medium Duty: includes applications with