Tech Quiz #92

by Jim White, Shermco Industries

This edition of TechQuiz covers medium-voltage circuit breakers. These are very
common devices, at least to NETA technicians. Probably very few “normal” people
would even recognize them as circuit breakers. Test your circuit breaker IQ.

1. When is the danger of an arc flash the greatest for 3. When evaluating insulation-resistance test results on
drawout circuit breakers? a medium-voltage, air-magnetic circuit breaker, what
a. When opening the circuit breaker quantity is evaluated?
b. When closing the circuit breaker a. Percent power factor
c. When racking the circuit breaker in b. Capacitance
d. When racking the circuit breaker out c. Insulation watts-loss
e. Both C and D d. Megohms

2. What electrical test can help determine the condition of 4. What dangerous energy could be released during a
the contact pivot’s lubrication state? vacuum bottle integrity test?
a. Insulation power factor a. Gamma rays
b. Contact resistance b. Nuclear radiation
c. Insulation resistance c. X-rays
d. Vacuum bottle integrity test d. None
e. DC overpotential e. Both A and C

5. What are the insulation power-factor tests typically


performed on a medium-voltage, air-magnetic circuit
tests measures the insulation quality across the arc chute. breaker?
a. Six guarded-specimen tests and three
ity from each pole unit to ground and the ungrounded-specimen
ungrounded-specimen tests
5. a. The guarded-specimen tests measure the insulation qual- b. Three ungrounded-specimen tests and six
yourself and the bottle being tested. grounded-specimen tests
small and can be blocked by putting the circuit breaker between c. Three guarded-specimen tests and six
ing the vacuum bottle integrity test. The amount of radiation is grounded-specimen tests
4. c. X-rays could be released if a vacuum bottle fails dur- d. Six ungrounded-specimen tests and three
guarded-specimen tests
is used when the device being tested is mostly resistive.
3. c. According to Doble® Engineering, insulation watts-loss
can be seen to increase each year the circuit breaker is in service.
the resistance of the pivot increases. If this is trended the resistance
heat created by current passing through the contact structures),
vision. As the lubricants in the contact pivot dry out (from the Jim White is the Training director for Shermco
Industries and the principal Shermco representative
2. b. The contact resistance test is almost like having x-ray on the NFPA 70B committee. Jim is the alternate
there is an increased hazard from arc flash. NETA representative on the NFPA 70E com-
mittee and serves as the NETA representative on
is made or broken (and there are no arc chutes or extinguishers), the IEEE/NFPA Arc-Flash Hazard Work Group
ing out, presents the greatest hazard. Whenever a bus connection (RTPC) Ad Hoc Committee. He served as the
Chairman of the 2008 IEEE Electrical Safety
1. e. Racking the circuit breaker, whether racking in or rack- Workshop. Jim is a NETA Certified Level IV Elec-
Answers trical Testing Technician and a member of the NETA Safety Committee.

www.netaworld.org Summer 2010 NETA WORLD 1