DESIGN STEP
‘Goomeiry
‘Actions
Preliminary
design
Initial member
selection
Frame stabilly
‘Member
verification
ble 3.2
tuence StS
‘SECTION
ei
e2
7
a
‘COMMENTS
Establish the clear epan and height based on the client
requirements. The geomstry used in the analysis should
‘be alite corservaive to allow for subsequent changes in
member se,
Establish actions depanding on location, site alitude and
local topography. Permanent actions ray be estimated,
based on selected cladding type.
Use tables from Appendix A or the preliminary desian,
‘method described in Section 6.
‘Select member sizes based on thelr cross-section
resistance ard buckling resistance. it may be acsumed that
the influence of shear on the bending resistance can be
‘neglacted for intial desian. Allow about 5% for axial load.
Rafter
Aithis stage it may be assumed that suficient restraints
San De noduced to ime member ucking
Shuma
“Tho latoral- torsional buckling resistance of tho column is
likely to be the ertical chack, so preliminary checks over
the restrained lengths will be necessary, intermediate
restrainis cannot be introduced to the column (eg. because
the side rails are not continuous), a larger column section
‘wil be required.
‘Saraiity to second ordar effects rust be assessed,
itis they hat second order effcts must be allowed for,
ether by empitying the results ota trstorder analysis,
or by completing a second orver analysis. When assessing
‘tame dla, iio recommendes that baces are modelled
inaccordancs with the guidance given in Section 7-4
Gaassificaion of member cross-sections.
Verification af cross-section resistance to bending,
shest and compression, Bending interaction with shear
is generally rot critcal
Buckling resistance is checked, establishing the position of
the restraints to both flanges and thus the bucking lengths.
(Out-ofplane buckling resistance is veriied against flexural
and lateral torsional buckling, Interaction of bending
‘moment and axial force is checked with the use of,
Exprostion 6 62 of BS EN 1003.1-1 and intoracton factors
from Annex B,
In-plane buckling resistance verification of members in
portal frames is not necessary, See Secticn &,
Frame deflections are chacked against cliant requirements.