Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

Control Sequence Document for Segment F:\UNIT2\SGS.

SRC Mon Oct 22 10:40:29 2018 Page - 1

<<< Rung Number 1 >>>


----------------------------------------------------------------
---- Segment name: sgs
----------------------------------------------------------------
----
---- Created by RLD_MSE on: Fri Oct 19 09:45:00 2018
----
----------------------------------------------------------------

<<< Rung Number 2 >>>


-
-
-
-
- SGS.SRC for P.T. CIKARANG
- P.T. CIKARANG
- P.T. CIKARANG
- PJV550
- A88G295724
-
- 19/10/2018
-
- MO-447 RELOCATION PLC SGS TO MARK V
-
-
-

<<< Rung Number 3 >>>


HP DRUM LEVEL HIGH

<<< Rung Number 4 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
HPLV1 0║ A┌───┐ ∙ ║ LHPLV1HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KHPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

HPLV1 -- HP DRUM LEVEL TRANSMITTER 1 mils


SGS 4 SGS 18

KHPLVHH -- mils <+200 mils>


SGS 4 SGS 5 SGS 6

LHPLV1HH -- HP DRUM LEVEL 1 HIGH-HIGH LOGIC


SGS -4 SGS 7

<<< Rung Number 5 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
HPLV2 0║ A┌───┐ ∙ ║ LHPLV2HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KHPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

HPLV2 -- HP DRUM LEVEL TRANSMITTER 2 mils


SGS 5 SGS 19

KHPLVHH -- mils <+200 mils>


SGS 4 SGS 5 SGS 6

LHPLV2HH -- HP DRUM LEVEL 2 HIGH-HIGH LOGIC


SGS -5 SGS 8
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 2

<<< Rung Number 6 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
HPLV3 0║ A┌───┐ ∙ ║ LHPLV3HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KHPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

HPLV3 -- HP DRUM LEVEL TRANSMITTER 3 mils


SGS 6 SGS 20

KHPLVHH -- mils <+200 mils>


SGS 4 SGS 5 SGS 6

LHPLV3HH -- HP DRUM LEVEL 3 HIGH-HIGH LOGIC


SGS -6 SGS 9

<<< Rung Number 7 >>>

LHPL LHPL
V1HH V1NHH
───┤/├────────────────────────────────────────────────────────────( )

LHPLV1HH -- HP DRUM LEVEL 1 HIGH-HIGH LOGIC


SGS -4 SGS 7

LHPLV1NHH -- CO HP DRUM LEVEL 1 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -7

<<< Rung Number 8 >>>

LHPL LHPL
V2HH V2NHH
───┤/├────────────────────────────────────────────────────────────( )

LHPLV2HH -- HP DRUM LEVEL 2 HIGH-HIGH LOGIC


SGS -5 SGS 8

LHPLV2NHH -- CO HP DRUM LEVEL 2 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -8

<<< Rung Number 9 >>>

LHPL LHPL
V3HH V3NHH
───┤/├────────────────────────────────────────────────────────────( )

LHPLV3HH -- HP DRUM LEVEL 3 HIGH-HIGH LOGIC


SGS -6 SGS 9

LHPLV3NHH -- CO HP DRUM LEVEL 3 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -9

<<< Rung Number 10 >>>


IP DRUM LEVEL HIGH

<<< Rung Number 11 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
IPLV1 0║ A┌───┐ ∙ ║ LIPLV1HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KIPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝
IPLV1 -- IP DRUM LEVEL TRANSMITTER 1 mils
SGS 11 SGS 23
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 3

KIPLVHH -- mils <+200 mils>


SGS 11 SGS 12 SGS 13

LIPLV1HH -- IP DRUM LEVEL 1 HIGH-HIGH LOGIC


SGS -11 SGS 14

<<< Rung Number 12 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
IPLV2 0║ A┌───┐ ∙ ║ LIPLV2HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KIPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

IPLV2 -- IP DRUM LEVEL TRANSMITTER 2 mils


SGS 12 SGS 24

KIPLVHH -- mils <+200 mils>


SGS 11 SGS 12 SGS 13

LIPLV2HH -- IP DRUM LEVEL 2 HIGH-HIGH LOGIC


SGS -12 SGS 15

<<< Rung Number 13 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
IPLV3 0║ A┌───┐ ∙ ║ LIPLV3HH
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
KIPLVHH 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

IPLV3 -- IP DRUM LEVEL TRANSMITTER 3 mils


SGS 13 SGS 25

KIPLVHH -- mils <+200 mils>


SGS 11 SGS 12 SGS 13

LIPLV3HH -- IP DRUM LEVEL 3 HIGH-HIGH LOGIC


SGS -13 SGS 16

<<< Rung Number 14 >>>

LIPL LIPL
V1HH V1NHH
───┤/├────────────────────────────────────────────────────────────( )

LIPLV1HH -- IP DRUM LEVEL 1 HIGH-HIGH LOGIC


SGS -11 SGS 14

LIPLV1NHH -- CO IP DRUM LEVEL 1 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -14

<<< Rung Number 15 >>>

LIPL LIPL
V2HH V2NHH
───┤/├────────────────────────────────────────────────────────────( )

LIPLV2HH -- IP DRUM LEVEL 2 HIGH-HIGH LOGIC


SGS -12 SGS 15

LIPLV2NHH -- CO IP DRUM LEVEL 2 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -15
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 4

<<< Rung Number 16 >>>

LIPL LIPL
V3HH V3NHH
───┤/├────────────────────────────────────────────────────────────( )

LIPLV3HH -- IP DRUM LEVEL 3 HIGH-HIGH LOGIC


SGS -13 SGS 16

LIPLV3NHH -- CO IP DRUM LEVEL 3 NOT HIGH-HIGH SIGNAL TO STG LOGIC


SGS -16

<<< Rung Number 17 >>>


HP DRUM LEVEL LOW 2OO3 VOTING

<<< Rung Number 18 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KHPLVLL 0║ A┌───┐ ∙ ║ LHPLV1LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
HPLV1 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

HPLV1 -- HP DRUM LEVEL TRANSMITTER 1 mils


SGS 4 SGS 18

KHPLVLL -- mils <-460 mils>


SGS 18 SGS 19 SGS 20

LHPLV1LL -- HP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -18 SGS 21 SGS 50

<<< Rung Number 19 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KHPLVLL 0║ A┌───┐ ∙ ║ LHPLV2LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
HPLV2 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

HPLV2 -- HP DRUM LEVEL TRANSMITTER 2 mils


SGS 5 SGS 19

KHPLVLL -- mils <-460 mils>


SGS 18 SGS 19 SGS 20

LHPLV2LL -- HP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -19 SGS 21 SGS 51

<<< Rung Number 20 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KHPLVLL 0║ A┌───┐ ∙ ║ LHPLV3LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
HPLV3 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝
HPLV3 -- HP DRUM LEVEL TRANSMITTER 3 mils
SGS 6 SGS 20

KHPLVLL -- mils <-460 mils>


SGS 18 SGS 19 SGS 20
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 5

LHPLV3LL -- HP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -20 SGS 21 SGS 52

<<< Rung Number 21 >>>

LHPL LHPL LHP


V1LL V2LL LVLL
───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
LHPL │ │
V3LL │ │
───┤ ├──┘ │

LHPL LHPL │
V1LL V3LL │
───┤ ├──────┤ ├──┘

LHPLV1LL -- HP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -18 SGS 21 SGS 50

LHPLV2LL -- HP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -19 SGS 21 SGS 51

LHPLV3LL -- HP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -20 SGS 21 SGS 52

LHPLVLL -- HP DRUM LEVEL 2oo3 LOW-LOW LOGIC


SGS -21 SGS 53

<<< Rung Number 22 >>>


IP DRUM LEVEL LOW 2oo3 VOTING

<<< Rung Number 23 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KIPLVLL 0║ A┌───┐ ∙ ║ LIPLV1LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
IPLV1 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

IPLV1 -- IP DRUM LEVEL TRANSMITTER 1 mils


SGS 11 SGS 23

KIPLVLL -- mils <-460 mils>


SGS 23 SGS 24 SGS 25

LIPLV1LL -- IP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -23 SGS 26 SGS 54

<<< Rung Number 24 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KIPLVLL 0║ A┌───┐ ∙ ║ LIPLV2LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
IPLV2 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

IPLV2 -- IP DRUM LEVEL TRANSMITTER 2 mils


SGS 12 SGS 24

KIPLVLL -- mils <-460 mils>


SGS 23 SGS 24 SGS 25

LIPLV2LL -- IP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -24 SGS 26 SGS 55
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 6

<<< Rung Number 25 >>>


╔═══════════╗
║ CMP ║
LTRUE Enable ║ ║
───┤ ├──────────────────────────────────────────────────╫────────┐ ║
║ ∙ ║
KIPLVLL 0║ A┌───┐ ∙ ║ LIPLV3LL
──────────────────╫──┤ │ ∙ ║
║ │ ├┤ ├─╫──────────( )
IPLV3 1║ B│A>B│ ║
──────────────────╫──┤ │ ║
║ └───┘ ║
╚═══════════╝

IPLV3 -- IP DRUM LEVEL TRANSMITTER 3 mils


SGS 13 SGS 25

KIPLVLL -- mils <-460 mils>


SGS 23 SGS 24 SGS 25

LIPLV3LL -- IP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -25 SGS 26 SGS 56

<<< Rung Number 26 >>>

LIPL LIPL LIP


V1LL V2LL LVLL
───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
LIPL │ │
V3LL │ │
───┤ ├──┘ │

LIPL LIPL │
V1LL V3LL │
───┤ ├──────┤ ├──┘

LIPLV1LL -- IP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -23 SGS 26 SGS 54

LIPLV2LL -- IP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -24 SGS 26 SGS 55

LIPLV3LL -- IP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -25 SGS 26 SGS 56

LIPLVLL -- IP DRUM LEVEL 2oo3 LOW-LOW LOGIC


SGS -26 SGS 57

<<< Rung Number 27 >>>


DIVERTER DAMPER 2oo3 VOTING

<<< Rung Number 28 >>>

LDDC1 LDDC2 LDDC


───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
│ │
LDDC3 │ │
───┤ ├──┘ │


LDDC1 LDDC3 │
───┤ ├──────┤ ├──┤

L3COM_ │
LDDC1 B │
───┤ ├──────┤/├──┘

L3COM_B -- LOGIC
SEQ_TRB1 -15.3 SEQ_TRB1 15.4 SEQ_TRB1 58.2 SEQ_TRB1 58.4 SEQ_TRB1 58.6
SEQ_TRB1 58.9 DAMPER 6 DAMPER 9 DAMPER 58 SEQ_LOAD 108
SEQ_AUX 3.2 SEQ_AUX 4.2 SGS 28 SGS 33

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

LDDC1 -- CI DIVERTER DAMPER LIMIT SWITCH 1 LOGIC


SGS 28

LDDC2 -- CI DIVERTER DAMPER LIMIT SWITCH 2 LOGIC


SGS 28
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 7

LDDC3 -- CI DIVERTER DAMPER LIMIT SWITCH 3 LOGIC


SGS 28

<<< Rung Number 29 >>>


GAS TURBINE SIGNAL 2oo3 VOTING

<<< Rung Number 30 >>>

L69 L69
PIP1 PIP2 L69PIP
───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
L69 │ │
PIP3 │ │
───┤ ├──┘ │

L69 L69 │
PIP1 PIP3 │
───┤ ├──────┤ ├──┘

L69PIP -- GTG TO HRSG SGS PERMISSIVE TO PURGE LOGIC


SGS -30 SGS 42 SGS 43 SGS 65

L69PIP1 -- CO GTG TO HRSG SGS PERMISSIVE TO PURGE HRSG 1 LOGIC


DAMPER 40 DAMPER 41 DAMPER -53 SGS 30

L69PIP2 -- CO GTG TO HRSG SGS PERMISSIVE TO PURGE HRSG 2 LOGIC


DAMPER -53 SGS 30

L69PIP3 -- CO GTG TO HRSG SGS PERMISSIVE TO PURGE HRSG 3 LOGIC


DAMPER -53 SGS 30

<<< Rung Number 31 >>>

L69XD_ L69XD_ L69XD_


PERM1 PERM2 PRM
───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
L69XD_ │ │
PERM3 │ │
───┤ ├──┘ │

L69XD_ L69XD_ │
PERM1 PERM3 │
───┤ ├──────┤ ├──┘

L69XD_PERM1 -- CO GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER 1 LOGIC


DAMPER 12 DAMPER -55 SGS 31

L69XD_PERM2 -- CO GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER 2 LOGIC


DAMPER -55 SGS 31

L69XD_PERM3 -- CO GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER 3 LOGIC


DAMPER -55 SGS 31

L69XD_PRM -- GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER LOGIC


SGS -31 SGS 43 SGS 66

<<< Rung Number 32 >>>


EMERGENCY PUSH BUTTON 2oo3 VOTING

<<< Rung Number 33 >>>

L4XD_ L4XD_ L4XD_


EMC1 EMC2 EMC
───┤ ├──┬───┤ ├──┬────────────────────────────────────────────────( )
│ │
L4XD_ │ │
EMC3 │ │
───┤ ├──┘ │

L4XD_ L4XD_ │
EMC1 EMC3 │
───┤ ├──────┤ ├──┤

L4XD_ L3COM_ │
EMC1 B │
───┤ ├──────┤/├──┘
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 8

L3COM_B -- LOGIC
SEQ_TRB1 -15.3 SEQ_TRB1 15.4 SEQ_TRB1 58.2 SEQ_TRB1 58.4 SEQ_TRB1 58.6
SEQ_TRB1 58.9 DAMPER 6 DAMPER 9 DAMPER 58 SEQ_LOAD 108
SEQ_AUX 3.2 SEQ_AUX 4.2 SGS 28 SGS 33

L4XD_EMC -- EMERGENCY STOP PUSH BUTTON LOGIC


SGS -33 SGS 35 SGS 58

L4XD_EMC1 -- EMERGENCY STOP PUSH BUTTON #1 LOGIC


SGS 33

L4XD_EMC2 -- EMERGENCY STOP PUSH BUTTON #2 LOGIC


SGS 33

L4XD_EMC3 -- EMERGENCY STOP PUSH BUTTON #3 LOGIC


SGS 33

<<< Rung Number 34 >>>


BOILER CONDITIONS SATISFIED

<<< Rung Number 35 >>>

LIPL LHPL L4XD_ L69


VNLL VNLL EMC HRSG
───┤ ├──────┤ ├──────┤ ├──────────────────────────────────────────( )

L4XD_EMC -- EMERGENCY STOP PUSH BUTTON LOGIC


SGS -33 SGS 35 SGS 58

L69HRSG -- BOILER CONFITION SATISFIED LOGIC


SGS -35 SGS 37 SGS 38 SGS 42 SGS 59

LHPLVNLL -- CO HP DRUM LEVEL LOW-LOW SIGNAL TO DCIS LOGIC


SGS 35 SGS -53

LIPLVNLL -- CO IP DRUM LEVEL LOW-LOW SIGNAL TO DCIS LOGIC


SGS 35 SGS -57

<<< Rung Number 36 >>>


GAS TURBINE CONDITIONS

<<< Rung Number 37 >>>

L69 L69H
HRSG RSGX
───┤ ├───────────┬────────────────────────────────────────────────( )

L69H L69HR │
RSGX SG_DO │
───┤ ├──────┤/├──┘

L69HRSG -- BOILER CONFITION SATISFIED LOGIC


SGS -35 SGS 37 SGS 38 SGS 42 SGS 59

L69HRSGX -- BOILER CONFITION SATISFIED AFTER DROP OUT TIME DELAY LOGIC
SGS -37 SGS 39 SGS 40

L69HRSG_DO -- LOGIC
SGS 37 SGS -38

<<< Rung Number 38 >>>


╔══════════════════════╗
L69 ║ TMV - Time Delay ║ L69HRSG_DO
HRSG Input L0║Input(enab)┌─────┐stat║
───┤/├──────────────────────────────────────────────────╫───────────┤ ├────╫──────────( )
║ │ TD │ ║
K69HRSGX 0║Final │ │Curr║1 T69HRSGX
──────────────────╫───────────┤ ├────╫──────────────────
║ │ │ ║
║ dt │ │ ║
║ ────────┤ │ ║
║ └─────┘ ║
╚══════════════════════╝

K69HRSGX -- sec <+65 SEC>


SGS 38

L69HRSG -- BOILER CONFITION SATISFIED LOGIC


SGS -35 SGS 37 SGS 38 SGS 42 SGS 59
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 9

L69HRSG_DO -- LOGIC
SGS 37 SGS -38

T69HRSGX -- sec
SGS -38

<<< Rung Number 39 >>>

L69H
RSGX L4SGS
───┤ ├──┬─────────────────────────────────────────────────────────( )


LDDC │
───┤ ├──┘

L4SGS -- HRSG SGS TRIP AUX LOGIC TO DCIS LOGIC


SGS -39 SGS 63

L69HRSGX -- BOILER CONFITION SATISFIED AFTER DROP OUT TIME DELAY LOGIC
SGS -37 SGS 39 SGS 40

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

<<< Rung Number 40 >>>

L69H L4SGS_
RSGX GTG
───┤/├──┬─────────────────────────────────────────────────────────( )


LDDC │
───┤/├──┘

L4SGS_GTG -- HRSG SGS TRIP AUX LOGIC TO GTG LOGIC


SGS -40 SGS 46

L69HRSGX -- BOILER CONFITION SATISFIED AFTER DROP OUT TIME DELAY LOGIC
SGS -37 SGS 39 SGS 40

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

<<< Rung Number 41 >>>


DIVERTER DAMPER CONDITIONS

<<< Rung Number 42 >>>

L69
HRSG L4DDC
───┤ ├──┬─────────────────────────────────────────────────────────( )


L69PIP │
───┤ ├──┘

L4DDC -- DIVERTER DAMPER NO EMGCY CLOSED LOGIC


SGS -42 SGS 48 SGS 62

L69HRSG -- BOILER CONFITION SATISFIED LOGIC


SGS -35 SGS 37 SGS 38 SGS 42 SGS 59

L69PIP -- GTG TO HRSG SGS PERMISSIVE TO PURGE LOGIC


SGS -30 SGS 42 SGS 43 SGS 65

<<< Rung Number 43 >>>

L69XD_ LDDC_
PRM L69PIP OPN
───┤ ├──────┤/├──┬────────────────────────────────────────────────( )


L69PIP │
───┤ ├───────────┘
L69PIP -- GTG TO HRSG SGS PERMISSIVE TO PURGE LOGIC
SGS -30 SGS 42 SGS 43 SGS 65
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 10

L69XD_PRM -- GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER LOGIC


SGS -31 SGS 43 SGS 66

LDDC_OPN -- DIVERTER DAMPER RELEASE TO OPEN LOGIC


SGS -43 SGS 61

<<< Rung Number 44 >>>


OUTPUT TO GAS TURBINE

<<< Rung Number 45 >>>

L69
LDDC RTF1
───┤/├────────────────────────────────────────────────────────┬───( )

│ L69
│ RTF2
├───( )

│ L69
│ RTF3
└───( )

L69RTF1 -- CIM_I SIGNAL DO DCS-READY TO FIRE-PURGE COMPLETE LOGIC


DAMPER 6 DAMPER 7 SGS -45

L69RTF2 -- CIM_I SIGNAL DO DCS-READY TO FIRE-PURGE COMPLETE LOGIC


DAMPER 6 SGS -45

L69RTF3 -- CIM_I SIGNAL DO DCS-READY TO FIRE-PURGE COMPLETE LOGIC


DAMPER 6 DAMPER 7 SGS -45

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

<<< Rung Number 46 >>>

L4SGS_ L4T_
GTG SGS1
───┤ ├────────────────────────────────────────────────────────┬───( )

│ L4T_
│ SGS2
└───( )

L4SGS_GTG -- HRSG SGS TRIP AUX LOGIC TO GTG LOGIC


SGS -40 SGS 46

L4T_SGS1 -- CIM_I HRSG SGS CHANNEL A TRIP AUX LOGIC LOGIC


DAMPER 40 SGS -46

L4T_SGS2 -- CIM_I HRSG SGS CHANNEL B TRIP AUX LOGIC LOGIC


DAMPER 41 SGS -46

<<< Rung Number 47 >>>


OUTPUT TO DIVERTER DAMPER

<<< Rung Number 48 >>>

L4DDC L4DDCY
───┤ ├────────────────────────────────────────────────────────────( )

L4DDC -- DIVERTER DAMPER NO EMGCY CLOSED LOGIC


SGS -42 SGS 48 SGS 62

L4DDCY -- CO OUTPUT TO DIVERTER DAMPER - DIVERTER DAMPER NO EMGCY CLOSED LOGIC


SGS -48

<<< Rung Number 49 >>>


OUTPUT TO DCIS
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 11

<<< Rung Number 50 >>>

LHPL LHPL
V1LL V1NLL
───┤/├────────────────────────────────────────────────────────────( )

LHPLV1LL -- HP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -18 SGS 21 SGS 50

LHPLV1NLL -- CO HP DRUM LEVEL 1 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -50

<<< Rung Number 51 >>>

LHPL LHPL
V2LL V2NLL
───┤/├────────────────────────────────────────────────────────────( )

LHPLV2LL -- HP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -19 SGS 21 SGS 51

LHPLV2NLL -- CO HP DRUM LEVEL 2 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -51

<<< Rung Number 52 >>>

LHPL LHPL
V3LL V3NLL
───┤/├────────────────────────────────────────────────────────────( )

LHPLV3LL -- HP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -20 SGS 21 SGS 52

LHPLV3NLL -- CO HP DRUM LEVEL 3 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -52

<<< Rung Number 53 >>>

LHP LHPL
LVLL VNLL
───┤/├────────────────────────────────────────────────────────────( )

LHPLVLL -- HP DRUM LEVEL 2oo3 LOW-LOW LOGIC


SGS -21 SGS 53

LHPLVNLL -- CO HP DRUM LEVEL LOW-LOW SIGNAL TO DCIS LOGIC


SGS 35 SGS -53

<<< Rung Number 54 >>>

LIPL LIPL
V1LL V1NLL
───┤/├────────────────────────────────────────────────────────────( )

LIPLV1LL -- IP DRUM LEVEL 1 LOW-LOW LOGIC


SGS -23 SGS 26 SGS 54

LIPLV1NLL -- CO IP DRUM LEVEL 1 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -54

<<< Rung Number 55 >>>

LIPL LIPL
V2LL V2NLL
───┤/├────────────────────────────────────────────────────────────( )

LIPLV2LL -- IP DRUM LEVEL 2 LOW-LOW LOGIC


SGS -24 SGS 26 SGS 55

LIPLV2NLL -- CO IP DRUM LEVEL 2 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -55

<<< Rung Number 56 >>>


LIPL LIPL
V3LL V3NLL
───┤/├────────────────────────────────────────────────────────────( )
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 12

LIPLV3LL -- IP DRUM LEVEL 3 LOW-LOW LOGIC


SGS -25 SGS 26 SGS 56

LIPLV3NLL -- CO IP DRUM LEVEL 3 LOW-LOW SIGNAL TO DCIS LOGIC


SGS -56

<<< Rung Number 57 >>>

LIP LIPL
LVLL VNLL
───┤/├────────────────────────────────────────────────────────────( )

LIPLVLL -- IP DRUM LEVEL 2oo3 LOW-LOW LOGIC


SGS -26 SGS 57

LIPLVNLL -- CO IP DRUM LEVEL LOW-LOW SIGNAL TO DCIS LOGIC


SGS 35 SGS -57

<<< Rung Number 58 >>>

L4XD_ L4XD_
EMC EMCX
───┤ ├────────────────────────────────────────────────────────────( )

L4XD_EMC -- EMERGENCY STOP PUSH BUTTON LOGIC


SGS -33 SGS 35 SGS 58

L4XD_EMCX -- CO SIGNAL TO DCIS LOGIC


SGS -58

<<< Rung Number 59 >>>

L69 L69H
HRSG RSGZ
───┤ ├────────────────────────────────────────────────────────────( )

L69HRSG -- BOILER CONFITION SATISFIED LOGIC


SGS -35 SGS 37 SGS 38 SGS 42 SGS 59

L69HRSGZ -- CO SIGNAL TO DCIS LOGIC


SGS -59

<<< Rung Number 60 >>>

LDDC LDDCX
───┤ ├────────────────────────────────────────────────────────────( )

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

LDDCX -- CO SIGNAL TO DCIS LOGIC


SGS -60

<<< Rung Number 61 >>>

LDDC_ LDDC_
OPN OPNX
───┤ ├────────────────────────────────────────────────────────────( )

LDDC_OPN -- DIVERTER DAMPER RELEASE TO OPEN LOGIC


SGS -43 SGS 61

LDDC_OPNX -- CO SIGNAL TO DCIS LOGIC


SGS -61

<<< Rung Number 62 >>>

L4DDC L4DDCX
───┤ ├────────────────────────────────────────────────────────────( )
L4DDC -- DIVERTER DAMPER NO EMGCY CLOSED LOGIC
SGS -42 SGS 48 SGS 62

L4DDCX -- CO SIGNAL TO DCIS LOGIC


SGS -62
Control Sequence Document for Segment F:\UNIT2\SGS.SRC Mon Oct 22 10:40:29 2018 Page - 13

<<< Rung Number 63 >>>

L4SGS L4SGSX
───┤ ├────────────────────────────────────────────────────────────( )

L4SGS -- HRSG SGS TRIP AUX LOGIC TO DCIS LOGIC


SGS -39 SGS 63

L4SGSX -- CO SIGNAL TO DCIS LOGIC


SGS -63

<<< Rung Number 64 >>>

L69
LDDC RTFX
───┤ ├────────────────────────────────────────────────────────────( )

L69RTFX -- CO SIGNAL TO DCIS LOGIC


SGS -64

LDDC -- DIVERTER DAMPER POSITION LOGIC


SGS -28 SGS 39 SGS 40 SGS 45 SGS 60
SGS 64

<<< Rung Number 65 >>>

L69
L69PIP PIPX
───┤ ├────────────────────────────────────────────────────────────( )

L69PIP -- GTG TO HRSG SGS PERMISSIVE TO PURGE LOGIC


SGS -30 SGS 42 SGS 43 SGS 65

L69PIPX -- CO SIGNAL TO DCIS LOGIC


SGS -65

<<< Rung Number 66 >>>

L69XD_ L69XD_
PRM PERMX
───┤ ├────────────────────────────────────────────────────────────( )

L69XD_PERMX -- CO SIGNAL TO DCIS LOGIC


SGS -66

L69XD_PRM -- GTG TO HRSG SGS PERMISSIVE TO OPEN DAMPER LOGIC


SGS -31 SGS 43 SGS 66

<<< Rung Number 67 >>>

LSGS_
LTRUE FLT
───┤/├────────────────────────────────────────────────────────────( )

LSGS_FLT -- CO SIGNAL SGS FAULT TO DCIS LOGIC


SGS -67

<<< Rung Number 68 >>>


----------------------------------------------------------------
---- End of Segment
----------------------------------------------------------------
----
----
----------------------------------------------------------------

You might also like