FROM WIRE WIRE TO CABLE ROUTE

TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH


ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
POWER CABLES (230VAC)
P011 1 BK BK 1 P011 230VAC EXISTING MAIN SUPPLY- 1
FEEDER 106 1 X1C-50mm² SUB-DISTRIBUTION CABLE
1 P 01 TRENCH
TO NEW 230VAC 5
344BAN-P01 BOARD SDB-2
LEVEL-1
EXISTING MDB-1 NEW
P021 1 BK BK 1 P021 230VAC EXISTING MAIN SUPPLY- 1
FEEDER 106 1 X1C-50mm² SUB-DISTRIBUTION CABLE
2 P 02 TRENCH
TO NEW 230VAC 5
344BAN-P02 BOARD SDB-2
LEVEL-1
EXISTING MDB-1 NEW
P031 1 BK BK 1 P031 230VAC EXISTING MAIN SUPPLY- 1
FEEDER 106 1 X1C-50mm² SUB-DISTRIBUTION CABLE
3 P 03 TRENCH
TO NEW 230VAC 5
344BAN-P03 BOARD SDB-2
LEVEL-1
EXISTING MDB-1 NEW
P041 1 BK BK 1 P041 230VAC EXISTING MAIN SUPPLY -2
FEEDER 204 1 X1C-50mm² SUB-DISTRIBUTION CABLE
4 P 04 TRENCH
TO NEW 230VAC 5
344BAN-P04 BOARD SDB-2
LEVEL-1
EXISTING MDB-2 NEW
P051 1 BK BK 1 P051 230VAC EXISTING MAIN SUPPLY -2
FEEDER 204 1 X1C-50mm² SUB-DISTRIBUTION CABLE
5 P 05 TRENCH
TO NEW 230VAC 5
344BAN-P05 BOARD SDB-2
LEVEL-1
EXISTING MDB-2 NEW
P061 1 BK BK 1 P061 230VAC EXISTING MAIN SUPPLY -2
FEEDER 204 1 X1C-50mm² SUB-DISTRIBUTION CABLE
6 P 06 TRENCH
TO NEW 230VAC 5
344BAN-P06 BOARD SDB-2
LEVEL-1
EXISTING MDB-2 NEW
230VAC QA1 L1 P071 1 WH WH 1 P071
115KV EXISTINGCA
SUB-DISTRIBUTION QA1 L2 P072 2 BK 2C-4mm² BK 2 P072 NEW PCB MOTOR
7 P 07 PCB CONDUIT
NEW CT-RSC BLE TRENCH
SUPPLY
125
PANEL 344BAN-P07 LEVEL-1
NEW CB08 (6XC01BAN)
230VAC QA2 L1 P081 1 RD RD 1 P081 -X1 1 115
EXISTINGCA
SUB-DISTRIBUTION QA2 L2 P082 2 WH 3C-6mm² WH 2 P082 -X1 2 DISCONNECT NEW DS MOTOR
8 P 08 CONDUIT
BLE TRENCH
SUPPLY
125
PANEL QA2 L3 P083 3 BK 344BAN-P08 BK 3 P083 -X1 3 SWITCH LEVEL-1
NEW DS07 (6XC01BAN)
230VAC QA3 L1 P091 1 WH WH 1 P091 -X1 4 115
EXISTINGCA
SUB-DISTRIBUTION QA3 L2 P092 2 BK 2C-4mm² BK 2 P092 -X1 5 DISCONNECT NEW DS CONTROL
9 P 09 CONDUIT
BLE TRENCH
POWER SUPPLY
125
PANEL 344BAN-P09 SWITCH LEVEL-1
NEW DS07 (6XC01BAN)
230VAC QA4 L1 P101 1 WH WH 1 P101 EXISTING
SUB-DISTRIBUTION QA4 L2 P102 2 BK 2C-4mm² BK 2 P102 125 VDC PANEL CABLE HEATING &
10 P 10 TRENCH LIGHTING
15
PANEL 344BAN-P10
LEVEL-1
NEW SDB-3
QA4 L1 P111 1 WH WH 1 P111 -XA 1
115KV BUS-1 EXISTING
125 VDC PANEL QA4 L2 P112 2 BK 2C-4mm² BK 2 P112 -XA 3 CABLE HEATING &
11 P 11 PROTECTION TRENCH LIGHTING
30
344BAN-P11
LEVEL-1
SDB-3 MAIN-1
-XA 2 P121 1 WH WH 1 P121 -XA 1
115KV BUS-1 115KV BUS-1 EXISTING
-XA 4 P122 2 BK 2C-4mm² BK 2 P122 -XA 3 CABLE HEATING &
12 PROTECTION P 12 PROTECTION TRENCH LIGHTING
5
344BAN-P12
LEVEL-1
MAIN-1 MAIN-2
-XA 2 P131 1 WH WH 1 P131 -XA 1
115KV BUS-1 115KV BUS-2 EXISTING
-XA 4 P132 2 BK 2C-4mm² BK 2 P132 -XA 3 CABLE HEATING &
13 PROTECTION P 13 PROTECTION TRENCH LIGHTING
8
344BAN-P13
LEVEL-1
MAIN-2 MAIN-1
-XA 2 P141 1 WH WH 1 P141 -XA 1
115KV BUS-2 115KV BUS-2 EXISTING
-XA 4 P142 2 BK 2C-4mm² BK 2 P142 -XA 3 CABLE HEATING &
14 PROTECTION P 14 PROTECTION TRENCH LIGHTING
8
344BAN-P14
LEVEL-1
MAIN-1 MAIN-2
-XA 2 P151 1 WH WH 1 P151 -XA 1
115KV BUS-2 115KV BREAKER EXISTING
-XA 4 P152 2 BK 2C-4mm² BK 2 P152 -XA 3 CABLE HEATING &
15 PROTECTION P 15 FAIL PROTECTION TRENCH LIGHTING
10
344BAN-P15
LEVEL-1
MAIN-2 CB08 (6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 1 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
-XA 2 P161 1 WH WH 1 P161 -XA 1
115KV BREAKER CAP (6XC01BAN) EXISTING
-XA 4 P162 2 BK 2C-4mm² BK 2 P162 -XA 3 CABLE HEATING &
16 FAIL PROTECTION P 16 PROTECTION TRENCH LIGHTING
8
344BAN-P16
LEVEL-1
CB08 (6XC01BAN) MAIN-2
-XA 2 P171 1 WH WH 1 P171 -XA 1
115KV CAPACITOR CAP (6XC01BAN) EXISTING
-XA 4 P172 2 BK 2C-4mm² BK 2 P172 -XA 3 CABLE HEATING &
17 PROTECTION P 17 PROTECTION TRENCH LIGHTING
8
344BAN-P17
LEVEL-1
MAIN-2 MAIN-1
-XA 2 P181 1 WH WH 1 DFR -XA 1
115KV CAPACITOR EXISTING
-XA 4 P182 2 BK 2C-4mm² BK 2 DFR -XA 3 CABLE HEATING &
18 PROTECTION P 18 DFR SERVER AND GPS PANEL TRENCH LIGHTING
15
344BAN-P18
LEVEL-1
MAIN-1
-XA 2 P191 1 WH WH 1 P191 -XA 1
DFR SERVER AND GPS EXISTING
-XA 4 P192 2 BK 2C-4mm² BK 2 P192 -XA 3 CABLE HEATING &
19 PANEL P 19 EVENT RECORDER 1 PANEL TRENCH LIGHTING
15
344BAN-P19
LEVEL-1

-XA 2 P201 1 WH WH 1 P201 -XA 1


EVENT RECORDER 1 EXISTING
-XA 4 P202 2 BK 2C-4mm² BK 2 P202 -XA 3 CABLE HEATING &
20 PANEL P 20 FAULT RECORDER 2 PANEL TRENCH LIGHTING
15
344BAN-P20
LEVEL-1

-XA 2 P211 1 WH WH 1 P211 -XA 1


FAULT RECORDER 2 EXISTING
-XA 4 P212 2 BK 2C-4mm² BK 2 P212 -XA 3 CABLE HEATING &
21 PANEL P 21 FAULT RECORDER 1 PANEL TRENCH LIGHTING
15
344BAN-P21
LEVEL-1

230VAC QA5 L1 P221 1 RD RD 1 P221 L1 EXISTING


SUB-DISTRIBUTION QA5 L2 P222 2 WH 3C-6mm² WH 2 P222 L2 CABLE AIR CONDITIONING
22 P 22 ACCU-1 TRENCH RELAY ROOM
20
PANEL P223 3 BK 344BAN-P22 BK 3 P223 GD
LEVEL-1
NEW
230VAC QA6 L1 P231 1 RD RD 1 P231 L1 EXISTING
SUB-DISTRIBUTION QA6 L2 P232 2 WH 3C-6mm² WH 2 P232 L2 CABLE AIR CONDITIONING
23 P 23 ACCU-2 TRENCH RELAY ROOM
20
PANEL P233 3 BK 344BAN-P23 BK 3 P233 GD
LEVEL-1
NEW
230VAC QA7 L1 P241 1 RD RD 1 P241 L1 EXISTING
SUB-DISTRIBUTION QA7 L2 P242 2 WH 3C-6mm² WH 2 P242 L2 CABLE AIR CONDITIONING
24 P 24 ACCU-3 TRENCH RELAY ROOM
30
PANEL P243 3 BK 344BAN-P24 BK 3 P243 GD
LEVEL-1
NEW
230VAC QB1 L1 P251 1 WH WH 1 P251
EXISTINGCA
SUB-DISTRIBUTION QB1 L2 P252 2 BK 2C-4mm² BK 2 P252 CX(6BS01BAN) NEW
25 P 25 CONDUIT
BLE TRENCH HEATING AND LIGHTING 50
PANEL 344BAN-P25 MARSHALLING BOX LEVEL-1
NEW
L1 P261 1 WH WH 1 P261
CX(6BS01BAN) CT09(6XC01BAN) EXISTINGCA
L2 P262 2 BK 2C-4mm² BK 2 P262 NEW
26 MARSHALLING BOX P 26 CONDUIT
BLE TRENCH HEATING AND LIGHTING 90
344BAN-P26 LEVEL-1
MARSHALLING BOX
CT09(6XC01BAN) P271 1 WH WH 1 P271 -X1 500
115KV EXISTINGCA
P272 2 BK 2C-4mm² BK 2 P272 -X1 515 NEW
27 P 27 PCB CONDUIT
NEW CT-RSC BLE TRENCH HEATING AND LIGHTING 10
MARSHALLING BOX 344BAN-P27 LEVEL-1
CB08 (6XC01BAN)
-X1 501 P281 1 WH WH 1 P281 -X1 500
CT07(6XC01BAN) EXISTINGCA
CB08 (6XC01BAN) -X1 516 P282 2 BK 2C-4mm² BK 2 P282 -X1 515 NEW
28 P 28 CONDUIT
BLE TRENCH HEATING AND LIGHTING 10
344BAN-P28 LEVEL-1
MARSHALLING BOX
CT07(6XC01BAN) -X1 20 P291 1 WH WH 1 P291 -X1 20 115
EXISTINGCA
-X1 21 P292 2 BK 2C-4mm² BK 2 P292 -X1 21 DISCONNECT NEW
29 P 29 CONDUIT
BLE TRENCH HEATING AND LIGHTING 10
MARSHALLING BOX 344BAN-P29 SWITCH LEVEL-1
DS07 (6XC01BAN)
115 -X1 20 P301 1 WH WH 1 P301
EXISTINGCA
DISCONNECT -X1 21 P302 2 BK 2C-4mm² BK 2 P302 CX(6BS02BAN) NEW
30 P 30 CONDUIT
BLE TRENCH HEATING AND LIGHTING 15
SWITCH 344BAN-P30 MARSHALLING BOX LEVEL-1
DS07 (6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 2 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
230VAC QB2 L1 P311 1 RD RD 1 P311 L1 EXISTING
SUB-DISTRIBUTION QB2 L2 P312 2 WH 3C-6mm² WH 2 P312 L2 CABLE AIR CONDITIONING
31 P 31 ACCU-4 TRENCH RELAY ROOM
25
PANEL GD P313 3 BK 344BAN-P31 BK 3 P313 GD
LEVEL-1
NEW
230VAC QB3 L1 P321 1 RD RD 1 P321 L1 EXISTING
SUB-DISTRIBUTION QB3 L2 P322 2 WH 3C-6mm² WH 2 P322 L2 CABLE AIR CONDITIONING
32 P 32 ACCU-5 TRENCH RELAY ROOM
35
PANEL GD P323 3 BK 344BAN-P32 BK 3 P323 GD
LEVEL-1
NEW
230VAC QB4 L1 P331 1 RD RD 1 P331 L1 EXISTING
SUB-DISTRIBUTION QB4 L2 P332 2 WH 3C-6mm² WH 2 P332 L2 CABLE AIR CONDITIONING
33 P 33 ACCU-6 TRENCH RELAY ROOM
40
PANEL GD P333 3 BK 344BAN-P33 BK 3 P333 GD
LEVEL-1
NEW
230VAC QB5 L1 P341 1 RD RD 1 P341 L1 EXISTING
SUB-DISTRIBUTION QB5 L2 P342 2 WH 3C-6mm² WH 2 P342 L2 CABLE AIR CONDITIONING
34 P 34 ACCU-7 TRENCH RELAY ROOM
40
PANEL GD P343 3 BK 344BAN-P34 BK 3 P343 GD
LEVEL-1
NEW
230VAC QB6 L1 P351 1 RD RD 1 P351 L1 EXISTING
SUB-DISTRIBUTION QB6 L2 P352 2 WH 3C-6mm² WH 2 P352 L2 EXHAUST FAN CABLE
35 P 35 TRENCH
AC POWER SUPPLY 35
PANEL GD P353 3 BK 344BAN-P35 BK 3 P353 GD 1&2
LEVEL-1
NEW
230VAC QA10 L1 P361 1 1 P361
EXISTING WIRES EXISTING
SUB-DISTRIBUTION QA10 L2 P362 2 2 P362 CABLE
36 WILL BE P 36 SUMP PUMP TRENCH
AC POWER SUPPLY
PANEL GD P363 3 3 P363
TRANSFERRED LEVEL-1
NEW
230VAC QB10 L1 P371 1 1 P371
EXISTING WIRES EXISTING
SUB-DISTRIBUTION QB10 L2 P372 2 2 P372 ACU RELAY CABLE
37 WILL BE P 37 TRENCH
AC POWER SUPPLY
PANEL GD P373 3 3 P373 & CONTROL ROOM
TRANSFERRED LEVEL-1
NEW
POWER CABLES (125VDC)
125VDC P1 + P341 1 BK BK 1 P341
SDB-3 EXISTING
MDB-1 BK 1X1C-50mm² BK CABLE
38 P 34 MCCB1 TRENCH
PANEL DC SUPPLY 5
FEEDER - F1 344BAN-P34
LEVEL-1
EXISTING MDB-1 BUSBAR 1
125VDC N1 - P351 1 BK BK 1 P351
SDB-3 EXISTING
MDB-1 BK 1X1C-50mm² BK CABLE
39 P 35 MCCB1 TRENCH
PANEL DC SUPPLY 5
FEEDER - F1 344BAN-P35
LEVEL-1
EXISTING MDB-1 BUSBAR 1
125VDC P1 + P361 1 BK BK 1 P361
SDB-3 EXISTING
MDB-2 1X1C-50mm² CABLE
40 P 36 MCCB2 TRENCH
PANEL DC SUPPLY 5
FEEDER - F3 344BAN-P36
LEVEL-1
EXISTING MDB-2 BUSBAR 2
125VDC N1 - P371 1 BK BK 1 P371
SDB-3 EXISTING
MDB-2 1X1C-50mm² CABLE
41 P 37 MCCB2 TRENCH
PANEL DC SUPPLY 5
FEEDER - F3 344BAN-P37
LEVEL-1
EXISTING MDB-2 BUSBAR 2
125VDC QA1 + P381 1 WH WH 1 P381 -XD1 1
CAP (6XC01BAN) EXISTING
SDB-3 QA1 - P382 2 BK 2C-4mm² BK 2 P382 -XD1 5 CABLE
42 P 38 PROTECTION TRENCH
PANEL DC SUPPLY 25
BUSBAR-1 344BAN-P38
LEVEL-1
NEW SDB MAIN-1
125VDC QA2 + P391 1 WH WH 1 P391 -XD 1
115KV BUS-1 EXISTING
SDB-3 QA2 - P392 2 BK 2C-4mm² BK 2 P392 -XD 5 CABLE
43 P 39 PROTECTION TRENCH
PANEL DC SUPPLY 25
BUSBAR-1 344BAN-P39
LEVEL-1
NEW SDB MAIN-1
125VDC QA3 + P401 1 WH WH 1 P401 -XD 1
115KV BUS-2 EXISTING
SDB-3 QA3 - P402 2 BK 2C-4mm² BK 2 P402 -XD 5 CABLE
44 P 40 PROTECTION TRENCH
PANEL DC SUPPLY 25
BUSBAR-1 344BAN-P40
LEVEL-1
NEW SDB MAIN-1
125VDC QA4 + P411 1 WH WH 1 P411 -XD 1
BREAKER FAIL EXISTING
SDB-3 QA4 - P412 2 BK 2C-4mm² BK 2 P412 -XD 6 CABLE DC SUPPLY DC1, BFR
45 P 41 PROTECTION TRENCH CLOSE & TRIP 1
25
BUSBAR-1 344BAN-P41
LEVEL-1
NEW SDB CB08 (6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 3 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
125VDC QA5 + P421 1 WH WH 1 P421 -XD 1 EXISTING
SDB-3 QA5 - P422 2 BK 2C-4mm² BK 2 P422 -XD 6 FAULT RECORDER 1 CABLE
46 P 42 TRENCH
PANEL DC SUPPLY 28
BUSBAR-1 344BAN-P42
LEVEL-1
NEW SDB
125VDC QA6 + P431 1 WH WH 1 P431 -XD 1 EXISTING
SDB-3 QA6 - P432 2 BK 2C-4mm² BK 2 P432 -XD 6 EVENT RECORDER 1 CABLE
47 P 43 TRENCH
PANEL DC SUPPLY 28
BUSBAR-1 344BAN-P43
LEVEL-1
NEW SDB
125VDC QB1 + P441 1 WH WH 1 P441 -XD 1
CAP (6XC01BAN) EXISTING
SDB-3 QB1 - P442 2 BK 2C-4mm² BK 2 P442 -XD 5 CABLE
48 P 44 PROTECTION TRENCH
PANEL DC SUPPLY 25
BUSBAR-2 344BAN-P44
LEVEL-1
NEW SDB MAIN-2
125VDC QB2 + P451 1 WH WH 1 P451 -XD 1
115KV BUS-1 EXISTING
SDB-3 QB2 - P452 2 BK 2C-4mm² BK 2 P452 -XD 5 CABLE
49 P 45 PROTECTION TRENCH
PANEL DC SUPPLY 25
BUSBAR-2 344BAN-P45
LEVEL-1
NEW SDB MAIN-2
125VDC QB3 + P461 1 WH WH 1 P461 -XD 1
115KV BUS-2 EXISTING
SDB-3 QB3 - P462 2 BK 2C-4mm² BK 2 P462 -XD 5 CABLE
50 P 46 PROTECTION TRENCH
PANEL DC SUPPLY 20
BUSBAR-2 344BAN-P46
LEVEL-1
NEW SDB MAIN-2
125VDC QB4 + P471 1 WH WH 1 P471 -XD 4
BREAKER FAIL EXISTING
SDB-3 QB4 - P472 2 BK 2C-4mm² BK 2 P472 -XD 9 CABLE
51 P 47 PROTECTION TRENCH
DC2, TRIP CIRCUIT 2 25
BUSBAR-2 344BAN-P47
LEVEL-1
NEW SDB CB08 (6XC01BAN)
125VDC QB5 + P481 1 WH WH 1 P481
115KV EXISTING
SDB-3 QB5 - P482 2 BK 2C-4mm² BK 2 P482 CABLE
52 P 48 PCB TRENCH
LOCAL OP. + CTRL SUPPLY 125
BUSBAR-2 344BAN-P48
LEVEL-1
NEW SDB CB08 (6XC01BAN)
125VDC QB6 + P491 1 WH WH 1 P491 -XD 1 EXISTING
SDB-3 QB6 - P492 2 BK 2C-4mm² BK 2 P492 -XD 6 FAULT RECORDER 2 CABLE
53 P 49 TRENCH
PANEL DC SUPPLY 28
BUSBAR-2 344BAN-P49
LEVEL-1
NEW SDB
125VDC QB7 + P501 1 WH WH 1 P501 -XD 1 EXISTING
SDB-3 QB7 - P502 2 BK 2C-4mm² BK 2 P502 -XD 6 DFR SERVER AND GPS PANEL CABLE
54 P 50 TRENCH
PANEL DC SUPPLY 30
BUSBAR-2 344BAN-P50
LEVEL-1
NEW SDB
CT INTERCONNECTION (shielded type)
1S1 I011 1 BK BK 1 I011 XI1 1
RATIO: 100/5
1S2 I012 2 WH 6C-4mm² WH 2 I012 XI1 2 EXISTING
1S3 I013 3 RD 344BAN-I01 RD 3 I013 XI1 3 NEW CABLE CT SECONDARY BOX TO
55 I 01 CONDUIT TRENCH CT MARSHALLING BOX
10
S1 1S4 I014 4 GN GN 4 I014 XI1 4
LEVEL-2
S2 1S5 I015 5 YL YL 5 I015 XI1 5
1S6 I016 6 BR BR 6 I016 XI1 6
2S1 I021 1 BK BK 1 I021 XI2 1
2S2 I022 2 WH 6C-4mm² WH 2 I022 XI2 2 EXISTING
2S3 I023 3 RD 344BAN-I02 RD 3 I023 XI2 3 NEW CABLE CT SECONDARY BOX TO
56 I 02 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I024 4 GN GN 4 I024 XI2 4
LEVEL-2
2S5 I025 5 YL YL 5 I025 XI2 5
CT07 2S6 I026 6 BR BR 6 I026 XI2 6 CT07
(6XC01BAN) 3S1 I031 1 BK BK 1 I031 XI3 1 (6XC01BAN)
3S2 I032 2 WH 6C-4mm² WH 2 I032 XI3 2 EXISTING
3S3 I033 3 RD 344BAN-I03 RD 3 I033 XI3 3 NEW CABLE CT SECONDARY BOX TO
57 I 03 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I034 4 GN GN 4 I034 XI3 4
LEVEL-2
3S5 I035 5 YL YL 5 I035 XI3 5
3S6 I036 6 BR BR 6 I036 XI3 6
4S1 I041 1 BK BK 1 I041 XI4 1
4S2 I042 2 WH 6C-4mm² WH 2 I042 XI4 2 EXISTING
4S3 I043 3 RD 344BAN-I04 RD 3 I043 XI4 3 NEW CABLE CT SECONDARY BOX TO
I 04 10
58 4S4 I044 4 GN GN 4 I044 XI4 4 CONDUIT TRENCH CT MARSHALLING BOX
LEVEL-2
4S5 I045 5 YL YL 5 I045 XI4 5
4S6 I046 6 BR BR 6 I046 XI4 6
PHASE A CT JB MARSHALLING BOX

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 4 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
1S1 I051 1 BK BK 1 I051 XI1 7
RATIO: 100/5
1S2 I052 2 WH 6C-4mm² WH 2 I052 XI1 8 EXISTING
1S3 I053 3 RD RD 3 I053 XI1 9 NEW CABLE CT SECONDARY BOX TO
60 I 05 CONDUIT TRENCH CT MARSHALLING BOX
10
S1 1S4 I054 4 GN 344BAN-I05 GN 4 I054 XI1 10
LEVEL-2
S2 1S5 I055 5 YL YL 5 I055 XI1 11
1S6 I056 6 BR BR 6 I056 XI1 12
2S1 I061 1 BK BK 1 I061 XI2 7
2S2 I062 2 WH 6C-4mm² WH 2 I062 XI2 8 EXISTING
2S3 I063 3 RD 344BAN-I06 RD 3 I063 XI2 9 NEW CABLE CT SECONDARY BOX TO
61 I 06 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I064 4 GN GN 4 I064 XI2 10
LEVEL-2
2S5 I065 5 YL YL 5 I065 XI2 11
CT07 2S6 I066 6 BR BR 6 I066 XI2 12 CT07
(6XC01BAN) 3S1 I071 1 BK BK 1 I071 XI3 7 (6XC01BAN)
3S2 I072 2 WH 6C-4mm² WH 2 I072 XI3 8 EXISTING
3S3 I073 3 RD 344BAN-I07 RD 3 I073 XI3 9 NEW CABLE CT SECONDARY BOX TO
62 I 07 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I074 4 GN GN 4 I074 XI3 10
LEVEL-2
3S5 I075 5 YL YL 5 I075 XI3 11
3S6 I076 6 BR BR 6 I076 XI3 12
4S1 I081 1 BK BK 1 I081 XI4 7
4S2 I082 2 WH WH 2 I082 XI4 8 EXISTING
4S3 I083 3 RD 6C-4mm² RD 3 I083 XI4 9 NEW CABLE CT SECONDARY BOX TO
I 08 10
63 4S4 I084 4 GN 344BAN-I08 GN 4 I084 XI4 10 CONDUIT TRENCH CT MARSHALLING BOX
LEVEL-2
4S5 I085 5 YL YL 5 I085 XI4 11
4S6 I086 6 BR BR 6 I086 XI4 12
PHASE B CT JB MARSHALLING BOX
1S1 I091 1 BK BK 1 I091 XI1 13
RATIO: 100/5
1S2 I092 2 WH 6C-4mm² WH 2 I092 XI1 14 EXISTING
1S3 I093 3 RD 344BAN-I09 RD 3 I093 XI1 15 NEW CABLE CT SECONDARY BOX TO
64 I 09 CONDUIT TRENCH CT MARSHALLING BOX
10
S1 1S4 I094 4 GN GN 4 I094 XI1 16
LEVEL-2
S2 1S5 I095 5 YL YL 5 I095 XI1 17
1S6 I096 6 BR BR 6 I096 XI1 18
2S1 I101 1 BK BK 1 I101 XI2 13
2S2 I102 2 WH 6C-4mm² WH 2 I102 XI2 14 EXISTING
2S3 I103 3 RD RD 3 I103 XI2 15 NEW CABLE CT SECONDARY BOX TO
65 I 10 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I104 4 GN 344BAN-I10 GN 4 I104 XI2 16
LEVEL-2
2S5 I105 5 YL YL 5 I105 XI2 17
CT07 2S6 I106 6 BR BR 6 I106 XI2 18 CT07
(6XC01BAN) 3S1 I111 1 BK BK 1 I111 XI3 13 (6XC01BAN)
3S2 I112 2 WH 6C-4mm² WH 2 I112 XI3 14 EXISTING
3S3 I113 3 RD RD 3 I113 XI3 15 NEW CABLE CT SECONDARY BOX TO
66 I 11 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I114 4 GN 344BAN-I11 GN 4 I114 XI3 16
LEVEL-2
3S5 I115 5 YL YL 5 I115 XI3 17
3S6 I116 6 BR BR 6 I116 XI3 18
4S1 I121 1 BK BK 1 I121 XI4 13
4S2 I122 2 WH WH 2 I122 XI4 14 EXISTING
4S3 I123 3 RD 6C-4mm² RD 3 I123 XI4 15 NEW CABLE CT SECONDARY BOX TO
I 12 10
67 4S4 I124 4 GN 344BAN-I12 GN 4 I124 XI4 16 CONDUIT TRENCH CT MARSHALLING BOX
LEVEL-2
4S5 I125 5 YL YL 5 I125 XI4 17
4S6 I126 6 BR BR 6 I126 XI4 18
PHASE C CT JB MARSHALLING BOX
1S1 I131 1 BK BK 1 I131 XI1 1
1S2 I132 2 WH 6C-4mm² WH 2 I132 XI1 2 EXISTING
1S3 I133 3 RD 344BAN-I13 RD 3 I133 XI1 3 NEW CABLE CT SECONDARY BOX TO
68 I 13 CONDUIT TRENCH CT MARSHALLING BOX
10
1S4 I134 4 GN GN 4 I134 XI1 4
LEVEL-2
1S5 I135 5 YL YL 5 I135 XI1 5
1S6 I136 6 BR BR 6 I136 XI1 6 PE PE
2S1 I141 1 BK BK 1 I141 XI2 1
2S2 I142 2 WH 6C-4mm² WH 2 I142 XI2 2 EXISTING
2S3 I143 3 RD 344BAN-I14 RD 3 I143 XI2 3 NEW CABLE CT SECONDARY BOX TO
69 I 14 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I144 4 GN GN 4 I144 XI2 4
LEVEL-2
2S5 I145 5 YL YL 5 I145 XI2 5
CT09 2S6 I146 6 BR BR 6 I146 XI2 6 PE PE CT09
(6XC01BAN) 3S1 I151 1 BK BK 1 I151 XI3 1 (6XC01BAN)
3S2 I152 2 WH 6C-4mm² WH 2 I152 XI3 2 EXISTING
3S3 I153 3 RD 344BAN-I15 RD 3 I153 XI3 3 NEW CABLE CT SECONDARY BOX TO
70 I 15 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I154 4 GN GN 4 I154 XI3 4
LEVEL-2
3S5 I155 5 YL YL 5 I155 XI3 5
3S6 I156 6 BR BR 6 I156 XI3 6

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 5 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
4S1 I161 1 BK BK 1 I161 XI4 1
4S2 I162 2 WH 6C-4mm² WH 2 I162 XI4 2 EXISTING
4S3 I163 3 RD 344BAN-I16 RD 3 I163 XI4 3 NEW CABLE CT SECONDARY BOX TO
I 16 10
71 4S4 I164 4 GN GN 4 I164 XI4 4 CONDUIT TRENCH CT MARSHALLING BOX
LEVEL-2
4S5 I165 5 YL YL 5 I165 XI4 5
4S6 I166 6 BR BR 6 I166 XI4 6
PHASE A CT JB MARSHALLING BOX
1S1 I171 1 BK BK 1 I171 XI1 7
1S2 I172 2 WH 6C-4mm² WH 2 I172 XI1 8 EXISTING
1S3 I173 3 RD RD 3 I173 XI1 9 NEW CABLE CT SECONDARY BOX TO
72 I 17 CONDUIT TRENCH CT MARSHALLING BOX
10
1S4 I174 4 GN 344BAN-I17 GN 4 I174 XI1 10
LEVEL-2
1S5 I175 5 YL YL 5 I175 XI1 11
1S6 I176 6 BR BR 6 I176 XI1 12 PE PE
2S1 I181 1 BK BK 1 I181 XI2 7
2S2 I182 2 WH 6C-4mm² WH 2 I182 XI2 8 EXISTING
2S3 I183 3 RD 344BAN-I18 RD 3 I183 XI2 9 NEW CABLE CT SECONDARY BOX TO
73 I 18 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I184 4 GN GN 4 I184 XI2 10
LEVEL-2
2S5 I185 5 YL YL 5 I185 XI2 11
CT09 2S6 I186 6 BR BR 6 I186 XI2 12 PE PE CT09
(6XC01BAN) 3S1 I191 1 BK BK 1 I191 XI3 7 (6XC01BAN)
3S2 I192 2 WH 6C-4mm² WH 2 I192 XI3 8 EXISTING
3S3 I193 3 RD 344BAN-I19 RD 3 I193 XI3 9 NEW CABLE CT SECONDARY BOX TO
74 I 19 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I194 4 GN GN 4 I194 XI3 10
LEVEL-2
3S5 I195 5 YL YL 5 I195 XI3 11
3S6 I196 6 BR BR 6 I196 XI3 12
4S1 I201 1 BK BK 1 I201 XI4 7
4S2 I202 2 WH WH 2 I202 XI4 8 EXISTING
4S3 I203 3 RD 6C-4mm² RD 3 I203 XI4 9 NEW CABLE CT SECONDARY BOX TO
I 20 10
75 4S4 I204 4 GN 344BAN-I20 GN 4 I204 XI4 10 CONDUIT TRENCH CT MARSHALLING BOX
LEVEL-2
4S5 I205 5 YL YL 5 I205 XI4 11
4S6 I206 6 BR BR 6 I206 XI4 12
PHASE B CT JB MARSHALLING BOX
1S1 I211 1 BK BK 1 I211 XI1 13
1S2 I212 2 WH 6C-4mm² WH 2 I212 XI1 14 EXISTING
1S3 I213 3 RD 344BAN-I21 RD 3 I213 XI1 15 NEW CABLE CT SECONDARY BOX TO
76 I 21 CONDUIT TRENCH CT MARSHALLING BOX
10
1S4 I214 4 GN GN 4 I214 XI1 16
LEVEL-2
1S5 I215 5 YL YL 5 I215 XI1 17
1S6 I216 6 BR BR 6 I216 XI1 18 PE PE
2S1 I221 1 BK BK 1 I221 XI2 13
2S2 I222 2 WH 6C-4mm² WH 2 I222 XI2 14 EXISTING
2S3 I223 3 RD RD 3 I223 XI2 15 NEW CABLE CT SECONDARY BOX TO
77 I 22 CONDUIT TRENCH CT MARSHALLING BOX
10
2S4 I224 4 GN 344BAN-I22 GN 4 I224 XI2 16
LEVEL-2
2S5 I225 5 YL YL 5 I225 XI2 17
CT09 CT09
2S6 I226 6 BR BR 6 I226 XI2 18 PE PE
(6XC01BAN) (6XC01BAN)
3S1 I231 1 BK BK 1 I231 XI3 13
3S2 I232 2 WH 6C-4mm² WH 2 I232 XI3 14 EXISTING
3S3 I233 3 RD RD 3 I233 XI3 15 NEW CABLE CT SECONDARY BOX TO
78 I 23 CONDUIT TRENCH CT MARSHALLING BOX
10
3S4 I234 4 GN 344BAN-I23 GN 4 I234 XI3 16
LEVEL-2
3S5 I235 5 YL YL 5 I235 XI3 17
3S6 I236 6 BR BR 6 I236 XI3 18
4S1 I241 1 BK BK 1 I241 XI4 13
4S2 I242 2 WH WH 2 I242 XI4 14 EXISTING

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 6 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J EXISTING
4S3 I243 3 RD RD 3 I243 XI4 15 NEW CABLE CT SECONDARY BOX TO
79 I 24 CONDUIT TRENCH CT MARSHALLING BOX
10
4S4 I244 4 GN 6C-4mm² GN 4 I244 XI4 16
LEVEL-2
4S5 I245 5 YL 344BAN-I24 YL 5 I245 XI4 17
PHASE C CT JB 4S6 I246 6 BR BR 6 I246 XI4 18 MARSHALLING BOX
VT INTERCONNECTION (shielded type)
X1 U011 1 RD RD 1 U011 XU1 1
REMOVE X3
X2 U012 2 YL 4C-4.0mm² YL 2 U012 XU1 4 VT-1 SECONDARY BOX TO
80 CONNECTION TO PE U 01 EXISTING
VT MARSHALLING BOX
10
X3 U013 3 BL 344BAN-U01 BL 3 U013 XU1 7 NEW CABLE
4 GN GN CONDUIT TRENCH
LEVEL-2
Y1 U021 1 RD RD 1 U021 XU1 10
REMOVE Y3 CONNECTION
CX(6BS01BAN) Y2 U022 2 YL 4C-4.0mm² YL 2 U022 XU1 13 CX(6BS01BAN) VT-1 SECONDARY BOX TO
81 TO PE U 02 VT MARSHALLING BOX
10
Y3 U023 3 BL 344BAN-U02 BL 3 U023 XU1 16
4 GN GN 4 EXISTING
Z1 U031 1 RD RD 1 U031 XU1 19 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U032 2 YL 4C-4.0mm² YL 2 U032 XU1 22 VT-1 SECONDARY BOX TO
82 TO PE U 03 LEVEL-2
VT MARSHALLING BOX
10
Z3 U033 3 BL 344BAN-U03 BL 3 U033 XU1 25
PHASE A VT JB 4 GN GN 4 MARSHALLING BOX
X1 U041 1 RD RD 1 U041 XU1 2
REMOVE X3
X2 U042 2 YL 4C-4.0mm² YL 2 U042 XU1 5 VT-1 SECONDARY BOX TO
83 CONNECTION TO PE U 04 EXISTING
VT MARSHALLING BOX
10
X3 U043 3 BL 344BAN-U04 BL 3 U043 XU1 8 NEW CABLE
4 GN GN 4 CONDUIT TRENCH
LEVEL-2
Y1 U051 1 RD RD 1 U051 XU1 11
REMOVE Y3 CONNECTION
CX(6BS01BAN) Y2 U052 2 YL 4C-4.0mm² YL 2 U052 XU1 14 CX(6BS01BAN) VT-1 SECONDARY BOX TO
84 TO PE U 05 VT MARSHALLING BOX
10
Y3 U053 3 BL 344BAN-U05 BL 3 U053 XU1 17
4 GN GN 4 EXISTING
Z1 U061 1 RD RD 1 U061 XU1 20 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U062 2 YL 4C-4.0mm² YL 2 U062 XU1 23 VT-1 SECONDARY BOX TO
85 TO PE U 06 LEVEL-2
VT MARSHALLING BOX
10
Z3 U063 3 BL 344BAN-U06 BL 3 U063 XU1 26
PHASE B VT JB 4 GN GN 4 MARSHALLING BOX
X1 U071 1 RD RD 1 U071 XU1 3
REMOVE X3
X2 U072 2 YL 4C-4.0mm² YL 2 U072 XU1 6 VT-1 SECONDARY BOX TO
86 CONNECTION TO PE U 07 EXISTING
VT MARSHALLING BOX
10
X3 U073 3 BL 344BAN-U07 BL 3 U073 XU1 9 PE NEW CABLE
4 GN GN 4 CONDUIT TRENCH
LEVEL-2
Y1 U081 1 RD RD 1 U081 XU1 12
REMOVE Y3 CONNECTION
CX(6BS01BAN) Y2 U082 2 YL 4C-4.0mm² YL 2 U082 XU1 15 CX(6BS01BAN) VT-1 SECONDARY BOX TO
87 TO PE U 08 VT MARSHALLING BOX
10
Y3 U083 3 BL 344BAN-U08 BL 3 U083 XU1 18 PE
4 GN GN 4 EXISTING
Z1 U091 1 RD RD 1 U091 XU1 21 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U092 2 YL 4C-4.0mm² YL 2 U092 XU1 24 VT-1 SECONDARY BOX TO
88 TO PE U 09 LEVEL-2
VT MARSHALLING BOX
10
Z3 U093 3 BL 344BAN-U09 BL 3 U093 XU1 27 PE
PHASE C VT JB 4 GN GN 4 MARSHALLING BOX
X1 U101 1 RD RD 1 U101 XU1 1
REMOVE X3
X2 U102 2 YL 4C-4.0mm² YL 2 U102 XU1 4 VT-2 SECONDARY BOX TO
89 CONNECTION TO PE U 10 EXISTING
VT MARSHALLING BOX
10
X3 U103 3 BL 344BAN-U10 BL 3 U103 XU1 7 NEW CABLE
4 GN GN 4 CONDUIT TRENCH
LEVEL-2
Y1 U111 1 RD RD 1 U111 XU1 10
REMOVE Y3 CONNECTION
CX(6BS02BAN) Y2 U112 2 YL 4C-4.0mm² YL 2 U112 XU1 13 CX(6BS02BAN) VT-2 SECONDARY BOX TO
90 TO PE U 11 VT MARSHALLING BOX
10
Y3 U113 3 BL 344BAN-U11 BL 3 U113 XU1 16
4 GN GN 4 EXISTING
Z1 U121 1 RD RD 1 U121 XU1 19 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U122 2 YL 4C-4.0mm² YL 2 U122 XU1 22 VT-2 SECONDARY BOX TO
91 TO PE U 12 LEVEL-2
VT MARSHALLING BOX
10
Z3 U123 3 BL 344BAN-U12 BL 3 U123 XU1 25
PHASE A VT JB 4 GN GN 4 MARSHALLING BOX

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 7 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
X1 U131 1 RD RD 1 U131 XU1 2
REMOVE X3
X2 U132 2 YL 4C-4.0mm² YL 2 U132 XU1 5 VT-2 SECONDARY BOX TO
92 CONNECTION TO PE U 13 EXISTING
VT MARSHALLING BOX
10
X3 U133 3 BL 344BAN-U13 BL 3 U133 XU1 8 NEW CABLE
4 GN GN 4 CONDUIT TRENCH
LEVEL-2
Y1 U141 1 RD RD 1 U141 XU1 11
REMOVE Y3 CONNECTION
CX(6BS02BAN) Y2 U142 2 YL 4C-4.0mm² YL 2 U142 XU1 14 CX(6BS02BAN) VT-2 SECONDARY BOX TO
93 TO PE U 14 VT MARSHALLING BOX
10
Y3 U143 3 BL 344BAN-U14 BL 3 U143 XU1 17
4 GN GN 4 EXISTING
Z1 U151 1 RD RD 1 U151 XU1 20 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U152 2 YL 4C-4.0mm² YL 2 U152 XU1 23 VT-2 SECONDARY BOX TO
94 TO PE U 15 LEVEL-2
VT MARSHALLING BOX
10
Z3 U153 3 BL 344BAN-U15 BL 3 U153 XU1 26
PHASE B VT JB 4 GN GN 4 MARSHALLING BOX
X1 U161 1 RD RD 1 U161 XU1 3
REMOVE X3
X2 U162 2 YL 4C-4.0mm² YL 2 U162 XU1 6 VT-2 SECONDARY BOX TO
95 CONNECTION TO PE U 16 EXISTING
VT MARSHALLING BOX
10
X3 U163 3 BL 344BAN-U16 BL 3 U163 XU1 9 PE NEW CABLE
GN GN CONDUIT TRENCH
LEVEL-2
Y1 U171 1 RD RD 1 U171 XU1 12
REMOVE Y3 CONNECTION
CX(6BS02BAN) Y2 U172 2 YL 4C-4.0mm² YL 2 U172 XU1 15 CX(6BS02BAN) VT-2 SECONDARY BOX TO
96 TO PE U 17 VT MARSHALLING BOX
10
Y3 U173 3 BL 344BAN-U17 BL 3 U173 XU1 18 PE
GN GN EXISTING
Z1 U181 1 RD RD 1 U181 XU1 21 NEW CABLE
REMOVE Z3 CONNECTION CONDUIT TRENCH
Z2 U182 2 YL 4C-4.0mm² YL 2 U182 XU1 24 VT-2 SECONDARY BOX TO
97 TO PE U 18 LEVEL-2
VT MARSHALLING BOX
10
Z3 U183 3 BL 344BAN-U18 BL 3 U183 XU1 27 PE
PHASE C VT JB GN GN MARSHALLING BOX
ANALOG/MEASURING CABLES (shielded)
METERING
XI1 4 M011 1 RD RD 1 M011 TB-M 1
EXISTING CT FOR
CT07(6XC01BAN) XI1 10 M012 2 WH WH 2 M012 TB-M 2
M 01 115KV CONTROL PANEL EXISTING 6XC01BAN 130
CORE-1 XI1 16 M013 3 BK 4C-6.0mm² BK 3 M013 TB-M 3 NEW CABLE METERING
98 CONDUIT TRENCH
XI1:5 XI1:11 XI1 17 M014 4 GN 344BAN-M01 GN 4 M014 TB-M 4 PE E1/E2/E3 +W1
LEVEL-2
NOTE: CT P1 IS FACING THE BUS, UPPER #'S ARE STAR POINT W/ PE CONNECTION
CT MK IN MCSB PNL; CORE 1; RATIO:100/5
XU2 18 M021 1 RD RD 1 M021
EXISTING VT FOR
CVT(6BS01BAN) XU2 19 M022 2 WH WH 2 M022 EXISTING
M 02 METERING 115KV BUS-1 70
CORE-3 XU2 20 M023 3 BK 4C-6.0mm² BK 3 M023 NEW CABLE
99 PANEL CONDUIT TRENCH
METERING
XU2 21 M024 4 GN 344BAN-M02 GN 4 M024 LEVEL-2
to check if existing cables
NOTE: MCB: Q6 ON, Q5 OFF, CORE-3; RATIO: (115000/R3)/66.4
VT MK are sufficient in length
XU2 18 M031 1 RD RD 1 M031
CVT(6BS02BAN) EXISTING VT FOR
XU2 19 M032 2 WH WH 2 M032
CORE-3 M 03 METERING EXISTING 115KV BUS-2 130
XU2 20 M033 3 BK 4C-6.0mm² BK 3 M033 NEW CABLE METERING
100 PANEL CONDUIT TRENCH
VT MK XU2 21 M034 4 GN 344BAN-M03 GN 4 M034
LEVEL-2
NOTE: MCB: Q6 ON, Q5 OFF, CORE-3; RATIO: (115000/R3)/66.4

M041 1 RD RD 1 M041 TB-M 6


EXISTING EXISTING EXISTING VT FOR
M042 2 WH 4C-4.0mm² WH 2 M042 TB-M 7 NEW CABLE
101 METERING M 04 115KV CONTROL PANEL CONDUIT TRENCH
6XC01BAN 10
M043 3 BK 344BAN-M04 BK 3 M043 TB-M 8 METERING
PANEL LEVEL-2
M044 4 GN GN 4 M051 TB-M 9 E1/E2/E3 +W1
115kV CAPACITOR PROTECTION MAIN 1
XI3 1 M051 1 RD RD 1 M051 XI1 1
CT07(6XC01BAN) CAP (6XC01BAN)
XI3 7 M052 2 YL 4C-6.0mm² YL 2 M052 XI1 2 CT FOR
CORE-3 M 05 PROTECTION EXISTING
C1-M1
145
XI3 13 M053 3 BL 344BAN-M05 BL 3 M053 XI1 3 NEW CABLE
102 XI3:6 XI3:12 XI3 18 M054 4 GN GN 4 M054 XI1 7 MAIN-1 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE BUS, UPPER #'S ARE STAR POINT W/ PE CONNECTION IN CAP REMOVE: LINK XI1:6 TO XI1:7
CT MK PROT M1; CORE 3; RATIO:FULL TAP JMP: XI1:6 TO XI1:8

1S1 M061 1 WH WH 1 M061 XI1 11


uCT(6XCB01BAN) CAP (6XC01BAN) EXISTING CT FOR
1S2 M062 2 BK 2C-6.0mm² BK 2 M062 XI1 12 NEW CABLE
103 CORE-1 M 06 PROTECTION CONDUIT TRENCH
C1-M1 160
344BAN-M06 60
LEVEL-2
CT JB MAIN-1

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 8 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
XU1 2 M071 1 RD RD 1 M071 XU1 1
BREAKER FAIL XU1 4 M072 2 YL YL 2 M072 XU1 2 CAP (6XC01BAN) EXISTING
NEW CABLE VT FOR
104 PROTECTION XU1 6 M073 3 BL 4C-4.0mm² M 07 BL 3 M073 XU1 3 PROTECTION CONDUIT TRENCH C1-M1
10
XU1 8 M074 4 GN 344BAN-M07 GN 4 M074 XU1 4 LEVEL-2
CB08(6XC01BAN) MAIN-1
115kV CAPACITOR PROTECTION MAIN 2
XI4 1 M081 1 RD RD 1 M081 XI1 1
CT07(6XC01BAN) XI4 7 M082 2 YL YL 2 M082 XI1 2 CAP (6XC01BAN) CT FOR
EXISTING 145
CORE-4 XI4 13 M083 3 BL 4C-6.0mm² BL 3 M083 XI1 3 PROTECTION C1-M2
NEW CABLE
105 XI4:6 XI4:12 XI4 18 M084 4 GN 344BAN-M08 M 08 GN 4 M084 XI1 7 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE BUS, UPPER #'S ARE STAR POINT W/ PE CONNECTION IN CAP
PROT M2; CORE 4; RATIO:FULL TAP
REMOVE: LINK XI1:4 TO XI1:5 TO XI1:6 TO XI1:7 MAIN-2
CT MK
2S1 M091 1 WH WH 1 M091 XI1 11
uCT(6XCB01BAN) CAP (6XC01BAN) EXISTING CT FOR
2S2 M092 2 BK 2C-6.0mm² BK 2 M092 XI1 13 NEW CABLE
106 CORE-2 M 09 PROTECTION CONDUIT TRENCH
C1-M2 160
344BAN-M09 REMOVE: LINK XI1:12 TO XI1:13 60
LEVEL-2
CT JB MAIN-2
XU2 11 M101 1 RD RD 1 M101 XU1 1
CVT(6BS02BAN) XU2 12 M102 2 YL YL 2 M102 XU1 2 CAP (6XC01BAN)
EXISTING
CORE-2 XU2 13 M103 3 BL 4C-6.0mm² BL 3 M103 XU1 3 PROTECTION NEW CABLE VT FOR
107 XU2 14 M104 4 GN 344BAN-M10 M 10 GN 4 M104 XU1 4 CONDUIT TRENCH C1-M2
145
LEVEL-2
NOTE: MCCB: Q4 ON, Q3 OFF, CORE-2; RATIO: (115000/R3)/66.4 MAIN-2
VT MK
115kV BUS 1 PROTECTION MAIN 1
M111 1 RD RD 1 M111 XI1 1
115KV BUS-1 CT FOR
6-01CT05BAN M112 2 YL YL 2 M112 XI1 2
PROTECTION EXISTING 6BUS1- M1 75
CORE-2 M113 3 BL 4C-6.0mm² BL 3 M113 XI1 3 NEW CABLE FROM BAY 61
108 M114 4 GN 344BAN-M11 M 11 GN 4 M114 6 MAIN-1
XI1 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 1
CT MK PROT M-1; CORE 2; RATIO:FULL TAP

M121 1 RD RD 1 M121 XI2 1


115KV BUS-1 CT FOR
6-02CT05BAN M122 2 YL YL 2 M122 XI2 2
PROTECTION EXISTING 6BUS1- M1
CORE-2 M123 3 BL 4C-6.0mm² BL 3 M123 XI2 3 NEW CABLE FROM BAY 62
109 M124 4 GN 344BAN-M12 M 12 GN 4 M124 XI2 6 MAIN-1 CONDUIT TRENCH
100
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 1
PROT M-1; CORE 2; RATIO:FULL TAP
CT MK
115kV BUS 2 PROTECTION MAIN 1
M131 1 RD RD 1 M131 XI1 1
115KV BUS-2 CT FOR
6-01CT09BAN M132 2 YL YL 2 M132 XI1 2
PROTECTION EXISTING 6BUS2- M1
CORE-2 M133 3 BL 4C-6.0mm² BL 3 M133 XI1 3 NEW CABLE FROM BAY 61
110 M 13 CONDUIT TRENCH
100
M134 4 GN 344BAN-M13 GN 4 M134 XI1 6 MAIN-1
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 2
CT MK PROT M-1; CORE 2; RATIO:FULL TAP

M141 1 RD RD 1 M141 XI2 1


115KV BUS-2 CT FOR
6-02CT09BAN M142 2 YL YL 2 M142 XI2 2 EXISTING
PROTECTION 6BUS2- M1
CORE-2 M143 3 BL 4C-6.0mm² BL 3 M143 XI2 3 NEW CABLE
111 M 14 CONDUIT TRENCH
FROM BAY 62 125
M144 4 GN 344BAN-M14 GN 4 M144 XI2 6 MAIN-1 LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 2
CT MK PROT M-1; CORE 2; RATIO:FULL TAP

XI3 1 M151 1 RD RD 1 M151 XI3 1


115KV BUS-2
CT09(6XC01BAN XI3 7 M152 2 YL YL 2 M152 XI3 2 CT FOR
PROTECTION EXISTING
CORE-3 XI3 13 M153 3 BL 4C-6.0mm² BL 3 M153 XI3 3 NEW CABLE 6BUS2- M1
112 M 15 145
XI3:6 XI3:12 XI3 18 M154 4 GN 344BAN-M15 GN 4 M154 XI3 6 MAIN-1 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE CAPACITOR, UPPER #'S ARE STAR POINT W/ PE CONNECTION IN
CT MK BUS 2 PROT M-1; CORE 3; RATIO:FULL TAP

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 9 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
115kV BUS 1 PROTECTION MAIN 2
M161 1 RD RD 1 M161 XI1 1
115KV BUS-1 CT FOR
6-01CT05BAN M162 2 YL YL 2 M162 XI1 2
PROTECTION EXISTING 6BUS1- M2
CORE-3 M163 3 BL 4C-6.0mm² BL 3 M163 XI1 3 NEW CABLE FROM BAY 61
113 M 16 75
M164 4 GN 344BAN-M16 GN 4 M164 XI1 6 MAIN-2 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 1
CT MK PROT M-2 CORE 3; RATIO:FULL TAP

M171 1 RD RD 1 M171 XI2 1


115KV BUS-1 CT FOR
6-02CT05BAN M172 2 YL YL 2 M172 XI2 2
PROTECTION EXISTING 6BUS1- M2
CORE-3 M173 3 BL 4C-6.0mm² BL 3 M173 XI2 3 NEW CABLE FROM BAY 62
114 M 17 CONDUIT TRENCH
100
M174 4 GN 344BAN-M17 GN 4 M174 XI2 6 MAIN-2
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 1
CT MK PROT M-2; CORE 3; RATIO:FULL TAP

115kV BUS 2 PROTECTION MAIN 2


M181 1 RD RD 1 M181 XI1 1
CT FOR
6-01CT09BAN M182 2 YL YL 2 M182 XI1 2 115KV BUS-2
EXISTING 6BUS2- M2
CORE-3 M183 3 BL 4C-6.0mm² BL 3 M183 XI1 3 PROTECTION NEW CABLE FROM BAY 61
115 M 18 100
M184 4 GN 344BAN-M18 GN 4 M184 XI1 6 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 2
CT MK PROT M-2; CORE 3; RATIO:FULL TAP MAIN-2

M191 1 RD RD 1 M191 XI2 1


CT FOR
6-02CT09BAN M192 2 YL 4C-6.0mm² YL 2 M192 XI2 2 115KV BUS-2
EXISTING 6BUS2- M2
CORE-3 M193 3 BL 344BAN-M19 BL 3 M193 XI2 3 PROTECTION NEW CABLE FROM BAY 62
116 M 19 125
M194 4 GN GN 4 M194 XI2 6 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE ____, ______#'S ARE STAR POINT W/ PE CONNECTION IN BUS 2
CT MK PROT M-2; CORE 3; RATIO:FULL TAP MAIN-2

XI4 1 M201 1 RD RD 1 M201 XI3 1


CT09(6XC01BAN) XI4 7 M202 2 YL YL 2 M202 XI3 2 115KV BUS-2 CT FOR
EXISTING
CORE-4 XI4 13 M203 3 BL 4C-6.0mm² BL 3 M203 XI3 3 PROTECTION NEW CABLE
6BUS2 M2
117 XI4:6 XI4:12 XI4 18 M204 4 GN 344BAN-M20 M 20 GN 4 M204 XI3 6 CONDUIT TRENCH 145
LEVEL-2
NOTE: CT P1 IS FACING THE CAPACITOR, UPPER #'S ARE STAR POINT W/ PE CONNECTION IN
BUS 2 PROT M-2; CORE 4; RATIO:FULL TAP MAIN-2
CT MK
115kV BREAKER FAILURE PROTECTION
XI2 1 M211 1 RD RD 1 M211 XI1 1
CT07 (6XC01BAN) XI2 7 M212 2 YL YL 2 M212 XI1 2 BREAKER FAIL CT FOR
EXISTING 145
CORE-2 XI2 13 M213 3 BL 4C-6.0mm² BL 3 M213 XI1 3 PROTECTION NEW CABLE BFR-4
118 M 21
XI2:6 XI2:12 XI2 18 M214 4 GN 344BAN-M21 GN 4 M214 XI1 7 CONDUIT TRENCH
LEVEL-2
NOTE: CT P1 IS FACING THE BUS, UPPER #'S ARE STAR POINT W/ PE CONNECTION IN BFR;
CT MK CORE 2; RATIO:FULL TAP CB08(6XC01BAN)
XU2 4 M221 1 RD RD 1 M221 XU1 1
CVT(6BS02BAN) XU2 5 M222 2 YL YL 2 M222 XU1 3 BREAKER FAIL EXISTING

119 CORE-1 XU2 6 M223 3 BL 4C-6.0mm² M 22 BL 3 M223 XU1 5 PROTECTION NEW CABLE VT FOR
145
CONDUIT TRENCH BFR-4
XU2 7 M224 4 GN 344BAN-M22 GN 4 M224 XU1 7 LEVEL-2
VT MK NOTE: MCCB: Q2 ON, Q1OFF, CORE-1; RATIO: (115000/R3)/66.4 CB08(6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 10 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
ANALOG INPUT TO NDME
XU1 1 M231 1 RD RD 1 M231 XU1 1
CAP (6XC01BAN) VT INPUT
XU1 2 M232 2 YL 4C-4.0mm² YL 2 M232 XU1 2 FAULT RECORDER 1 EXISTING
120 PROTECTION M 23 CABLE TRAY
FOR NDME 10
XU1 3 M233 3 BL 344BAN-M23 BL 3 M233 XU1 3 FROM C1-M2
MAIN-2 XU1 4 M234 4 GN GN 4 M234 XU1 4 NEW
XI1 4 M241 1 RD RD 1 M241 XI1 1
CAP (6XC01BAN) CT INPUT
XI1 5 M242 2 YL 4C-6.0mm² YL 2 M242 XI1 2 FAULT RECORDER 1 EXISTING
121 PROTECTION M 24 CABLE TRAY
FOR NDME 10
XI1 6 M243 3 BL 344BAN-M24 BL 3 M243 XI1 3 FROM C1-M2
MAIN-2 XI1 7 M244 4 GN GN 4 M244 XI1 6 NEW
VT ANALOG SIGNALS FROM BUS-1
XU2 18 M251 1 RD RD 1 M251
CVT(6BS01BAN) VT INPUT FOR
XU2 19 M252 2 WH WH 2 M252
CORE-1/2/3 M 25 SYNCHROCHECK/PROTECTION/M 300
XU2 20 M253 3 BK 4C-6.0mm² BK 3 M253 EXISTING ETERING USAGE
122 CABLE TRAY
VT MK XU2 21 M254 4 GN 344BAN-M25 GN 4 M254
NOTE: MCB: Q6 ON, Q5 OFF, CORE-3; RATIO: (115000/R3)/66.4

NDME SIGNAL CABLES


-XR1 1 R011 1 RD RD 1 R011 -XB1 2 + COMMON
-XR1 9 R012 2 YL YL 2 R012 -XB1 31 DIFF. TRIP
115KV BUS-1 -XR1 7 R013 3 BL BL 3 R013 -XB1 32 RELAY FAILURE
SEQUENCE EVENT
PROTECTION R014 4 GN 8C-2.5mm² GN 4 R014 EXISTING
123 R 01 RECORDER CABLE TRAY
10
R015 5 WH 344BAN-R01 WH 5 R015
R016 6 BK BK 6 R016
R017 7 BR BR 7 R017
MAIN-1 R018 8 OR OR 8 R018 NEW
-XR1 1 R021 1 RD RD 1 R021 -XB1 2 + COMMON
-XR1 9 R022 2 YL YL 2 R022 -XB1 31 DIFF. TRIP
115KV BUS-1 -XR1 7 R023 3 BL BL 3 R023 -XB1 32 RELAY FAILURE
SEQUENCE EVENT
PROTECTION R024 4 GN 8C-2.5mm² GN 4 R024 EXISTING
124 R 02 RECORDER CABLE TRAY
10
R025 5 WH 344BAN-R02 WH 5 R025
R026 6 BK BK 6 R026
R027 7 BR BR 7 R027
MAIN-2 R028 8 OR OR 8 R028 NEW
-XR1 1 R031 1 RD RD 1 R031 -XB1 3 + COMMON
-XR1 9 R032 2 YL YL 2 R032 -XB1 31 DIFF. TRIP
115KV BUS-2 -XR1 7 R033 3 BL BL 3 R033 -XB1 32 RELAY FAILURE
SEQUENCE EVENT
PROTECTION R034 4 GN 8C-2.5mm² GN 4 R034 EXISTING
125 R 03 RECORDER CABLE TRAY
10
R035 5 WH 344BAN-R03 WH 5 R035
R036 6 BK BK 6 R036
R037 7 BR BR 7 R037
MAIN-1 R038 8 OR OR 8 R038 NEW
-XR1 1 R041 1 RD RD 1 R041 -XB1 3 + COMMON
-XR1 9 R042 2 YL YL 2 R042 -XB1 31 DIFF. TRIP
115KV BUS-2 -XR1 7 R043 3 BL BL 3 R043 -XB1 32 RELAY FAILURE
SEQUENCE EVENT
PROTECTION R044 4 GN 8C-2.5mm² GN 4 R044 EXISTING
126 R 04 RECORDER CABLE TRAY
10
R045 5 WH 344BAN-R04 WH 5 R045
R046 6 BK BK 6 R046
R047 7 BR BR 7 R047
MAIN-2 R048 8 OR OR 8 R048 NEW
-XR1 1 R051 1 RD RD 1 R051 -XB1 4 '+COMMON
-XR1 10 R052 2 YL YL 2 R052 -XB1 49 BREAKER FAIL START
115KV BREAKER -XR1 11 R053 3 BL BL 3 R053 -XB1 50 BREAKER FAIL TRIP
SEQUENCE EVENT
FAIL PROTECTION -XR1 12 R054 4 GN 8C-2.5mm² GN 4 R054 -XB1 51 EXISTING BFR_AR SUCCESSFUL
127 R 05 RECORDER 10
-XR1 13 R055 5 WH 344BAN-R05 WH 5 R055 -XB1 52 CABLE TRAY BFR_AR NOT READY
-XR1 14 R056 6 BK BK 6 R056 -XB1 53 BFR_DEFINITIVE TRIP
-XR1 16 R057 7 BR BR 7 R057 -XB1 54 BFR_RELAY FAILURE
BFR4 R058 8 OR OR 8 R058 NEW

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 11 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
XR1 1 R061 1 RD RD 1 R061 -XB1 1 +COMMON
XR1 14 R062 2 YL YL 2 R062 -XB1 13 OVERCURRENT
115KV CAPACITOR XR1 9 R063 3 BL BL 3 R063 -XB1 14 OVERCURRENT TRIP
SEQUENCE EVENT
PROTECTION XR1 10 R064 4 GN 8C-2.5mm² GN 4 R064 -XB1 15 EXISTING START UNBALANCE
128 R 06 RECORDER CABLE TRAY
10
XR1 12 R065 5 WH 344BAN-R06 WH 5 R065 -XB1 16 OVERVOLTAGE
XR1 13 R066 6 BK BK 6 R066 -XB1 17 OVERVOLTAGE TRIP
XR1 6 R067 7 BR BR 7 R067 -XB1 18 RELAY FAILURE
MAIN-1 R068 8 OR OR 8 R068 NEW
-XR1 1 R071 1 RD RD 1 R071 -XB1 1 +COMMON
-XR1 12 R072 2 YL YL 2 R072 -XB1 19 OVERCURRENT
115KV CAPACITOR -XR1 7 R073 3 BL BL 3 R073 -XB1 20 OVERCURRENT TRIP
SEQUENCE EVENT
PROTECTION -XR1 8 R074 4 GN 8C-2.5mm² GN 4 R074 -XB1 21 EXISTING START UNBALANCE
129 R 07 RECORDER CABLE TRAY
10
-XR1 10 R075 5 WH 344BAN-R07 WH 5 R075 -XB1 22 OVERVOLTAGE
-XR1 11 R076 6 BK BK 6 R076 -XB1 23 OVERVOLTAGE TRIP
-XR1 6 R077 7 BR BR 7 R077 -XB1 23 RELAY FAILURE
MAIN-2 R078 8 OR OR 8 R078 -XB1 24 NEW
NEW BAY CONTROL & ALARM CABLES
TBK 1 C011 1 RD RD 1 C011 XS2 4 +VE COMMON FROM BFR
TBK 10 C012 2 YL YL 2 C012 XS2 7 CMD CLOSING FROM MCSB
EXISTING TBK 12 C013 3 BL BL 3 C013 XS2 8 CMD OPENING FROM MCSB
BREAKER FAIL EXISTING
115KV CONTROL TBK 8 C014 4 GN 8C-2.5mm² GN 4 C014 XT2 40 PROT LOCK-OUT FOR BLOCK
130 C 01 PROTECTION CABLE 30
PANEL TBK 9 C015 5 WH 344BAN-C01 WH 5 C015 XT2 41 TO MODIFY INTERNAL WIRING TRENCH CLOSING
TBK 14 C016 6 BK BK 6 C016 XS3 21 PSD MODE
C017 7 BR BR 7 C017
E1/E2/E3 +W1 C018 8 OR OR 8 C018 CB08 (6XC01BAN)
XT4 9 C021 1 RD RD 1 C021 X1 695 PHASE A OPEN STATE
XT4 12 C022 2 YL YL 2 C022 X1 697 PHASE B OPEN STATE
XT4 15 C023 3 BL BL 3 C023 X1 699 PHASE C OPEN STATE
BREAKER FAIL 115kV EXISTING
XT4 8 C024 4 GN 8C-2.5mm² GN 4 C024 X1 610 NEW CABLE PHASE A CLOSING W
131 PROTECTION C 02 PCB CONDUIT TRENCH
135
XT4 11 C025 5 WH 344BAN-C02 WH 5 C025 X1 615 PHASE B CLOSING W
LEVEL-3
XT4 14 C026 6 BK BK 6 C026 X1 620 PHASE C CLOSING W
7 BR BR 7
CB08 (6XC01BAN)-BFR 8 OR OR 8 CB08 (6XC01BAN)
XT4 2 C031 1 RD RD 1 C031 X1 688 PHASE A CLOSE STATE
XT4 4 C032 2 YL YL 2 C032 X1 690 PHASE B CLOSE STATE
XT4 6 C033 3 BL BL 3 C033 X1 692 PHASE C CLOSE STATE
BREAKER FAIL 115kV EXISTING
XT4 1 C034 4 GN 8C-2.5mm² GN 4 C034 X1 632 NEW CABLE PHASE A TRIP COIL 1
132 PROTECTION C 03 PCB CONDUIT TRENCH
135
XT4 3 C035 5 WH 344BAN-C03 WH 5 C035 X1 637 PHASE B TRIP COIL 1
LEVEL-3
XT4 5 C036 6 BK BK 6 C036 X1 642 PHASE C TRIP COIL 1
7 BR BR 7
CB08 (6XC01BAN)-BFR 8 OR OR 8 CB08 (6XC01BAN)
PHASE A CLOSE STATE
XT5 2 C041 1 RD RD 1 C041 X1 788
SUPERVISION
XT5 4 C042 2 YL YL 2 C042 X1 790 PHASE B CLOSE STATE
BREAKER FAIL XT5 6 C043 3 BL BL 3 C043 X1 792 115kV EXISTING PHASE C CLOSE STATE
NEW CABLE
133 PROTECTION XT5 1 C044 4 GN 8C-2.5mm² C 04 GN 4 C044 X1 730 PCB CONDUIT TRENCH PHASE A TRIP COIL 2 135
XT5 3 C045 5 WH 344BAN-C04 WH 5 C045 X1 735 LEVEL-3 PHASE B TRIP COIL 2
XT5 5 C046 6 BK BK 6 C046 X1 740 PHASE C TRIP COIL 2
XT3 33 C047 7 BR BR 7 C047 X1 745 -VE COMMON FROM BFR
CB08 (6XC01BAN)-BFR 8 OR OR 8 CB08 (6XC01BAN)
XS3 2 C051 1 RD RD 1 C051 X1 111 X1:211 X1:311 X1:53 +VE COMMON FROM PSD
XS3 25 C052 2 YL YL 2 C052 X1 112 CB PH-A OPEN FOR PSD
XS3 26 C053 3 BL BL 3 C053 X1 212 CB PH-B OPEN FOR PSD
BREAKER FAIL 115kV EXISTING
XS3 27 C054 4 GN 8C-2.5mm² GN 4 C054 X1 312 NEW CABLE CB PH-C OPEN FOR PSD
134 PROTECTION C 05 PCB CONDUIT TRENCH
135
XS3 28 C055 5 WH 344BAN-C05 WH 5 C055 X1 54 CB PH A/B/C CLOSE FOR PSD
LEVEL-3
C056 6 BK BK 6 C056
C057 7 BR BR 7 C057
CB08 (6XC01BAN)-BFR 8 OR OR 8 CB08 (6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 12 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
CB OPEN (DS
X1 31 C061 1 RD RD 1 C061 TBI 17
INTERLOCK)
115kV EXISTING EXISTING
CB OPEN (DS
NEW CABLE
135 PCB X1 32 C062 2 YL C 06 YL 2 C062 TBI 18 115KV CONTROL PANEL CONDUIT TRENCH INTERLOCK)
4C-2.5mm² LEVEL-3
C063 3 BL 344CBN-C06 BL 3 C063 125
CB08(8XC02CBN) C064 4 GN GN 4 C064 E1/E2/E3 +W1
+COMMON
X1:13 X1 11 C071 1 1 C071 TBI 10
(DISCREPANCY SW)
OPEN
X1 12 C072 2 2 C072 TBI 6
CLOSED
X1 14 C073 3 3 C073 TBI 5
+COMMON (ANN)
115kV X1 850 C074 4 4 C074 TBI 11 EXISTING EXISTING
NEW CABLE
136 PCB C 07 115KV CONTROL PANEL CONDUIT TRENCH
135
X1 870 C075 5 12C-2.5mm² 5 C075 TBI 12 LEVEL-3 SF6 LOW ALARM
X1 872 C076 6 344BAN-C07 6 C076 TBI 13 SF6 LOCK-OUT
X1 874 C077 7 7 C077 TBI 14 SPRING DISCHARGE
C078 8 8 C078
C079 9 9 C079
C0710 10 10 C0710
C0711 11 11 C0711
CB08(8XC02CBN) C0712 12 12 C0712 E1/E2/E3 +W1
EXISTING TBK 15 C081 1 RD RD C081 X1 4A 115 kV EXISTING
+VE COMMON (230VAC)
FOR DS LOCAL
115KV CONTROL TBK 17 C082 2 YL 4C-6.0mm² YL C082 X1 4B DISCONNECT NEW CABLE
137 C 08 CONDUIT TRENCH
CLOSING/OPENING 120
PANEL TBK 19 C083 3 BL 344BAN-C08 BL C083 X1 8 SWITCH REM CLOSING CMD
LEVEL-3
E1/E2/E3 +W1 TBK 20 C084 4 GN GN C084 X1 7 DS07 (6XC01BAN) REM OPENING CMD
TBS1.CO
1 C091 1 1 C021 X1 21 X1: 23 X1: 680 X1: 894 +VE COMMON FROM RTU
M
TB-S1 1 C092 2 2 C022 X1 895 CB08(6XC01BAN) LOCAL/REMOTE

TB-S1 2 C093 3 3 C023 X1 22 CB08(6XC01BAN) OPENED

TB-S1 3 C094 4 12C-2.5mm² 4 C024 X1 24 CB08(6XC01BAN) CLOSED


115kV EXISTING
NEW RTU PANEL NEW CABLE
138 C 09 PCB CONDUIT TRENCH
135
TB-S1 5 C095 5 344BAN-C09 5 C025 X1 682 LEVEL-3
CB08(6XC01BAN) SF6 GEN LOCK-OUT

TB-S1 6 C096 6 6 C026 POLE DISCREPANCY


C097 7 7 C027
C028 8 8 C028
C029 9 9 C029
C0210 10 10 C0210
C0211 11 11 C0211
RTU C0212 12 12 C0212 CB08 (6XC01BAN)
TBI 15 C101 1 1 C101 X2 55 +VE COMMON (ANN)

TBI 16 C102 2 2 C102 X2 56 CONTROL VOLTAGE SUPPLY FAIL

TBI 10 C103 3 3 C103 X2 5 X2-7 +COMMON (DISCREPANCY


EXISTING TBI 7 C104 4 12C-2.5mm² 4 C104 X2 8 115 kV EXISTING CLOSED
115KV CONTROL TBI 8 C105 5 344BAN-C10 5 C105 X2 6 DISCONNECT NEW CABLE OPEN
139 C 10 CONDUIT TRENCH 135
PANEL TBI 19 C106 6 6 C106 X2 11 SWITCH DS OPEN (CB
LEVEL-3
TBI 20 C107 7 7 C107 X2 12 INTERLOCK)
TBI 21 C028 8 8 C028 X2 9 DS CLOSE (CB
TBI 22 C029 9 9 C029 X2 10 INTERLOCK)
C0210 10 10 C0210
C0211 11 11 C0211
E1/E2/E3 +W1 C0212 12 12 C0212 DS07 (6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 13 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
+COMMON
TBS1.COM 4 C111 1 RD RD 1 C111 X2 62 X2-1 X2-3
TB-S1 8 C112 2 YL YL 2 C112 X2 59 REMOTE
115 kV EXISTING
TB-S1 9 C113 3 BL BL 3 C113 X2 60 LOCAL
NEW RTU PANEL DISCONNECT NEW CABLE
140 TB-S1 10 C114 4 GN 8C-2.5mm² C 11 GN 4 C114 X2 4 CONDUIT TRENCH DS OPENED 135
SWITCH
TB-S1 11 C115 5 WH 344BAN-C11 WH 5 C115 X2 2 LEVEL-3 DS CLOSED
C116 6 BK BK 6 C116
C117 7 BR BR 7 C117
RTU 8 OR OR 8 0 DS07 (6XC01BAN)
+COMMON
TBK1 1 C121 1 1 C121 TBK 21
TBK1 2 C122 2 2 C122 TBK 22 CB08(6XC01BN) CLOSE CMD

TBK1 4 C123 3 3 C123 TBK 23 CB08(6XC01BN) OPEN CMD

TBK1 5 C124 4 4 C124 TBK 24 +COMMON


TBK1 6 C125 5 12C-2.5mm² 5 C125 TBK 25 DS07(6XC01BN) CLOSE CMD
EXISTING
NEW RTU PANEL TBK1 8 C126 6 344BAN-C12 6 C126 TBK 26 EXISTING DS07(6XC01BN) OPEN CMD
141 C 12 115KV CONTROL PANEL CABLE TRAY 15
TBS1.COM 2 C127 7 7 C127 TBI 23 +COMMON FROM RTU

TB-S1 4 C028 8 8 C028 TBI 24 CB08(6XC01BAN) SF6 LOW ALM

C029 9 9 C029
C0210 10 10 C0210
C0211 11 11 C0211
RTU C0212 12 12 C0212 E1/E2/E3 +W1
TBS1.COM7 C131 1 RD RD 1 C131 XR2 1 +COMMON FROM RTU
TBS1 12 C132 2 YL YL 2 C132 XR2 7 6BS01BN-M1 PROT RLY FAIL
TBS1 13 C133 3 BL BL 3 C133 XR2 15 6BS01BN-M1 PROT AC FAIL
115KV BUS-1
NEW RTU PANEL TBS1 14 C134 4 GN 8C-2.5mm² GN 4 C134 XR2 16 EXISTING 6BS01BN-M1 PROT DC FAIL
142 C 13 PROTECTION CABLE TRAY
15
C135 5 WH 344BAN-C13 WH 5 C135
C136 6 BK BK 6 C136
C137 7 BR BR 7 C137
RTU 8 OR OR 8 M1 PROT PANEL
TBS1.COM8 C141 1 RD RD 1 C141 XR2 1 +COMMON FROM RTU
TBS1 15 C142 2 YL YL 2 C142 XR2 7 6BS01BN-M2 PROT RLY FAIL
TBS1 16 C143 3 BL BL 3 C143 XR2 15 6BS01BN-M2 PROT AC FAIL
115KV BUS-1
NEW RTU PANEL TBS1 17 C144 4 GN 8C-2.5mm² GN 4 C144 XR2 16 EXISTING 6BS01BN-M2 PROT DC FAIL
143 C 14 PROTECTION CABLE TRAY
15
C145 5 WH 344BAN-C14 WH 5 C145
C146 6 BK BK 6 C146
C147 7 BR BR 7 C147
RTU 8 OR OR 8 M2 PROT PANEL
TBS1.COM9 C151 1 RD RD 1 C151 XR2 1 +COMMON FROM RTU
TBS1 18 C152 2 YL YL 2 C152 XR2 7 6BS02BN-M1 PROT RLY FAIL
TBS1 19 C153 3 BL BL 3 C153 XR2 15 6BS02BN-M1 PROT AC FAIL
115KV BUS-2
NEW RTU PANEL TBS1 20 C154 4 GN 8C-2.5mm² GN 4 C154 XR2 16 EXISTING 6BS02BN-M1 PROT DC FAIL
144 C 15 PROTECTION CABLE TRAY
15
C155 5 WH 344BAN-C15 WH 5 C155
C156 6 BK BK 6 C156
C157 7 BR BR 7 C157
RTU 8 OR OR 8 M1 PROT PANEL
TBS1.COM10 C161 1 RD RD 1 C161 XR2 1 +COMMON FROM RTU
TBS1 21 C162 2 YL YL 2 C162 XR2 7 6BS02BN-M2 PROT RLY FAIL
TBS1 22 C163 3 BL BL 3 C163 XR2 15 6BS02BN-M2 PROT AC FAIL
115KV BUS-2
NEW RTU PANEL TBS1 23 C164 4 GN 8C-2.5mm² GN 4 C164 XR2 16 EXISTING 6BS02BN-M2 PROT DC FAIL
145 C 16 PROTECTION CABLE TRAY
135
C165 5 WH 344BAN-C16 WH 5 C165
C166 6 BK BK 6 C166
C167 7 BR BR 7 C167
RTU 8 OR OR 8 M2 PROT PANEL
TBS1.COM11 C171 1 RD RD 1 C171 XR2 1 +COMMON FROM RTU
TBS1 24 C172 2 YL YL 2 C172 XR2 16 BFR RLY FAIL
TBS1 25 C173 3 BL BL 3 C173 XR2 19 BFR RLY AC FAIL
BREAKER FAIL
NEW RTU PANEL TBS1 26 C174 4 GN 8C-2.5mm² GN 4 C174 XR2 20 EXISTING BFR RLY DC FAIL
146 C 17 PROTECTION CABLE TRAY
135
C175 5 WH 344BAN-C17 WH 5 C175
C176 6 BK BK 6 C176
C177 7 BR BR 7 C177
RTU 8 OR OR 8 CB08 (6XC01BAN)-BFR

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 14 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
12
TBS1.COM C181 1 RD RD 1 C181 XR2 1 +COMMON FROM RTU
TBS1 27 C182 2 YL YL 2 C182 XR2 7 6XC01BAN-M1 PROT RLY FAIL
TBS1 28 C183 3 BL BL 3 C183 XR2 15 6XC01BAN-M1 PROT AC FAIL
CAP (6XC01BAN)
NEW RTU PANEL TBS1 29 C184 4 GN 8C-2.5mm² GN 4 C184 XR2 16 EXISTING 6XC01BAN-M1 PROT DC FAIL
147 C 18 PROTECTION CABLE TRAY
135
C185 5 WH 344BAN-C18 WH 5 C185
C186 6 BK BK 6 C186
C187 7 BR BR 7 C187
RTU 8 OR OR 8 M1 PROT PANEL
13
TBS1.COM C191 1 RD RD 1 C191 XR2 1 +COMMON FROM RTU
TBS1 30 C192 2 YL YL 2 C192 XR2 7 6XC01BAN-M2 PROT RLY FAIL
TBS1 31 C193 3 BL BL 3 C193 XR2 15 6XC01BAN-M2 PROT AC FAIL
CAP (6XC01BAN)
NEW RTU PANEL TBS1 32 C194 4 GN 8C-2.5mm² GN 4 C194 XR2 16 EXISTING 6XC01BAN-M2 PROT DC FAIL
148 C 19 PROTECTION CABLE TRAY
135
C195 5 WH 344BAN-C19 WH 5 C195
C196 6 BK BK 6 C196
C197 7 BR BR 7 C197
RTU 8 OR OR 8 M2 PROT PANEL
115KV BUS-1 PROTECTION SIGNALS
C201 1 RD RD 1 C201
115KV BUS-1 EXISTING 6-01CB04BAN BLOCK CLOSING
C202 2 YL 4C-4.0mm² YL 2 C202 EXISTING
149 PROTECTION C 20 115KV CONTROL PANEL CABLE TRAY
20
C203 3 BL 344BAN-C20 BL 3 C203
MAIN-1 C204 4 GN GN 4 C204 EXISTING
C211 1 RD RD 1 C211
115KV BUS-1 EXISTING 6-01CB04BAN BLOCK CLOSING
C212 2 YL 4C-4.0mm² YL 2 C212 EXISTING
150 PROTECTION C 21 115KV CONTROL PANEL CABLE TRAY
20
C213 3 BL 344BAN-C21 BL 3 C213
MAIN-2 C214 4 GN GN 4 C214 EXISTING
C221 1 RD RD 1 C221
115KV BUS-1 EXISTING 6-02CB04BAN BLOCK CLOSING
C222 2 YL 4C-4.0mm² YL 2 C222 EXISTING
151 PROTECTION C 22 115KV CONTROL PANEL CABLE TRAY
20
C223 3 BL 344BAN-C22 BL 3 C223
MAIN-1 C224 4 GN GN 4 C224 EXISTING
C231 1 RD RD 1 C231
115KV BUS-1 EXISTING 6-02CB04BAN BLOCK CLOSING
C232 2 YL 4C-4.0mm² YL 2 C232 EXISTING
152 PROTECTION C 23 115KV CONTROL PANEL CABLE TRAY
20
C233 3 BL 344BAN-C23 BL 3 C233
MAIN-2 C234 4 GN GN 4 C234 EXISTING
XC1 5 C241 1 RD RD 1 C241 INITIATE FROM BP1-M1
XC1 6 C242 2 YL YL 2 C242
XB2 3 C243 3 BL BL 3 C243
115KV BUS-1 BREAKER FAIL INITIATE TO BP1-M1
XB2 15 C244 4 GN 8C-2.5mm² GN 4 C244 EXISTING
153 PROTECTION C 24 PROTECTION CABLE TRAY
10
XC1 7 C245 5 WH 344BAN-C24 WH 5 C245 BLOCK AUTO RECLOSING
XC1 8 C246 6 BK BK 6 C246
C247 7 BR BR 7 C247
MAIN-1 8 OR OR 8 EXISTING BFR(6-01CB04CBN)
XC1 5 C251 1 RD RD 1 C251
115KV BUS-1 BREAKER FAIL INITIATE FROM BP1-M2
XC1 6 C252 2 YL 4C-4.0mm² YL 2 C252 EXISTING
154 PROTECTION C 25 PROTECTION CABLE TRAY
10
XB2 1 C253 3 BL 344BAN-C25 BL 3 C253
INITIATE TO BP1-M2
MAIN-2 XB2 15 C254 4 GN GN 4 C254 EXISTING BFR(6-01CB04CBN)
XC2 5 C261 1 RD RD 1 C261 INITIATE FROM BP1-M1
XC2 6 C262 2 YL YL 2 C262
10
XB2 4 C263 3 BL BL 3 C263
115KV BUS-1 BREAKER FAIL INITIATE TO BP1-M1
XB2 17 C264 4 GN 8C-2.5mm² GN 4 C264 EXISTING
155 PROTECTION C 26 PROTECTION CABLE TRAY
XC2 7 C265 5 WH 344BAN-C26 WH 5 C265 BLOCK AUTO RECLOSING
XC2 8 C266 6 BK BK 6 C266
10
C267 7 BR BR 7 C267
MAIN-1 8 OR OR 8 EXISTING BFR(6-02CB04CBN)
XC2 5 C271 1 RD RD 1 C271
115KV BUS-1 BREAKER FAIL INITIATE FROM BP1-M2
XC2 6 C272 2 YL 4C-4.0mm² YL 2 C272 EXISTING
156 PROTECTION C 27 PROTECTION CABLE TRAY
10
XB2 3 C273 3 BL 344BAN-C27 BL 3 C273 INITIATE TO BP1-M2
MAIN-2 XB2 17 C274 4 GN GN 4 C274 EXISTING BFR(6-02CB04CBN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 15 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
115KV BUS-2 PROTECTION SIGNALS
C281 1 RD RD 1 C281
115KV BUS-2 EXISTING 6-01CB08BAN BLOCK CLOSING
C282 2 YL 4C-4.0mm² YL 2 C282 EXISTING
157 PROTECTION C 28 115KV CONTROL PANEL CABLE TRAY
20
C283 3 BL 344BAN-C28 BL 3 C283
MAIN-1 C284 4 GN GN 4 C284 EXISTING
C291 1 RD RD 1 C291
115KV BUS-2 EXISTING 6-01CB08BAN BLOCK CLOSING
C292 2 YL 4C-4.0mm² YL 2 C292 EXISTING
158 PROTECTION C 29 115KV CONTROL PANEL CABLE TRAY
20
C293 3 BL 344BAN-C29 BL 3 C293
MAIN-2 C294 4 GN GN 4 C294 EXISTING
C301 1 RD RD 1 C301
115KV BUS-2 EXISTING 6-02CB08BAN BLOCK CLOSING
C302 2 YL 4C-4.0mm² YL 2 C302 EXISTING
159 PROTECTION C 30 115KV CONTROL PANEL CABLE TRAY
20
C303 3 BL 344BAN-C30 BL 3 C303
MAIN-1 C304 4 GN GN 4 C304 EXISTING
C311 1 RD RD 1 C311
115KV BUS-2 EXISTING 6-02CB08BAN BLOCK CLOSING
C312 2 YL 4C-4.0mm² YL 2 C312 EXISTING
160 PROTECTION C 31 115KV CONTROL PANEL CABLE TRAY
20
C313 3 BL 344BAN-C31 BL 3 C313
MAIN-2 C314 4 GN GN 4 C314 EXISTING
XC1 5 C321 1 RD RD 1 C321 INITIATE FROM BP2-M1
XC1 6 C322 2 YL YL 2 C322
XB2 3 C323 3 BL BL 3 C323
115KV BUS-2 BREAKER FAIL INITIATE TO BP2-M1
XB2 15 C324 4 GN 8C-2.5mm² GN 4 C324 EXISTING
161 PROTECTION C 32 PROTECTION CABLE TRAY
10
XC1 7 C325 5 WH 344BAN-C32 WH 5 C325
BLOCK AUTO RECLOSING
XC1 8 C326 6 BK BK 6 C326
C327 7 BR BR 7 C327
MAIN-1 8 OR OR 8 EXISTING BFR(6-01CB08CBN)
XC1 5 C331 1 RD RD 1 C331
115KV BUS-2 BREAKER FAIL INITIATE FROM BP2-M2
XC1 6 C332 2 YL 4C-4.0mm² YL 2 C332 EXISTING
162 PROTECTION C 33 PROTECTION CABLE TRAY
10
XB2 1 C333 3 BL 344BAN-C33 BL 3 C333 INITIATE TO BP2-M2
MAIN-2 XB2 15 C334 4 GN GN 4 C334 EXISTING BFR(6-01CB08CBN)
XC2 5 C341 1 RD RD 1 C341 INITIATE FROM BP2-M1
XC2 6 C342 2 YL YL 2 C342
10
XB2 4 C343 3 BL BL 3 C343
115KV BUS-2 BREAKER FAIL INITIATE TO BP2-M1
XB2 17 C344 4 GN 8C-2.5mm² GN 4 C344 EXISTING
163 PROTECTION C 34 PROTECTION CABLE TRAY
XC2 7 C345 5 WH 344BAN-C34 WH 5 C345
BLOCK AUTO RECLOSING
XC2 8 C346 6 BK BK 6 C346
10
C347 7 BR BR 7 C347
MAIN-1 8 OR OR 8 EXISTING BFR(6-02CB08CBN)
XC3 5 C351 1 RD RD 1 C351 XT2 7 INITIATE FROM BP2-M1
XC3 6 C352 2 YL YL 2 C352 XT2 19
10
XB2 5 C353 3 BL BL 3 C353 XT1 13
115KV BUS-2 BREAKER FAIL INITIATE TO BP2-M1
XB2 19 C354 4 GN 8C-2.5mm² GN 4 C354 XT1 33 EXISTING
164 PROTECTION C 35 PROTECTION CABLE TRAY
C355 5 WH 344BAN-C35 WH 5 C355
C356 6 BK BK 6 C356
10
C357 7 BR BR 7 C357
MAIN-1 8 OR OR 8 CB08(6XC01BAN)
XC3 5 C361 1 RD RD 1 C361 XT3 2
INITIATE FROM BP2-M1
XC3 6 C362 2 YL YL 2 C362 XT3 13
10
XB2 4 C363 3 BL BL 3 C363 XT1 14
115KV BUS-2 BREAKER FAIL INITIATE TO BP2-M1
XB2 19 C364 4 GN 8C-2.5mm² GN 4 C364 XT1 34 EXISTING
165 PROTECTION C 36 PROTECTION CABLE TRAY
C365 5 WH 344BAN-C36 WH 5 C365
C366 6 BK BK 6 C366
10
C367 7 BR BR 7 C367
MAIN-2 8 OR OR 8 CB08(6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 16 of 17
FROM WIRE WIRE TO CABLE ROUTE
TERMINAL SIZE TERMINAL 1 2 3 4 PURPOSE LENGTH
ITEM EQUIPMENT MARKING # C C # MARKING EQUIPMENT
J J # TAG # J J J
115KV CAP-1 M1/M2 PROTECTION SIGNALS
XT2 8 C371 1 RD RD 1 C371 XC1 4
INITIATE FROM CAP2-M2
XT2 20 C372 2 YL YL 2 C372 XC1 6
XT1 14 C373 3 BL BL 3 C373 XC2 10 CAP (6XC01BAN) +VE COMMON FROM BFR
BREAKER FAIL
XT1 15 C374 4 GN 8C-2.5mm² GN 4 C374 XC2 11 PROTECTION EXISTING TRIP2 PHASE A
166 PROTECTION C 37 CABLE TRAY
10
XT1 16 C375 5 WH 344BAN-C37 WH 5 C375 XC2 12 TRIP2 PHASE B
XT1 17 C376 6 BK BK 6 C376 XC2 13 TRIP2 PHASE C
XB1 4 C377 7 BR BR 7 C377 XC2 18
CAP M2 OPERATE TO BLOCK AR
CB08(6XC01BAN) XB1 14 C378 8 OR OR 8 C378 XC2 19 MAIN-2
XT2 8 C381 1 RD RD 1 C381 XC1 4
INITIATE FROM CAP2-M1
XT2 20 C382 2 YL YL 2 C382 XC1 6
XT1 14 C383 3 BL BL 3 C383 XC2 10 +VE COMMON FROM BFR
BREAKER FAIL CAP (6XC01BAN)
XT1 15 C384 4 GN 8C-2.5mm² GN 4 C384 XC2 11 EXISTING TRIP2 PHASE A
167 PROTECTION C 38 PROTECTION CABLE TRAY
15
XT1 16 C385 5 WH 344BAN-C38 WH 5 C385 XC2 12 TRIP2 PHASE B
XT1 17 C386 6 BK BK 6 C386 XC2 13 TRIP2 PHASE C
XB1 3 C387 7 BR BR 7 C387 XC2 18 CAP M1 OPERATE TO BLOCK AR
CB08(6XC01BAN) XB1 13 C388 8 OR OR 8 C388 XC2 19 MAIN-1
X1:51 X1 43 C391 1 RD RD 1 C391 XB1 5 +VE COMMON FROM CAP2 M-2
115kV CAP (6XC01BAN)
X1 52 C392 2 YL 4C-2.5mm² YL 2 C392 XB1 25 EXISTING CB OPENED
PCB PROTECTION NEW CABLE
168 X1 44 C393 3 BL 344BAN-C39 C 39 BL 3 C393 XB1 24 CONDUIT TRENCH
CB CLOSED 135
LEVEL-3
CB08(6XC01BN) C394 4 GN GN 4 C394 MAIN-2

X1:41 X1 33 C401 1 RD RD 1 C401 XB1 5 +VE COMMON FROM CAP2 M-1


115kV CAP (6XC01BAN) EXISTING
X1 42 C402 2 YL 4C-2.5mm² YL 2 C402 XB1 25 CB OPENED
PCB PROTECTION NEW CABLE
169 X1 34 C403 3 BL 344BAN-C40 C 40 BL 3 C403 XB1 24 CONDUIT TRENCH
CB CLOSED 135
LEVEL-3
CB08(6XC01BN) C404 4 GN GN 4 C404 MAIN-1
4-20mA Analog signals
-B42LA X1.1 M251 1 1 M251 XI3 1
PHASE A REF CONTACT
-B42LA X1.2 M252 2 2 M252 XI3 2
115kV -B42LB X1.1 M253 3 3 M253 XI3 4 BREAKER FAIL PHASE B REF
4P X 1.0sq.mm EXISTING
PCB -B42LB X1.2 M254 4 4 M254 XI3 5 PROTECTION NEW CABLE CONTACT
170 (TWISTED PAIR CABLE) M 25 PHASE C REF 135
-B42LC X1.1 M255 5 5 M255 XI3 7 CONDUIT TRENCH
LEVEL-4
-B42LC X1.2 M256 6 6 M256 XI3 8 CONTACT
-B123 .+ M257 7 7 M257 XI3 10
TEMP. MONITORING
-B123 .- M258 8 8 M258 XI3 11
CB08(6XC01BN) NO SHIELD WIRE 344BAN-M25 8 SHIELD XI3 12 CB08(6XC01BAN)

0344 BY 7530 K 067 REV.B


BANTAY SS LVIP3 - CABLE AND ROUTING SCHEDULE Sheet 17 of 17