Professional Documents
Culture Documents
Power Equations and Non-Detection Zone of Passive Islanding Detection and Protection Method For Grid Connected Photovoltaic Generation System
Power Equations and Non-Detection Zone of Passive Islanding Detection and Protection Method For Grid Connected Photovoltaic Generation System
Abstract—Islanding detection and protection is an important condition by monitor parameters in Point of Common
concern for grid connected photovoltaic (PV) power generation Coupling (PCC) such as voltage amplitude and frequency
system due to personnel and equipment safety. Over/Under and then cause the inverter to shut down when there is
Voltage Protection (OVP/UVP) and Over/Under Frequency sufficient transition from normal specified conditions. Once
Protection (OFP/UFP) are basical inverter resident passive the voltage level or frequency at the PCC exceeds the preset
islanding detection method (IDM) for detecting an islanding normal range, the situation is regarded as utility malfunction.
condition by monitor parameters in Point of Common The inverter is forced to be shut down to prevent lasting
Coupling (PCC) such as voltage amplitude and frequency and islanding operation.
then cause the inverter to shut down when there is sufficient
transition from normal specified conditions. The real and II. GRID CONNECTED PV SYSTEM CONFIGURATION
reactive power equations and Non-Detection Zone (NDZ) of
OVP/UVP and OFP/UFP methods for grid connected PV Grid connected PV inverters are required to have passive
system are derived and analyzed in this paper. Analyses show islanding detection and protection methods that cause the PV
that the behavior of the system at the time of disconnection will inverter to stop supplying power to the utility grid if the
depend on the imbalance power at the instant before the switch voltage amplitude or the frequency of the point of common
opens to form the island, these results also indicate the NDZ of coupling (PCC) between the local customer load and the
OVP/UVP and OFP/UFP methods is considerable large and utility grid strays outside of prescribed limits.
the reaction times for these protective methodologies may be
variable or unpredictable.
I. INTRODUCTION
Grid connected photovoltaic (PV) power generation
system becoms the popular type of distributed generation
(DG) due to the advantage of immediate and efficient
utilization. Clarifying the technical requirements for grid
connected and solving the problems such as anti-islanding
protection are very important issues for widespread
Figure 1. Grid connected PV power generation System
application of PV system.
Islanding is a condition in which a portion of the utility
These protection methods not only protect consumers
system, which contains both load and generation, is isolated
equipment but also serve as anti-islanding detection methods
from the remainder of the utility system and continues to
and generally implemented in the inverter program software.
operate. Generally, islanding is undesirable because it poses
It is usually assumed that the local load can be modeled as a
a safety hazard to utility service personnel and also it can
parallel RLC circuit because for most IDM some type of
lead to asynchronous reclosure which will damage the
RLC load that causes the most difficulty in detection[2]. The
equipments[1]. The isolation point is generally on the low-
grid connected PV power generation system is shown in
voltage distribution line when an islanding condition exists,
Figure 1.
but islanding may also occur on the higher voltage
PV system consisting of a PV array and a inverter, is
distribution or transmission lines when large numbers of PV
connected to the local utility system at Node “a”. Power
and other DG sources are present[2]. Over/Under Voltage
flows show in figure 1, node “a” is the PCC between the
Protection (OVP/UVP) and Over/Under Frequency
utility grid and PV inverter. The utility grid voltage source at
Protection (OFP/UFP) are basical inverter resident passive
the right can be disconnected from node “a” by the switch S2
islanding detection method (IDM) for detecting an islanding
(breaker/recloser). A local load is also connected at the PCC.
361
Approximatively, ∆L·∆C=0, ∆L/L=0,
∵ ΔL ⋅ ΔC = 0
⎛ f ⎞
2
LC ⎛ f ⎞
2
∵ Δ L ⋅ Δ C = 0, Δ L / L = 0
∴ ⎜⎜ min ⎟⎟ ≤ ≤ ⎜⎜ max ⎟⎟
f LC + L Δ C + Δ LC ΔQ ⎛ ΔC ΔL ⎞
⎝ ⎠ ⎝ f ⎠ ∴ = −Q f ⎜ + ⎟ (8 )
2 2 P ⎝ C L ⎠
⎛ f ⎞ LC + L Δ C + Δ LC ⎛ f ⎞
⎜⎜ ⎟⎟ ≤ ≤ ⎜⎜ ⎟⎟
⎝ f max ⎠ LC ⎝ f min ⎠
2 2 Therefore, form formula (5) and formula (8), the NDZ of
⎛ f ⎞ ΔC ΔL ⎛ f ⎞ reactive power is
⎜⎜ ⎟⎟ ≤ 1 + + ≤ ⎜⎜ ⎟⎟
⎝ f max ⎠ C L ⎝ f min ⎠
2 2 ⎛ ⎛ f ⎞
2
⎞ ΔQ ⎛ ⎛ f ⎞
2
⎞
⎛ f ⎞ ΔC ΔL ⎛ f ⎞ Q f ⎜1 − ⎜⎜ ⎟⎟ ⎟≤ ≤ Q f ⎜1 − ⎜⎜ ⎟⎟ ⎟ (9 )
⎜⎜ ⎟⎟ − 1 ≤ + ≤ ⎜⎜ ⎟⎟ − 1 (5) ⎜ ⎟ ⎜ ⎟
⎝ f max ⎠ C L ⎝ f min ⎠ ⎝ ⎝ f max ⎠ ⎠
P
⎝ ⎝ f min ⎠ ⎠
From the reactive power mismatch ∆Q, the relationship
Analogously the NDZ of active power is
between ∆L, ∆C and ∆Q is shown in formula (6).
2 2
⎛ V ⎞ ΔP ⎛ V ⎞
⎛ 1 ⎞ ⎜⎜ ⎟⎟ − 1 ≤ ≤ ⎜⎜ ⎟⎟ − 1 (10 )
Δ Q = V 2 ⎜⎜ − 2 π (C + Δ C )⎟⎟
⎝ 2 π f (L + Δ L ) ⎠ ⎝ V max ⎠ P ⎝ V min ⎠
⎛ ⎞ So the NDZ of OVP/UVP and OFP/UFP methods are
⎜ ⎟
1 ⎛ Δ C ⎞⎟ shown in figure 3.
= V 2⎜ − 2π C ⎜ 1 + ⎟
⎜ ⎛ ΔL ⎞ ⎝ C ⎠⎟
⎜ 2 π fL ⎜ 1 + ⎟ ⎟
⎝ ⎝ L ⎠ ⎠
QL ⎛ Δ C ⎞
= − Q C ⎜1 + ⎟ (6)
ΔL ⎝ C ⎠
1+
L
Q L QC
Qf = = (7 )
P P
362
IV. CONCLUSIONS [12] G. Kern, “SunSine300: Utility interactive AC module anti-islanding
test results,” in Proc. IEEE Photovoltaic Specialists Conf., Anaheim,
Anti-islanding detection and protection for grid CA, 1997, pp. 1265–1268.
connected PV systems is very important for safety and must [13] M. Ropp, M. Begovic, A. Rohatgi, G. A. Kern, R. H. Bonn, and S.
exhibit sufficient dependability and security. There are many Gonzalez, “Determining the relative effectiveness of islanding
methods to detect island operation. Over/Under Voltage detection methods using phase criteria and nondetection zones,” IEEE
Trans. Energy Conversion, vol. 15, no. 3, pp. 290–296, Sep. 2000.
Protection (OVP/UVP) and Over/Under Frequency
Protection (OFP/UFP) are basical inverter resident passive [14] Kitamura, A., Okamoto, M., Yamamoto, F., Nakaji, K., Matsuda, J.,
Hotta, K., “Islanding Phenomenon Elimination Study at Rokko Test
islanding detection method (IDM) for detecting an islanding Center,” Proceedings of the 1st IEEE World Conference on
condition by monitor parameters in Point of Common Photovoltaic Energy Conversion, Part 1, pp.759-762, 1994.
Coupling (PCC) such as voltage amplitude and frequency. [15] SAHA, S., SUNDAKSINGH. V.P, “Novel grid-coiinectcd
The real and reactive power equations and Non-Detection photovoltaic inverter,” IEE Proc., Gener. Transm. Distrib, 143(2),
Zone (NDZ) of OVP/UVP and OFP/UFP methods for grid pp. 219-224, 1996.
connected PV system are derived and analyzed in this paper.
Analyses show that the behavior of the system at the time of BIOGRAPHIES
disconnection will depend on the imbalance power at the Zengqiang Mi received the B.S. degree and the M.S. degree in Electronic
instant before the switch opens to form the island, these Engineering from North China Electric Power University, China, in 1983
results also indicate the NDZ of OVP/UVP and OFP/UFP and 1989 respectively. He is a professor in North China Electric Power
University, Baoding, Hebei Province, China. His special fields of interest
methods is considerable large and the reaction times for included power system automation and protection.
these protective methodologies may be variable or Fei Wang received the B.S. degree from Hebei University, China, in 1993
unpredictable. and the M.S. degree from North China Electric Power University, China, in
These inverter resident passive methods are cost- 2005. Now he is studying for the Ph.D. degree in the Key Laboratory of
effective but their non-detection zone includes balanced Power System Protection and Dynamic Security Monitoring and Control
islands, which limits dependability. Inverter resident active under Ministry of Education, North China Electric Power University,
Baoding, Hebei Province, China. His present research interests are in
methods are effective and can detect balanced islands, but it power system automation, reactive power theory and DG.
will make the power quality worse. External methods are not
commonly used, but may be a solution of the future.
REFERENCES
[1] M. Ropp, M. Begovic, “Prevention of Islanding in Grid connected
Photovoltaic Systems,” Progress in Photovoltaics vol. 7, pp.39-59,
1999.
[2] W. Bower and M. Ropp, “Evaluation Of Islanding Detection Methods
For Photovoltaic Utility-Interactive Power Systems,” Rep. IEA-PVPS
T5-09:2002, Mar. 2002.
[3] IEEE Standard 929–2000, “IEEE Recommended Practice For Utility
Interface Of Photovoltaic (PV) Systems,” Apr., 2000.
[4] IEEE Standard 547-2003, “IEEE Standard for Interconnecting
Distributed Resources with Electric Power Systems,” 2003
[5] IEC 62116, “Test procedure of islanding prevention measures for
utility-interconnected photovoltaic inverters,” August 2006, Draft.
[6] H. Sun. “Performance Assessment of Islanding Detection Methods
Using the Concept of Non-Detection Zones,” M.A.Sc. thesis, Dept.
Elect. Comput. Eng., Concordia Univ., Montreal, QC, Canada, Jan.
2005.
[7] Z. Ye, A. Kowalkar, Y. Zhang, P. Du, and R.Walling, “Evaluation of
anti-islanding schemes based on non detection zone concept,” IEEE
Trans. Power Electron., vol. 19, no. 5, pp. 1171–1176, Sep. 2004.
[8] Jang, S., Kim, K, “An islanding detection method for distributed
generations using voltage unbalance and total harmonic distortion of
current,” IEEE Trans. Power Deliv., 2004, 19, pp. 745–752.
[9] Hung, G., Chang, C., and Chen, C. “Automatic phase shift method for
islanding detection of grid connected photovoltaic inverters,” IEEE
Trans. Energy Convers., 2003, 18,(1).
[10] A.Woyte, R. Belmans, and J. Nijs, “Testing the islanding protection
function of photovoltaic inverters,” IEEE Trans. Energy Conversion,
vol. 18, no. 1, pp. 157–162, Mar. 2003.
[11] M. Ropp, “Design Issues for Grid connected Photovoltaic Systems,”
Ph.D. dissertation, Georgia Institute of Technology, Atlanta, GA,
1998.
363