Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

1. Location : Station – 05 / 6.

6 KV MCC Panel

Feeder Name : G – 45S

2. Equipment Details:

Make Siemens
3. Type 7SJ61
CT Ratio 75/1A
General Inspection : OK

4. Service Settings:

Phase O/C On CLP


5. I>> ∞ IE>> ∞
TI>> ∞ TIE>> ∞
I> 1.7A IE> 0.5A
TI> 0.06 sec TIE> 0.5 sec
Earth O/C On Unbalance 1/∞ On
IE>> ∞ I2> 0.11A
IE> 0.1A TI2> 0.5 sec
TIE> 0.3 sec I2>> 0.5A
CLP Set up TI2>> ∞
Cold load pickup On Thermal O/L On
Start condition No Current K factor 0.48
CB open time 5 sec Time Constant 2.0 min
Active time 12 sec K Alarm 90%
Stop time ∞ I Alarm 0.75A
CLP phase - Startup Mot On
I>> ∞ Startup Ct 6A
TI>> ∞ Startup time 6.0 sec
I> 3.5A Lock Rotor time 7.0 sec
TI> 0.5sec
Secondary Injection Test:
Measurement:

Ref Injected Current (A) Measured Current in Relay


R 1.0 75
Y 1.0 75
B 1.0 75

5.1 I>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RY 1.7 1.7 0.06 0.07
YB 1.7 1.7 0.06 0.08
BR 1.7 1.7 0.06 0.07

5.2 I>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RY 0.75 0.75 0.06 0.08
YB 0.75 0.75 0.06 0.08
BR 0.75 0.75 0.06 0.07

5.3 IE>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RE 0.1 0.101 0.3 0.30
YE 0.1 0.103 0.3 0.30
BE 0.1 0.101 0.3 0.30

5.4 IE>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RE 0.2 0.201 0.3 0.30
YE 0.2 0.200 0.3 0.31
BE 0.2 0.201 0.3 0.30

5.5 I2>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RY 0.11 0.19 0.5 0.49
YB 0.11 0.19 0.5 0.50
BR 0.11 0.19 0.5 0.49

5.6 I2>:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RY 0.5 0.866 0.5 0.50
YB 0.5 0.866 0.5 0.51
BR 0.5 0.866 0.5 0.50

5.7 Thermal Overload:

Ref Set Current (A) Injected Current (A) K factor Θ Alarm Operating Time (S)
RY 0.75 4.5 0.48 90% 18.27
YB 0.75 4.5 0.48 90% 18.04
BR 0.75 4.5 0.47 90% 18.91

5.8 Startup Motor:

Ref Set Current (A) Injected Current (A) Set Time (S) Operating Time (S)
RY 6.0 6.0 6.0 6.01
YB 6.0 6.0 6.0 6.01
BR 6.0 6.0 6.0 6.01

6. Functional checks: (Whether Operational Checks OK / Not OK / Not Available)

1 Correct operation of appropriate indicator / aux. relay OK


2 Correct operation of output contacts OK
3 Relay cover properly fixing OK
4 Correct operating reset switch OK

7. Comments : Nil.
8. Remarks : Relay found Healthy.