Insoection Notes of Sri N.Vara Prasad, Dy.

CEElTrD/HQ at KIITSS on
18.12.2018

sl. Observations Action By


No.
1 2 Nos. of released power transformers of M/s CGL make of ST.DEE/TrD/SC
13.5/20MVA are lying in the TSS switch yard. &
2 2 Nos. of 21.6/30.24MVA power transformers are ADEE/TrD IDKJ
commissioned by Construction organisation during 20L7-L8.
TR-46 commissioned on 8.4.L7 and TR-47 commissioned on
10.2.18.
3 Yearly maintenance of TR-46 is overdue since April 2018.
However, half-yearly maintenance has been carried out on
17.8.18. Oil sample has not been tested for water content,
resistivity, inter facial tension, Total acidity, flash point and
and sediments durinq the
4 Half-yearly maintenance of TR-47 has been carried out on
21.8.18.
5 In fne TSS up gradation work, all equipment on 132kV side and
on 25kV side connected to transformer have been replaced.
However, equipment connected to feeder CB bays is yet to be

6 In the switch yard old ballast has been removed and new
ballast is yet to be filled.

;'-"'fi-Yk, rl
- -"tri 4;
*6a
e ,
,.4
25kV side
It
\.

;r
I 1.
r !i:

L32
7 CB ald associated equipment connected with patch tripling
work is lyinq in the TSS.
8 Aciditv test kit is not available in the TSS.
9 reeaer cs trippings for the last 4 months are tabulated, below.
CB-229 (BKL side CB-230 (BZA side
2t
2t
16
08
10 For switch yard lighting, 9 Nos. tubular poles are still fitted with ST.DEE/M/SC
4' x 24W, T5 fittinqs, require replacement with LED fittings.
11 Similarly, T5 fittings in Control room are to be replaced with
LED tube liqht fittings.
t2 Counselled the staff available on safety awareness and ST.DEE/TrDlSC
precautions to be taken while working. &
13 But for the yearly maintenance of Power Transformers TR-46, ADEE/TTDIDKJ
all other equipment maintenance schedules have been
completed.

r<\r
'sad)
il re
N.
lrrDlHQ

ffioT qt-q H SOUTH CENTRAL RAILWAY

Headquarters Office,
Electrical Branch,
Rail Nilayam,
Secunderabad - 500025.

Lt. No. E.93/TR/DY.CEE/TrD Date : 19.12.2018

Copy to:

PCEE/SCR : for kind information


CEDE/SCR : for kind information

ST.DEE/TrD/SC: for information and necessary action'

ADEE/TrD /DlQ : for information and necessary action'