Operating Instructions EN

Roof extract fans


(Translation of the original)

BA-REF 6.0 - 07/2016

RHM FDM

RVM

RDA RDM 3E / FE
BA-REF 6.0 - 07/2016 English

Contents
1.  Revision Index ....................................................................................................................................... EN-2 
2.  About This Operating Manual ............................................................................................................... EN-3 
3.  Designated Use ..................................................................................................................................... EN-5 
4.  Safety .................................................................................................................................................... EN-6 
5.  Product Description ............................................................................................................................... EN-9 
6.  Transport and Storage ........................................................................................................................ EN-11 
7.  Installation ........................................................................................................................................... EN-12 
8.  Electrical Connection........................................................................................................................... EN-14 
9.  Commissioning / Operation ................................................................................................................. EN-16 
10.  Maintenance ........................................................................................................................................ EN-17 
11.  Faults ................................................................................................................................................... EN-18 
12.  Service, Spare Parts and Accessories ................................................................................................ EN-19 
13.  Annex .................................................................................................................................................. EN-20 
EC DECLARATION OF CONFORMITY..................................................................................................... EN-21 
EC DECLARATION OF CONFORMITY..................................................................................................... EN-22 
EC DECLARATION OF CONFORMITY..................................................................................................... EN-23 

German DE-2.... DE-24

Weitere Sprachen auf Anfrage / Further languages on request

1. Revision Index
Table 1-1: Revision index
Revision Date
BA-DV 5.1 – 05/2006 05/2006
BA-DV 5.2 – 03/2009 03/2009
BA-DV 5.3 – 11/2009 11/2009
BA-DV 5.4 – 07/2010 07/2010
BA-DV 5.5 – 01/2011 01/2011
BA-REF 5.6 – 07/2013 07/2013
BA-REF 5.7 – 02/2014 02/2014
BA-REF 5.8 – 05/2014 05/2014
BA-REF 5.9 – 12/2015 12/2015
BA-REF 6.0 – 07/2015 12/2016

EN-2/24
BA-REF 6.0 - 07/2016 English

2. About This Operating Manual


These operating instructions are an integral part of the roof fan.
Nicotra Gebhardt GmbH shall not accept any liability or provide any
warranty cover for primary damage or secondary damage arising as a
consequence of disregarding these operating instructions.
 Read operating manual carefully before use.
 Retain operating manual for entire service life of roof fan.
 Keep operating manual accessible to personnel at all times.
 Pass operating manual on to any subsequent owner or user of roof
fan.
 Insert any supplementary instructions received from the manufacturer
in the operating manual.

2.1. Validity
This operating manual only applies to the roof fans stated on the front
page.

2.2. Target Group


This operating manual is intended for operators and qualified
professionals trained in installation, commissioning, operation,
maintenance and decommissioning.

2.3. Other Applicable Documents


 In addition to reading these instructions, due notice should also be
taken of the following documents and specifications on the roof fan:
- IEC 60364/ - DIN EN ISO 13732-1
- DIN VDE 0100 - Type plate
- DIN EN 60204-1 - Technical catalogue
- DIN EN ISO 13857 - Additional notes on roof fan
- DIN EN ISO 12100 (Warning Signs, Arrow
Indicating Direction of
Rotation)

2.4. Symbols and Markings


2.4.1. Use of Warning Signs

Nature, source and consequences of hazard!


 Steps required to avert danger
Signal word

EN-3/24
BA-REF 6.0 - 07/2016 English

2.4.2. Levels of Danger in Warning Signs


Table 2-1: Levels of danger in warning signs
Symbol / Danger Level Likelihood of Occurrence Consequences of Neglect

Imminent danger Death, serious physical injury


DANGER

Potential danger Death, serious physical injury


WARNING

Potential danger Minor physical injury


CAUTION

CAUTION Potential danger Damage to property

2.4.3. Notes

Note Note giving pointers for easier or safe work.


 Steps required for easier or safe work.

2.4.4. Other Symbols and Markings

Table 2-2: Other symbols and markings


Symbol Meaning
 Requirement for an operation
 Operation with one step
1. ….
2. …. Operation with several steps
3. ….
앫 Bullet point (primary list)
- Bullet point (secondary list)
Accentuation (bold) For emphasis

EN-4/24
BA-REF 6.0 - 07/2016 English

3. Designated Use
3.1. Operating Data / Maximum Ratings

Risk of injury!
 Adhere to technical specifications and permissible limits.
CAUTION

For technical specifications reference should be made to the type plate,


technical data sheet and technical catalogue.
The roof fans are suitable for extracting dust-free air and other non-corrosive
gases or vapours.

Permissible conveyed medium temperatures


Table 3-1: Maximum ratings
Perm. temperature of Max. ambient temp.
Range
conveyed medium on drive motor
RHM 31/F1 -20°C to +40°C
RDA 21 -20°C to +40°C 1)
FDM F1 -20°C to +40°C
+ 40°C
RVM F1 -20°C to +40°C
RDM 3E/FE - 4D/43/63 -20°C to +120°C
RDM 3E/FE - BI/4P/6P -20°C to +60°C
1) = Data depend on model; see full list “Roof fans”.

Examples of incorrect use include the following:


 Extraction of media with impermissibly high or low temperatures
CAUTION  Extraction of corrosive media
 Extraction of very dusty media
 Extraction of potentially explosive media.
Unauthorised operation
 No operation above the indicated rpm (see type plate, data sheet)
 No operation at rpm ranges with increased vibration (resonance)
CAUTION
 No operation at rpm ranges out of permitted fan curve area (stability of
flow pattern)
 No operation if fan becomes polluted
Avoid dynamic load of the impeller.
CAUTION
No frequent alteration of load (stop and go)!

EN-5/24
BA-REF 6.0 - 07/2016 English

4. Safety
4.1. Product Safety
The fans offer a high degree of operational safety and high quality standards
guaranteed by a certified Quality Management System (EN ISO 9001).
Before leaving the factory all the fans are inspected and sealed with a mark
of conformity.
Nevertheless, when operating roof fans supplied by Nicotra Gebhardt GmbH
there can be a risk of death or injury for the user or third parties, and a risk of
damage to the roof fan or other material assets.
 Only use roof fans in perfect working order and as intended, having due
regard for safety, an awareness of hazards and in due compliance with
the operating instructions.
 Arrange immediate repair of any faults which could compromise safety.

The roof extract fans are delivered without inlet guards. If there is a
danger of contact with the impeller owing to the way the fan is installed,
then it is necessary to fit an inlet guard conforming to DIN EN ISO
DANGER
13857 (available as an accessory).
Only then the roof fan can be set in operation!

4.2. Safety Instructions


 The roof fan may only be commissioned, operated and serviced in
compliance with the following instructions:
− Operating instructions
− Warning and information signs on roof fan
− Any other operating and installation instructions pertaining to the
machine
− Terms and requirements relevant to the machine
− Applicable national and regional regulations, especially regarding
health & safety and accident prevention.

4.3. Safety Devices


 Use appropriate safeguards to prevent contact with rotating parts (shafts,
impeller, etc.).
 After installation (and before electrical connection) immediately refit any
guards which have been removed during installation.

CAUTION The suitability of protection devices and their fixtures to the fan have to
be evaluated within the complete security concept of the installation.

EN-6/24
BA-REF 6.0 - 07/2016 English

4.4. Professional Staff


 Installation of roof fan and any work on it to be carried out by skilled
professionals only with due regard to these operating instructions and
any applicable regulations.
 Electrical connection to be carried out by qualified electricians only.

4.5. Protective Gear

Ensure that members of staff are wearing protective gear appropriate to


their deployment and environment.
CAUTION!
The protective clothing is specified below!

4.6. Specific Hazards


4.6.1. Noise Emission
The sound emission expected in normal use of the fan is documented in the
technical lists and should be duly taken into account.
 Wear ear defenders when working near to or on the running fan!

4.6.2. Heavy Loads


The heavy weight of the roof fan and its components entail the following risks
in transit and during installation:
 Risk of being trapped, crushed or cut by moving or toppling machinery
 Danger of falling components
 Do not stand or work under suspended loads
 Wear a hard hat, safety shoes and gloves

4.6.3. Rotating Shafts and Impellers


Objects falling onto rotating shafts and impellers can fly off at an angle and
cause serious injury.
Articles of clothing and hair can get caught in rotating shafts and impellers.
 Do not remove guards during operation
 Do not wear loose-fitting clothing when working near rotating
shafts and impellers
 Wear goggles

Caution electrical hazard!


Electrical potential at intermediate circuit of Driver and power
connections if the permanentmagnet motor rotates!
 do not work at the fan if the impeller/motor is not locked
 lock fan impeller by proper means

EN-7/24
BA-REF 6.0 - 07/2016 English
4.6.4. Hot Surfaces
There is a risk of sustaining burns or scalds on hot surfaces during operation.
 Do not touch the motor during operation
 When the roof fan has stopped wait until the motor has cooled
down
 Wear protective gloves

4.7. Structural Modifications, Spare Parts


Note Unauthorised structural modifications may not be made to the roof fan
without the consent of Nicotra Gebhardt GmbH. Nicotra Gebhardt
GmbH shall not accept liability for any damage arising as a result of
said modifications. Use only genuine spare parts supplied by Nicotra
Gebhardt GmbH.

4.8. Installation and Maintenance


 The following steps should be taken before working on the roof fan:
- Switch off the machine and take measures to prevent it from being
switched back on accidentally.
- Display the following message on a sign:
Do not switch on! Work currently in progress on the machine

4.9. Signs on the Roof Fan


Depending on the model, the type plate and the arrow indicating the direction
of rotation are fitted to the housing or handle for high visibility.
4.9.1. Type Plate
Fig 4-1:
Example type plate

EN-8/24
BA-REF 6.0 - 07/2016 English
4.9.2 Arrow Indicating Direction of Rotation
Fig 4-2:
Arrow indicating direction
of rotation
4.9.3 Terminal Board Circuit Diagram
Fig 4-3: Stuck / inserted in terminal box or stuck on motor bracket.
Example circuit diagram

Example only!

5. Product Description
5.1. General Information on Roof Fans
All the roof fans are delivered ready for connection and are protected
by an outlet guard conforming to DIN EN ISO 13857.
Inlet guards are not fitted as standard.
If there is a danger of contact with the impeller owing to the way the fan
DANGER is installed, then it is necessary to fit an inlet guard conforming to DIN
EN ISO 13857 (available as an accessory).

5.2. Roof Fans with Built-In Motor


5.2.1. RDA 21 genovent
Centrifugal roof fan, with built-in motor, horizontal discharge, made of
galvanised sheet steel.
Outlet guard conforming to DIN EN ISO 13857.

5.3. Roof Fans with Built-On Motor


5.3.1. RVM F1
Centrifugal roof fan, vertical discharge, with standard IEC motor, galvanised
sheet steel V-casing and structure.
Outlet guard conforming to DIN EN ISO 13857.

5.3.2. RDM 3E/FE genovent


Centrifugal roof fan, vertical discharge, with standard IEC motor outside
airstream with external air cooling. Aluminium casing and galvanised sheet
steel structure.
More information on fans with integrated frequency inverter see separate
operation manual BA-ESR_NI-DV.

EN-9/24
BA-REF 6.0 - 07/2016 English
5.3.3. RHM 31/F1
Centrifugal roof fan, horizontal discharge, with standard IEC motor,
galvanised sheet steel cowl and structure.
Outlet guard conforming to DIN EN ISO 13857.

5.3.4. FDM F1
Centrifugal roof fan, highly noise-attenuated design, vertical discharge, with
standard IEC motor, galvanised sheet steel casing and structure
Outlet guard conforming to DIN EN ISO 13857

5.4. Motor Protection


5.4.1. Models RDA 21
The motors used in RDA 21 models are fitted with thermal contacts.
With single-phase motors drawing up to max. 2.5 A the thermal contacts are
connected in sequence externally with the winding.
They switch the motor off automatically when it has reached a set maximum
temperature and switch it back on again automatically when it has cooled
down. In all other motors the winding temperature is monitored by thermal
contacts in combination with a motor protection unit or a contactor assembly.
5.4.2. Models RVM/ RDM3E/ RDMFE/ RHM/ FDM
The motors used in RVM/ RHM/ FDM/ RDM 3E/FE - 4D/43/63 models are
fitted with thermal contacts.
They switch the motor off automatically when it has reached a set maximum
temperature and switch it back on again automatically when it has cooled
down.
The motors used in the variable-speed models RDM 3E/FE - BI/4P/6P are
protected against overload by frequency inverter. The frequency inverter
reacts with a speed reduction up to switch the motor off.

EN-10/24
BA-REF 6.0 - 07/2016 English

6. Transport and Storage


6.1. Packaging
Roof fans are packaged in sturdy cardboard boxes or wooden crates
depending on their size and weight.

6.2. Symbols on Packaging


The following symbols are printed on the cardboard boxes:
Table 6-1: Symbols on packaging

Symbol

Meaning Handle with care Keep dry Top

6.3. Transportation of Roof Fan


Danger of injury from falling components!
 Use tested and appropriate load handling equipment only (see type plate
or data sheet).
 Lift the roof fan by the base frame and/or by the eyelet rings only.
WARNING  Secure load.
 Do not stand under suspended loads.
The casing may be damaged by lifting!
CAUTION The roof fans listed below should always be lifted by the eyelet rings using a
lifting device and spacer crossbar.
Lifting device and spacer crossbar for roof fans:
 RVM F1-7180 and 7190
 RDM FE-7180 and 7190
1. Select means of transport according to weight and dimensions of fan.
2. Lift roof fan at the lifting points provided (see packaging).
3. Secure load using e.g. straps or other aids designed to prevent slipping.
Fig 6-1: 4. Transport roof fan with care and avoid damage caused by e.g. knocks
Lifting device and hitting the ground hard at an angle.

6.4. Storage of Roof Fan


Risk of corrosion!
 Store the fan in its packaging, adding any other protection dictated by its
storage environment.
 Store roof fan in a well-ventilated room only at normal temperatures and
CAUTION
in a non-corrosive atmosphere.
 Store roof fan in conditions registering less than 70 % atmospheric
humidity.
 Adhere to max. permissible temperature of –20°C to +40°C.

EN-11/24
BA-REF 6.0 - 07/2016 English

7. Installation
7.1. Safety Instructions for Installation
 Observe the safety instructions and preventive measures in Chapter 4
and the relevant legal requirements.

7.2. Installation Preparation


 Place of installation suitable for the roof fan in terms of its category,
condition, ambient temperature and environmental media.
 Base level and with sufficient load-bearing capacity.
 Place of installation horizontal (installation permissible on surfaces
with angles of inclination of up to max. 20°).
Note In the case of the roof fans listed below the two discharge openings opposite
each other should be placed at right angles to the pitch.
 RDA 21
 RDM 3E/FE
Correct Incorrect
Fig 7-1:
Installation direction

 Unpack the roof fan carefully.


 Remove all the packaging and dispose of it correctly.

EN-12/24
BA-REF 6.0 - 07/2016 English

7.3. Carrying out Installation


The roof fans are designed for mounting on a base.
There are four holes in the base frame for fixing to the roof base.
Access to the fixing holes:
RHM FDM

Undo fixing bolts on outer casing and remove or raise outer


Remove cowl (7) casing (6) and secure.
RDA 21 RDM 3E /FE RVM F1

Remove side panel (5) Remove side panel (5) Remove cowl (7) und outlet
guard (8)

A Gebhardt ZBS roof base (accessories)


1 Sealing lip (supplied with ZBS roof base)
B Wall base (on site)
2 Sealant (on site)
Fig7-2: Roof base 3 Spacer disc (on site)

1. Place sealing lip (1) and sealing tape (2) on the base (for airtight bed).
2. Place the roof fan complete with mounting plate on the base (A and B).
3. Insert connecting cable but do not connect.
4. Mount sealing washers (4) (plastic) under the base fixing bolts.
5. Tighten base screws evenly.
6. Rotate impeller by hand ensuring that it runs smoothly and freely.
7. If applicable, refit side panels on fan.
Fig 7-3: Sealing
Note Use adjustable connecting sleeves to connect to ducting!
 No forces or vibrations transferred to the roof fan from plant parts!
 The stability against collapse of the fan has been checked!

EN-13/24
BA-REF 6.0 - 07/2016 English
Warping impedes smooth running of impeller and causes fatigue
fractures!
CAUTION  Avoid uneven tightening of base screws.
 Install roof fan so as to guarantee its stability at all times during
operation.

7.4. Installing Safety Devices


Note Conformity with DIN EN ISO 13857 only relates to the safety guard installed
insofar as it is supplied with the fan.
The operator of the system is responsible for full compliance with
DIN EN ISO 13857.
1. Fit guards to protect exposed inlet openings (DIN EN ISO 13857).
2. Design safety devices in such a way that they prevent objects from being
sucked in or from falling in.
3. Ensure that all the mechanical safety devices are fitted.

8. Electrical Connection
8.1. Safety Instructions for Electrical Connection
Caution! Danger of electric shock!
 Observe the safety instructions and preventive measures in Chapter 4
and the relevant legal requirements.
DANGER  EN 60204

8.2. Connecting the Motor


Note All the roof fans are delivered ready for connection. The terminal box and
inspection switch are located under the cowl and housing cover respectively.
The connection diagram is located in the terminal box.
Note The system should always be evaluated in its entirety and specific
application in terms of assessing whether it conforms to the applicable EMC
standards and directives.
This is the responsibility of the customer.
Frequency inverter operation
RDA 21 type roof fans should only be operated using a
CAUTION compatible sinusoidal filter active on all poles between the converter and
motor.
Standard dU/dt filters are not permitted for use on the converter.
Separate EMC protective measures may be required with the combination of
revision switches and frequency converters.

 Current, voltage and frequency of mains supply checked for conformity


with fan type plate and motor rating plate.
 Star-delta or soft start provided for motors with a nominal output >4 kW.

EN-14/24
BA-REF 6.0 - 07/2016 English
 Inspection switch present if applicable.
 Note separate operating instructions BA-ESR_NI DV for devices with
integrated frequency inverter
Table 8-1: 1 Cowl 5 Side panel
2 Cable duct 6 Outer member
General diagram of roof 3 Terminal box 7 Casing
fans 4 Inspection switch 8 Outlet guard
(optional) 9 Integrated frequency
inverter for type
RDM 3E/FE - BI/4P/6P

RHM FDM

2 4 3 1

RDA 21 RDM 3E / FE RVM F1

1. Remove cowl (1).


1.1 . Dismantle outlet guard (RVM) (8)
2. Lock the impeller for highly efficient permanent magnet motors
 Measures taken to prevent roof fan from starting suddenly.
3. Remove side panels on following models
3.1. FDM model - undo outer member (6) and lift off or raise and prop up securely
3.2. RDA 21/ RDM 3E/RDM FE models remove side panel (5)
3.3. RVM: undo casing (7) and lift off or raise prop up securely (large sizes)
4. Run connection cable through cable duct in base frame (2) to terminal box (3) or inspection switch
(4) or frequency inverter (9).
5. On RDM 3E/RDM FE models lay mains power cable loosely to allow the central section to be
swung back easily.
6. In the vicinity of the impeller fix the cable to the support arm with cable clips (RDM 3E/RDM FE),
and fix the cable to the guard and/or handle using cable ties.
7. Refit outer member (FDM) and side panels (RDA 21/ RDM 3E/RDM FE).
8. Connect motor as shown on connection diagram supplied resp. integrated frequency inverter (see
separate operation manual BA-ESR_NI-DV)
9. Fit cowl (1) and outlet guard (RVM and FDM) (8).
10. Ensure that all the electrical safety devices have been fitted and connected.
11. Connect motors with a nominal output >4 kW to star-delta or soft start.

EN-15/24
BA-REF 6.0 - 07/2016 English

8.3. Carrying out a Test Run

Risk of injury from rotating impeller!


 Never reach into the impeller when the fan is open.
DANGER

1. Disconnect motor / frequency inverter from the mains.


2. Take measures to prevent roof fan from being switched on accidentally.
3. Clear the ducting system and fan of all foreign bodies (tools, small parts,
construction waste, etc.).
4. Close all the inspection openings.
5. Switch on fan and check direction of rotation of impeller by comparing it
with the arrow on the fan indicating the direction of rotation.
6. If the direction of rotation is wrong, reverse the polarity of the motor /
frequency inverter having due regard to the safety instructions or by used
of OJ-DV Hterm (see page 33 in separate operating manual BA-ESR_NI-
DV).
7. Once operating speed has been reached measure the current
consumption and compare it with the nominal motor current on the roof
fan type plate or motor rating plate.
8. If there is continuous overload switch the roof fan off immediately.
9. Check that the roof fan runs smoothly and quietly. Ensure that there are
no unusual oscillations or vibrations.
10. Check the motor for any abnormal noises.

9. Commissioning / Operation
The motors are designed for continuous operation S1. If operations involve
more than three starts per hour Nicotra Gebhardt GmbH shall be required to
confirm the suitability of the motor.

9.1. Commissioning the Roof Fan

Risk of injury from rotating parts and hot surfaces!


 Ensure that all the safety devices are fitted!
 Ensure that the impeller has been secured acc. to DIN EN ISO 13857!
DANGER
Incorrect sinusoidal filter may cause material damage!
CAUTION  RDA 21 type roof fans with frequency converters should only be
operated with a compatible sinusoidal filter active on all poles.
Material damage may be caused by overload from excessive starting
CAUTION currents!
 Adhere to the output limits imposed by the power supply company.

Course of action
1. Check working order of all control instruments connected.
2. Switch on roof fan.
EN-16/24
BA-REF 6.0 - 07/2016 English

10. Maintenance
10.1. Safety Instructions for Maintenance
 Observe the safety instructions and preventive measures in Chapter 4
and the relevant legal requirements.
 Follow the directions of the motor supplier and the instructions specified
by the manufacturers of the switches and control units.

10.2. Maintenance Preparation


1. Disconnect motor from the mains.
2. Roof fans fitted with an inspection switch should be switched off by
means of the inspection switch.
3. Take measures to prevent roof fan from being switched on accidentally.
4. Wait until the impeller has stopped.
5. Wait until all hot surfaces have cooled down.
6. Remove any residues from the fan.

10.3. Tilting the RDA/RDM 3E/RDM FE Roof Fan Up / Back


Risk of injury from roof fan falling back suddenly from tilted position!
 Take measures to prevent roof fan from swinging back.
DANGER

Tilting up
 Side panels removed, cowl removed
10
1. Remove screws (8).
9 2. Tilt back central section (10).
3. Secure central section on both sides using screws (8) and nuts in
articulated joint (9).
8

Tilting back (after servicing)


Fig 10-1: Tilting mechanism 1. Prop up tilted roof fan (release locking screws).
2. Remove locking screws from articulated joint (9) and lower roof fan
carefully down out of tilted position.
3. Insert and tighten fixing bolts (8).

EN-17/24
BA-REF 6.0 - 07/2016 English

10.4. Observing Regular Inspection Intervals


In the interests of upkeep and safety we recommend having the operation
and condition of the fans inspected at regular intervals by duly qualified
service personnel or a professional maintenance firm and documenting these
inspections.
The nature and extent of the maintenance work, the service intervals and any
additional work required needs to be specified on a case-by-case basis
depending on the use of the fans and the general conditions on site.

Our servicing and inspection recommendations based on VDMA 24186-1


can be found on our website -Downloads-.
 Maintenance preparation completed
 Roof fan tilted up and secured (RDA/RDM)

Pressure washers can cause damage to property!


CAUTION  Do not use pressure washers (steam jet cleaners) to clean the
equipment.
Maintenance recommendations for roof fans:
 Conduct test run if applicable (see Chapter 8.3).
 Document inspection intervals observed.

If the state of the fan does not allow adapted action for repair it has to
CAUTION
be put out of order immediately and to be replaced if required.

11. Faults
If faults occur during operation which cannot be repaired by maintenance
personnel please contact the service department of Nicotra Gebhardt GmbH.

Roof fan may be damaged by improper operating states!


CAUTION  Switch the roof fan off immediately if permissible limits are exceeded and
in the event of irregularities or faults.

EN-18/24
BA-REF 6.0 - 07/2016 English

12. Service, Spare Parts and Accessories


Nicotra Gebhardt GmbH Tel.: +49 (0) 7942 101 384
Gebhardtstraße 19–25 Fax: +49 (0) 7942 101 385
74638 Waldenburg Mail: service@nicotra-gebhardt.com
Germany www.nicotra-gebhardt.com

12.1. Ordering Spare Parts


 Use only genuine spare parts supplied by Nicotra Gebhardt GmbH as
featured in the list of spare parts.
The use of spare parts supplied by other manufacturers may compromise the
safety of the equipment.
The requirements for CE conformity are no longer met if spare parts supplied
by other manufacturers are fitted.
Nicotra Gebhardt GmbH shall not accept any liability or provide any warranty
cover in respect of primary or secondary damage arising as a consequence
of using spare parts supplied by other manufacturers.
Spare parts can be ordered online at www.gebhardt.de/partshop

12.2. Accessories
Nicotra Gebhardt GmbH has a wide range of accessories for economic and
efficient use of the fans.
Accessories are optional and always need to be ordered separately.
Spare parts should be selected on the basis of the technical specifications or
via our electronic selection program.
Accessories are supplied with separate operating or installation instructions
unless their installation or use are self-explanatory.

EN-19/24
BA-REF 6.0 - 07/2016 English

13. Annex
13.1. Further Documentation Supplied by
Nicotra Gebhardt GmbH
Table 14 1: Further documentation
Type of Documentation File Location
Maintenance and inspection Internet, see link in Chapter 10.4.
recommendations
Electric wiring diagram Connection diagrams:
EC Machinery Directive 2006/42/EC Annex
EU Low Voltage Directive 2014/35/EU Annex
EC-Directive for the setting of Annex
ecodesign requirements for energy-
related products (2009/125/EC)
EU Electromagnetic Compatibility Annex
Directive (2014/30/EU)

EN-20/24
BA-REF 6.0 - 07/2016 English

EC DECLARATION OF CONFORMITY
to EC Machinery Directive (2006/42/EC)
EU Low Voltage Directive (2014/35/EU)

We hereby declare that, as designed, constructed and placed in the stream


of commerce by ourselves, the machinery named below meets the relevant
health and safety requirements specified in the EC Directives listed below.
This declaration shall be null and void if modifications are made to the
machine without consulting us and obtaining our approval.

Designation: Roof fan


Machine type: RHM / RDM 3E/FE / FDM / RDA 21 / RVM
Year of construction/type designation: See type plate

Relevant EC Directives:
EC Machinery Directive (2006/42/EC)
EU Low Voltage Directive (2014/35/EU)

Harmonised standards applied, in particular:


DIN EN ISO 12100 , DIN EN ISO 13857, DIN EN 60204-1

Waldenburg, 20.04.2016

Representative for the documentation: Jeanette von Berg

Head of Production Research & Development Director

i.V. I. Stöbe i.V. Dr. J. Anschütz

For the full list of applied standards and technical specifications see manufacturer’s documentation.

EN-21/24
BA-REF 6.0 - 07/2016 English

EC DECLARATION OF CONFORMITY
We hereby declare that, the machinery named below complies with the eco-
design requirements set by Commission Regulation (EU) No 1253/2014,
according to Annex III, No 1.

Designation: Roof fan

Machine type: RHM / RDM 3E/FE / FDM / RDA 21-EC / RVM

Serial no: See type plate

Year of manufacturing: See type plate

Relevant EC Directives: EC-Directive for the setting of ecodesign


requirements for energy-related products
(2009/125/EC)

Waldenburg, 18.12.2015

Head of Production Research & Development Director

i.V. I. Stöbe i.V. Dr. J. Anschütz

For the full list of applied standards and technical specifications see manufacturer’s documentation.

EN-22/24
BA-REF 6.0 - 07/2016 English

EU DECLARATION OF CONFORMITY
to EU- Directive of Electromagnetic Compatibility (2014/30/EU)

Herewith we declare that the machinery designated below, on the basis of its
design and construction in the form brought onto the market by us is in
accordance with the relevant safety and health requirements of the EU
Council Directive as mentioned below.
If alterations are made to the machinery without prior consultations with us,
this declaration becomes invalid.

Designation:
Roof fan

Machine type:
RDM 3E/FE

Serial no:
See type plate

Year of manufacturing:
See type plate

Relevant EU Directives:
EU-Directive of Electromagnetic Compatibility (2014/30/EU)

Applied harmonized standards, in particular:

RDM 3E/FE - BI/4P/4F/6P: DIN EN 60204-1, DIN EN 61800-3


DIN EN 61000-3-12, DIN EN 61000-3-2

Waldenburg, 20.04.2016

Head of Production Research & Development Director

i.V. I. Stöbe i.V. Dr. J. Anschütz


For the full list of applied standards and technical specifications see manufacturer’s documentation.

EN-23/24
BA-REF 6.0 - 07/2016 English