Ventilation plant for rooms where the room temperature shall be kept constant by cooling the supply air.
Plant diagram
Function diagrams Extract air temperature control Minimum and maximum limitation Summer compensation
of the supply air temperature
1-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Description Basic functions Options
of Functions The universal controller (N1) compares the extract air Control of a 2-stage direct expansion evaporator coil
temperature acquired by the extract air temperature The controller’s built-in step switch controls the stages
sensor (B2) (alternatively: room temperature acquired of the direct expansion evaporator coil (M7) via
by the room temperature sensor (B2b / c)) with the switching outputs Q1 and Q2 depending on demand
setpoint and controls the direct expansion evaporator and facilitates control of the refrigerant valve (Y7) via
coil (M7) via switching output Q1 depending on its modulating output Y1. The values for switching the
demand. stages (S1-ON = 33 %, S1-OFF = 1 %, S2-ON = 66 %
When the plant is shut down, the direct expansion and S2-OFF = 33 %) are preset.
evaporator coil is locked.
Summer compensation
This function is activated if an outside sensor or duct
temperature sensor (B9x) is used for acquiring the
outside temperature.
The values SUM-D and WIN-D for setpoint
compensation are set to 0 K as standard. In that case,
no setpoint compensation will take place.
To enable the function, the value of SUM-D must be
preselected (refer to “Parameter settings”).
In that case, to save cooling energy and to avoid
cooling shocks, the extract air temperature setpoint
will be continuously raised (summer compensation)
when the outside temperature rises in the range from
20 °C to 30 °C (SUM-STT = 20 °C and SUM-END =
30 °C preset).
Setpoint compensation acts on the Comfort and the
Economy setpoint.
Device list Legend Type of unit Data sheet Product No. Qty.
N1 Universal controller, 2 control loops, 2 analog and 2 relay N3101 RLU222 1
outputs
B2 Duct temperature sensor 400 mm, LG-Ni1000 N1761 QAM2120.040 1
2-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Variants Legend Type of unit Data sheet Product No. Qty.
B1a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B2a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B2b Room temperature sensor LG-Ni1000, DC 0...10 V, QAA.. 1
Pt1000, T1 without setpoint adjuster
B2c Room temperature sensor LG-Ni1000, DC 0...10 V, QAA.. 1
Pt1000, T1 with setpoint adjuster
B9a Duct temperature sensor LG-Ni1000, DC 0...10 V, Pt1000, QAM21.. 1
T1
B9b Outside sensor LG-Ni1000, DC 0...10 V, Pt1000, T1 QAC.. 1
Y7a Modulating refrigerant valves with magnetic actuator, N4717 MVS661..N 1
PN40, hermetically sealed, for ammonia and safety
refrigerants
Y7b Modulating refrigerant valves with magnetic actuator, N4721 M3FB..LX.. 1
PN40, flanged, hermetically sealed, for refrigeration units
and heat recovery
Connection
diagram
3-4
Technical information in this document might not be up to date and are subject to change. Drawings serve 01.01.2009
illustration purposes only. Siemens is not responsible for the content and any manual modifications. CE1A3101en024
Application Sheet ADB003 LU2 HQ
Synco™ 200 RLU222
Ventilation Plant, Cooling Basic type A07
Engineering A number of settings are plant-specific and may need adjusting after the initial commissioning of the controller
The connection diagram does not show all plant interlocks but only those directly connected to the controller or
associated equipment
Configuration Diagram
RLU222 Basic type A07 (ADB003 LU2 HQ)