Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Unit # 8 Boiler safety valve setting

Dated : 09-10/09/2014
Oil Consumed : 09.09.14- 42 KL
10.09.14- 60 KL
S.N. Location Safety valve Type Popping Reset Pressure % of Blow Remarks
of S/V Tag No. Pressure Down
Design Actual Design Actual Design Actual

1. SV-1 1750 WB 182.5 182 175.2 174 4 4.3


LHS (Front)
2. Boiler SV-2 1740 WB 186.2 185.7 176.9 165 5 11
Drum (Right)
3. SV-3 1740 WB 188 - 178.6 - 5 -
LHS(Rear)
4. SV-4 1739 WD 166.6 167 159.9 157.8 4 4.07 MS temp.
(M.S. RHS) 380
S.H.
5. SV-5 1739 WD 166.6 164.45 159.9 151.3 4 6 MS temp.
(M.S.- LHS) 403
6. SV-6 ERV 1538 164.6 - 158.1 - 4 -
S.H. VX – 10W
7. ERV SV-7 ERV 1538 164.6 - 158.1 - 4 -
VX – 10W
8. SV-8 1786 WB 47 46.82 44.7 44.05 5 5.9
CRH (CRH-LHS)

9. SV-9 1786 WD 43.8 42.0 41.6 38.0 5 9.5


(HRH-LHS)
10 SV-10 1786 WD 43.8 42.5 41.6 40.0 5 5.8
(HRH-RHS)
11. HRH SV-11 1786 WD 45.9 46.5 43.6 45.0 5 3.2
(HRH-LHS)
12. SV-12 1786 WD 45.9 44.5 43.6 41.0 5 7.8
(HRH-RHS)

13 Soot S.V-13 40 - 38.4 - 4 -


Blower