Part 10. All-Air Systems - Chapter 4. Dual-Duct System: Table 1 Summarizes The Cooling Load Requirements of 2)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Part 10. All-Air Systems | Chapter 4.

Dual-Duct System

ERSH = effective room sensible heat (Btu/hr). Subscripts: z = zone peak; bk = block peak.
BF = dehumidifiet bypass factor; trm = room temperature (F); tadp = apparatus dewpoint temperature (F)
hea = specific enthalpy of entering mixture of outdoor air at design conditions and and return air at average syste
mcondition (Btu/lb).
Hadp = specific enthalpy at apparatus dewpoint temperature (Btu/lb).

the Btu calculations should be adjusted by increasing the room conditions and offsetting the zone heating load (Part
outdoor air bypass factor by 0.1. 2).
Table 1 summarizes the cooling load requirements of If a preheater is required, it may be selected to
various conventional systems applied to single and temper the minimum outdoor air to 40 F or to heat the
multiple zones. It also presents the methods applied in mixture of outdoor and return air to the required dewpoint
calculating the dehumidified and supply air quantities as temperature.
well as the refrigeration or the dehumidifier load, and
defines the fan and zone supply air quantities. SUPPLY AIR
HEATING LOAD The supply air for the various types of conventional
systems may either equal the dehumidifier air quantity
When heating is required, the load for each zone is (Table 1) or be increased to maintain the proper air
calculated to offset the transmission loss plus infiltration. circulation within the conditioned space. If it is increased,
The capacities of the heating or reheating coils should be it may be accomplished either by the addition of a
capable of both raising the supply air temperature to permanent bypass of untreated recirculated space air to
be mixed with the dehumidified air, or by the selection of

You might also like