Application
Note: NEMA 1 models cannot be retrofitted in the
IMPORTANT: Use this P66 Series Electronic Fan field to obtain the NEMA 3R (Rainproof) rating.
Speed Control only as an operating control. Where
failure or malfunction of the P66 control could lead to A P66 and speed controlled motor can replace On/Off
personal injury or property damage to the controlled fan cycling controls, multiple speed motors, condenser
equipment or other property, additional precautions flood-back systems, temperature fan-speed controls,
must be designed into the control system. and modulating louver systems.
Incorporate and maintain other devices, such as Typical applications include:
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against • computer room air conditioning
failure or malfunction of the P66 control.
• commercial air conditioning
IMPORTANT: Utiliser ce P66 Series Electronic Fan • commercial refrigeration
Speed Control uniquement en tant que dispositif de
contrôle de fonctionnement. Lorsqu'une défaillance The P66 Series controls must be applied only to
ou un dysfonctionnement du P66 control risque de single-phase motors intended for use with a solid-state
provoquer des blessures ou d'endommager motor speed control. An applicable motor must be a
l'équipement contrôlé ou un autre équipement, la single-phase, permanent split-capacitor motor and
conception du système de contrôle doit intégrer des must be:
dispositifs de protection supplémentaires. Veiller
• ball-bearing construction only (Sleeve-bearing
dans ce cas à intégrer de façon permanente d'autres
motors are not acceptable for use with P66
dispositifs, tels que des systèmes de supervision ou
controls.)
d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de • designed to handle non-sinusoidal waveforms
protection en cas de défaillance ou de generated by solid-state motor speed controls
dysfonctionnement du P66 control.
• designed to dissipate the motor heat generated at
The P66 Series Electronic Fan Speed Controls are reduced speed operation
pressure-actuated electronic motor-speed controllers
designed primarily to control condenser fan motors on
Heating, Ventilating, Air Conditioning, and ! CAUTION: Risk of Property Damage.
Refrigeration (HVAC/R) applications (Figure 1). These
controls vary the supply voltage to the fan motor in Use only single-phase Permanent Split-Capacitor
response to the sensed refrigerant pressure, providing (PSC) motors approved by the manufacturer for
direct response to changes in condenser pressure, speed control applications with the P66 control.
regardless of the variations in air delivery curves. Failure to use a single-phase PSC motor may
damage the motor and other property.
P66 controls are available with one or two pressure
sensor inputs. In dual sensor models, the control MISE EN GARDE: Risque De dégâts matériels.
selects the input with the greatest demand.
Utiliser uniquement les moteurs PSC (Permanent
P66 control models are also available with NEMA 3R
Split-Capacitor) monophasés approuvés par le
(Rainproof) enclosures for outdoor applications
fabricant pour les applications de régulation de
(Figure 1). These models come with a plastic
vitesse avec le régulateur P66. L'utilisation d'un
enclosure, appropriate gaskets, and low voltage wire
moteur autre qu'un moteur PSC monophasé risque
leads for 24 VAC power. In addition, the critical high
d'endommager le moteur et de provoquer d'autres
voltage components are encapsulated in a potting
dégâts matériels
compound.
Dimensions
6.75
172
5.33
0.093 135
2.36 6.00
Diameter 152
Capillary
5.26
4.20
134
107
7/16 in.
Valve 20 UNF-2B
3.38
Depressor
86
4.56 0.27
116 7
4.72
1/4 in. Flare 120
!
branchement électrique. Tout contact avec des
CAUTION: Risk of Environmental and composants conducteurs de tensions dangereuses
Property Damage. risque d'entraîner une décharge électrique et de
Avoid sharp bends in the capillary tubes. Sharp provoquer des blessures graves, voire mortelles.
bends can weaken or kink capillary tubes, which
may result in refrigerant leaks or restrictions of flow.
24 24
VAC VAC
L1 L1
M1 M1
L1 P66 L1 P66
Motor Motor
P66_IN-PHASE_WIRRING
R R
Main Main
C C
L2 L2
Capacitor Aux Capacitor Aux
S S
L3 L3
Figure 2: Permanent Split-Capacitor Motor Connections to the P66 Fan Speed Control
(The 24 VAC power supply must be connected in-phase with the motor power supply.)
24 24
VAC VAC
L1 L1
M1 M1
L1 P66 P66
Motor Motor
P66_WIRING_OPT
R R
P66_WIRING
Main L1 Main
C C
L2 L2
Capacitor Aux Aux
S S
Capacitor
Figure 3: Permanent Split-Capacitor Motor Figure 4: Optional Wiring Diagram for Permanent
Connections to the P66 Fan Speed Control Split-Capacitor Motor Connections to the P66
Fan Speed Control
97%
90%
Motor Voltage
10% to 40%
of Line No fan operation
(model specific) in this
pressure range.
Pressure Input
0 Operating Range Operating Range
P66_OP_CHART
350 psig
psig (190/250 psig) Plus 20 or 30 psi*
For further information on model specifications and options, please contact Johnson Controls Application
Engineering at 1-800-275-5676.