DIESEL GENERATOR SET

TECHNICAL PARAMETERS
FU 300

GENERAL DATA

Standby Power L.T.P. (cos = 0,8) kVA / kW 330 / 264

PRIME POWER (P.R.P.) Prime Power P.R.P. (cos = 0,8) kVA / kW 300 / 240
(ISO 8528): Nominal current Amps 432

Prime Power is available for an Nominal voltage V 230 / 400


unlimited number of annual hours in Frequency Hz 50
variable load application in accordance
ENGINE MTU 6R1600G20F
with ISO 8528, A 10% overload
capacity is available for a period of 1 Emission standard STAGE 3A
hour within a 12-hour period of
Engine speed rpm 1500
operation.
Class 8528 / engine governor G3 ELECTRONIC

Engine speed regulation % ± 0,25


STAND-BY POWER (L.T.P.)
(ISO 8528): Cylinder configuration 6R

Fuel - Diesel EN 590


Standby Power rating is applicable for
supplying emergency power for the Cooling type LIQUIDE / AIR ANTIFREEZE + AIR
duration of a utility power interruption. Displacement l 10,50
No overload, limited to 500 operation
hours per year Engine power PRP ISO 3046 kW 274

Battery charging alternator voltage V 24

SINCRO MECC ALTE


ALTERNATOR
SK250 LL ECO38-2LN/4

Brushless, self exciting, Brushless, self exciting,


Type
synchronic synchronic

Pole / Connecting type 4 / star Y 4 / star Y

Insulation class H H

Protection grade IP 21 IP 21
NOTE:
ELECTRONIC ELECTRONIC
Voltage regulation type
AVR BL3 AVR UVR6
All parameters are given for reference
conditions: ambient air temperature up Voltage regulation ±1% ±1%
to 40 OC and site altitude above sea 300% In 300% In
Short circuit current capacity
level 1000m.
Waveform distortions THD < 2% < 3%

Reactances Xd” 6,1% 8,1%


STANDARD WARRANTY

Prime Power – 12 mounts

GENERATING SET DESCRIPTION

F U 300 N A S C G P L
F

L - Light tower
P - Generating set mounted on a trailer
G - Engine preheating for cold start
C - Silent canopy, CC – Super silent canopy, no letter open version mounted on a base frame
S - With Automatic Transfer Switches (ATS)
A - Automatic start, R - Manual start
N – Synchronization with main, P – Synchronization with other genset
Prime power kVA
Engine: V -Volvo, I - Iveco, M - Mitsubishi, B - JCB, U - MTU, P-Perkins, D-Doosan
FOGO Generating set

www.fogo.pl Ver. 11 02 EN
FU 300

INSTALATION GUIDELINE
Power output connection connectors mm2 5 x M12
Power output cables elastic cable mm2 5x240 ( 30m)
ATS control connection elastic cable mm2 7x1,5 ( 30m)
Preheating, battery charger ect. elastic cable mm2 3x2,5 ( 30m)
Above 30 m connection cables– please contact technical department
*** NOTE: For reference only***

ATS box overall size (connection from the bottom) mm 1200/700/500 (wall mounted) STANDARD EQUIPMENT:
Engine exhaust outlet diameter mm -* - diesel engine
- alternator
Exhaust pipe diameter (max. 7m, 4 elbows) mm -*
- starting batteries
Exhaust pipe diameter (max. 15m, 4 elbows) mm -* - on engine wiring
- fuel tank with on engine fuel installation
- elastic engine and alternator mountings
- exhaust compensators
- silencer
OPEN VERSION - on engine liquids (engine oil and cooling
Dimensions(LxWxH) mm 3480x1600x2080 liquid, without fuel)
Weight (without fuel) kg 3481
- generating set terminal box
- main circuit bracer
Fuel tank capacity liters 700 - generating set control panel with engine and
Autonomy (100% load, alternator parameters indication
hours 11,0
full tank) - emergency stop
Radiator high mm -* - acoustic warning signal

Radiator width mm -*
Radiator distance from
mm -*
the floor
Version:
Air outlet surface m2 -*
Air inlet surface m2 -*
R - open version, manual start
- standard equipment
Noise level (LWA) dB 122** AG - open version, automatic start
- standard equipment
+ battery charger
+ with external start command
ASG - open version, automatic start, AMF+ATS
- standard equipment
+ battery charger
CONTENERIZED VERSION + AMF+ATS Automatic Transfer Switches with
Automatic Mains Failure
Dimensions (LxWxH) mm 4100x1600x2615
RC - soundproof, manual start
Weight (without fuel) kg 4281 - standard equipment
Fuel tank capacity liters 700 + soundproof canopy
Autonomy (100% load, full ACG - soundproof, automatic start
hours 11,0 - standard equipment
tank)
Noise level (LWA) dB 98***
+ soundproof canopy
+ battery charger
+ with external start command
ASCG - soundproof, automatic start
AMF+ATS
Pictures for reference only
- standard equipment
+ soundproof canopy
+ battery charger
OPERATION DATA + AMF+ATS Automatic Transfer Switches with
Engine oil type 15W40 Rimula R3X Automatic Mains Failure
Total oil capacity l -*
Oil consumption (per 1 kW) l/h -*
Oil change intervals hours/year 100 (first time) 500 / 1
ACCESSORY:
Coolant type (glycol) - 380C Antifreeze Glicoshell
- external fuel tank
Coolant quantity l -*
- synchronization with other generator set
Coolant change intervals hours/years 1000 / 2 - ventilation
Starting battery capacity Ah 2 x 180 - exhaust piping system
Fuel type Diesel EN 590 - differential protection
- other voltage application
Fuel consumption 100% load l/h 63,7 - individual ATS
Fuel consumption 75% load l/h 47,8 - spark arrestor
31,9 - remote control
Fuel consumption 50% load l/h
- maintenance contract
Fuel filters change interval hours 500 - others*
Oil filters change interval hours 500
Foundation concrete slab (for reference only) L/W mm 4300x1800

* - please contact technical department


** - for installation, noise protection required
*** - according to 2005/88/EC

Ver. 11 02 EN Specification may change without notice