Application Sheet ADB003 LU2 HQ

Synco™ 200 RLU222


Ventilation Plant, Cooling Basic type A07

Extract air (room) temperature control

Ventilation plant for rooms where the room temperature shall be kept constant by cooling the supply air.

Options  Minimum and maximum limitation of the supply air temperature


 Relative remote setpoint adjuster
 Outside temperature-dependent functions
 2-stage direct expansion evaporator coil
 Comfort/Protection mode changeover

Plant diagram

Function diagrams Extract air temperature control Minimum and maximum limitation Summer compensation
of the supply air temperature

LIM MAX Maximum limitation TOa Outside temperature


LIM MIN Minimum limitation TEx Extract air temperature
SETCOOL Cooling setpoint TSu Supply air temperature
Sp Setpoint Yctl Controller output
SpTSu Supply air temperature setpoin

1-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Description Basic functions Options
of Functions The universal controller (N1) compares the extract air Control of a 2-stage direct expansion evaporator coil
temperature acquired by the extract air temperature The controller’s built-in step switch controls the stages
sensor (B2) (alternatively: room temperature acquired of the direct expansion evaporator coil (M7) via
by the room temperature sensor (B2b / c)) with the switching outputs Q1 and Q2 depending on demand
setpoint and controls the direct expansion evaporator and facilitates control of the refrigerant valve (Y7) via
coil (M7) via switching output Q1 depending on its modulating output Y1. The values for switching the
demand. stages (S1-ON = 33 %, S1-OFF = 1 %, S2-ON = 66 %
When the plant is shut down, the direct expansion and S2-OFF = 33 %) are preset.
evaporator coil is locked.
Summer compensation
This function is activated if an outside sensor or duct
temperature sensor (B9x) is used for acquiring the
outside temperature.
The values SUM-D and WIN-D for setpoint
compensation are set to 0 K as standard. In that case,
no setpoint compensation will take place.
To enable the function, the value of SUM-D must be
preselected (refer to “Parameter settings”).
In that case, to save cooling energy and to avoid
cooling shocks, the extract air temperature setpoint
will be continuously raised (summer compensation)
when the outside temperature rises in the range from
20 °C to 30 °C (SUM-STT = 20 °C and SUM-END =
30 °C preset).
Setpoint compensation acts on the Comfort and the
Economy setpoint.

Minimum and maximum limitation of the supply air


temperature
To activate this function, a supply air temperature
sensor (B1) must be connected to input X2 as a limit
sensor.
If the supply air temperature rises above or drops
below the limit value (LIM MAX = 35 °C, LIM MIN =16
°C preset), the normal control function will be
overridden by the limit function with PI mode.

Relative setpoint adaptation


The controller is supplied with absolute setpoint
adjust-ment activated as standard. This setpoint can
be read-justed by ±3 K. In that case, a remote setpoint
adjuster (R5) is required, which must be connected to
input X4. This setpoint adjuster is used to readjust the
controller's setpoint from a room.

Operating mode selection Comfort / Protection


An external switch (e.g. time switch) can be used (S5)
to switch the controller's operating mode from Comfort
to Protection (PRT), or vice versa. If required, the
controller can be reconfigured to switch between
Comfort and Economy (ECO).

Device list Legend Type of unit Data sheet Product No. Qty.
N1 Universal controller, 2 control loops, 2 analog and 2 relay N3101 RLU222 1
outputs
B2 Duct temperature sensor 400 mm, LG-Ni1000 N1761 QAM2120.040 1

Optional Legend Type of unit Data sheet Product No. Qty.


B1 Duct temperature sensor 400 mm, LG-Ni1000 N1761 QAM2120.040 1
B9 Duct temperature sensor 400 mm, LG-Ni1000 N1761 QAM2120.040 1
R5 Setpoint adjuster, passive, temperature ranges: -20...20 N1991 BSG21.5 1
°C; 20...60 °C; -3...3 K
S5 Digital time switch, 1-channel, with 7-day program N5243 SEH62.1 1
Y7 Modulating refrigerant valves with magnetic actuator, N4714 MVL661..-.. 1
PN40, hermetically sealed, for safety refrigerants
+ For selection of the refrigeration valve, refer to the Data Sheet.

2-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Variants Legend Type of unit Data sheet Product No. Qty.
B1a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B2a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B2b Room temperature sensor LG-Ni1000, DC 0...10 V, QAA.. 1
Pt1000, T1 without setpoint adjuster
B2c Room temperature sensor LG-Ni1000, DC 0...10 V, QAA.. 1
Pt1000, T1 with setpoint adjuster
B9a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B9b Outside sensor LG-Ni1000, DC 0...10 V, Pt1000, T1 QAC.. 1
Y7a Modulating refrigerant valves with magnetic actuator, N4717 MVS661..N 1
PN40, hermetically sealed, for ammonia and safety
refrigerants
Y7b Modulating refrigerant valves with magnetic actuator, N4721 M3FB..LX.. 1
PN40, flanged, hermetically sealed, for refrigeration units
and heat recovery

Connection
diagram

M7 Direct expansion evaporator coil,


1- or 2-stage
K1 Relay for direct expansion
evaporator coil, stage 1
K2 Relay for direct expansion
evaporator coil, stage 2

Parameter settings Parameter Setting Function Remarks

Path: ... > COMMIS > APPL ID


Basic type A07 Select application ADB003 LU2 HQ

Path: ... > COMMIS > PARA > MODE


OPMODE ECO Assign ECO If Comfort / Economy changeover
via S5 is required

Path: ... > COMMIS > PARA > CTLOOP 1


SUM-D 2.0 K Adjust value If summer compensation fo is
required

3-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Engineering  A number of settings are plant-specific and may need adjusting after the initial commissioning of the controller
 The connection diagram does not show all plant interlocks but only those directly connected to the controller or
associated equipment

Configuration Diagram
RLU222 Basic type A07 (ADB003 LU2 HQ)

4-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024