SELUBUNG TENDON
1 𝑊
MT = (RA x (x1)) - 𝑥 𝑥(𝑥1)2
2 12
1 2698,54
= {103893,79 lb x (3,85 ft x 12)} - 𝑥 𝑥 46,22
2 12
= 4559898,44 in.-lb
𝑟2 251,06 𝑖𝑛𝑐ℎ2
Kb = = = 9,42 inch
𝐶𝑡 26,64 𝑖𝑛𝑐ℎ2
E1 = a max - Kt
= 5,63 – 11,75
= -6,12 inch ≤ Ct = 11,75 inch
Karena 18 tendon dengan kehilangan LOP 21,09% tidak memenuhi syarat Tidak Memenuhi
Syarat, maka dicoba lagi menggunakan 27 tendon dengan asumsi kehilangan LOP 28,28%.
Data Input untuk 27 tendon :
Fpi = 189.000 psi = 189.000 lb/inch2
Aps = 4,13 inch2
Pi = Fpi x Aps = 189.000 x 4,13 = 780.759 lb
Pe = (100%-23%) x Pi
= (100%-23%) x 780.759
= 506.116,63 lb
Fpe = Pe : Aps = 135.588,63 lb / 4,13 inch2 = 135.588,63 psi
L = 62 ft
Ac = 486,50 inch2
Fc’ = 5000 psi
R2 = 172,14 inch2
Ct = 21 inch
Cb = 17 inch
WD = 506,77 plf
WSD = 660 plf 2555,45 plf
2366,77
WL = 1200 plf
MD = 292.220.3,82 in.-lb
MSD = 247.776.0,00 in.-lb 14.511.695,82 in.-lb
ML = 9.110.280,00 in.-lb
E1 = a max - Kt
= 20,64 - 10,12
= 10,52 inch ≤ Cb = 17 inch Memenuhi Syarat